Hytronik Hbir29/sv Pir Standalone Motion Sensor With Bluetooth Mesh Instruction Manual

HBIR29/SV PIR Standalone Motion Sensor with Bluetooth Mesh

Product Information

The PIR Standalone Motion Sensor with One DALI Channel Output is
a versatile motion sensor designed for indoor use. It operates at a
frequency of 2.4 GHz – 2.483 GHz and has a transmission power of 4
dBm. The sensor has a range of 10-30 meters, making it suitable for
various applications.

The sensor utilizes the Mesh protocol for communication and is
compatible with a voltage range of 220-240VAC at 50/60Hz. It has a
low standby power consumption and provides switched power when
motion is detected. The sensor employs a warming-up mechanism to
ensure accurate detection.

With different models available, the detection range varies. The
HBIR29/SV model has a maximum detection range, followed by
HBIR29/SV/R, HBIR29/SV/H, and HBIR29/SV/RH. The sensor offers a
wide detection angle and operates within a specified temperature
range. It has an IP rating for protection against dust and
moisture.

The product complies with relevant standards and certifications,
ensuring its quality and reliability.

Product Usage Instructions

  1. Ensure the sensor is installed in a suitable location within
    the recommended detection range.
  2. Connect the sensor to a power source using the specified
    voltage range.
  3. Refer to the user manual for any additional installation
    instructions specific to your application.
  4. If necessary, adjust the detection angle of the sensor to suit
    your requirements.
  5. When the sensor is powered on, it will enter the warming-up
    phase. Wait for this phase to complete before expecting accurate
    motion detection.
  6. The sensor will provide switched power when motion is detected
    within its range. Connect the DALI channel output to the desired
    device or lighting system.
  7. For any troubleshooting or further information, refer to the
    Hytronik website or contact customer support.

Installation and Instruction Manual

PIR Standalone Motion Sensor with
One DALI Channel Output

Mesh

HBIR29/SV HBIR29/SV/R HBIR29/SV/H HBIR29/SV/RH

1. Technical Specifications

Operation frequency Transmission power Range (Typical indoor) Protocol Operating voltage Stand-by power Switched power Warming-up Sensor principle Detection range (Max.)* HBIR29/SV Detection range (Max.)* HBIR29/SV/R
Detection range (Max.)* HBIR29/SV/H
Detection range (Max.)* HBIR29/SV/RH
Detection angle Operation temperature IP rating
Standard compliance
Certification

2.4 GHz – 2.483 GHz 4 dBm 10~30m
Mesh 220~240VAC 50/60Hz <0.65W (Empty load) Max. 40 devices, 80mA
5s PIR detection Installation Height : 6m Detection Range (Ø) :9m
Installation Height : 6m Detection Range (Ø) :10m Installation height15m (forklift)
12m (person) Detection range (Ø)24m Installation height20m (forklift)
12m (person) Detection range (Ø)40m 360O
Ta:-20OC~+50OC IP20 EN300328, EN301489-1, EN301489-17, EN62479, EN55015, EN61547, EN60669-1, EN60669-2-1, EN62493 CB, CE , EMC, RED, RCM

3. Installation
Mechanical Structure & Dimensions
Ø 66~68mm

1

2

3 4

5

A

B

* Install blind as required

1

2

3

* Install lens as required

6

2. Download the App

7

1

2

Ø 78

62 70.5 75.2

Download on the
APP Store
The access to Silvair apps mobile app: Silvair on the App Store web app: platform.silvair.com
Subject to change without notice.

1. Ceiling (drill hole 66~68mm) 2. Carefully prise off the cable clamps. 3. Make connections to the pluggable
terminal blocks. 4. Insert plug connectors and secure using
the provided cable clamps, then clip terminal covers to the base. 5. Fit detection blind (if required) and desired lens. 6. Clip fascia to body. 7. Bend back springs and insert into ceiling.
HBIR29/SV-20201012-A0

Wire Preparation

0.75 – 2.5mm 7-8mm

Pluggable screw terminal. It is recommended to make connections to the terminal before fitting to the sensor.

Wiring Diagram

L
220~240VAC
N

NL

HBIR29/SV

DA

DA

­ +L N LED LED Driver
DA DA

Max.40pcs

4.Mesh Factory Reset
The device HBIR29/SV can be reset by placing a strong magnet (e.g. N38 neodymium magnet, d=10mm*h=4mm) near the sensor lens for 5 seconds. Once the factory reset is done successfully, the luminaire flashes and then permanent on, then the device is being able to be re-commissioned by SILVAIR app.

5.To Reprovision
Place a strong magnet on the site of the Reset/Hall effect sensor (see diagram 4 below). To trigger the reset the magnet must be held in position for 5 seconds.

Diagram

Status LED Flashes rapidly when unprovisioned. Flashes slowly when provisioned
Module/Antenna placement

Reset zone
Magnet to be replaced for reprovisioning

Note: When change the lens part of HBIR29/SV, please kindly make sure that the lens fits the right location, where the “Reset dot” and “BLE dot”matches with the physical location on the PCB.

Status LED blinking Sequence HBIR29/SV Unprovisioned HBIR29/SV Provisioned Factory reset Factory reset (initial burst) MESH package received Attention (from network)

30ms ON 15ms ON 500ms ON 100ms ON 30ms ON 500ms ON

300ms OFF 2,000ms OFF 1,000ms OFF 1,000ms OFF
50ms OFF 500ms OFF

Subject to change without notice.

HBIR29/SV-20201012-A0

6. Detection Pattern & Optional Accessories

1. HBIR29/SV (Low-bay)
HBIR29/SV: Low-bay flat lens detection pattern for single person @ Ta = 20ºC (Recommended ceiling mount installation height 2.5m-6m)

A: Tangential movement

B: Radial movement

Mount height

2.5m

h = max.6m

h = max.6m

3m


Tangential: max. 9m

# Radial: max. 4m

4m 5m

insensitive

sensitive

insensitive

sensitive

6m

Optional Accessory — Ceiling/Surface Mount Box: HA03

Tangential (A) max 50m2 (Ø = 8m) max 64m2 (Ø = 9m) max 38m2 (Ø = 7m) max 38m2 (Ø = 7m) max 38m2 (Ø = 7m)

Radial (B) max 13m2 (Ø = 4m) max 13m2 (Ø = 4m) max 13m2 (Ø = 4m) max 13m2 (Ø = 4m) max 13m2 (Ø = 4m)

Ø 94 4.2

75 44 66

Optional Accessory — Blind Insert for Blocking Certain Detection Angles
Valid Range

Valid Range

Blind Option 1 — Aisle Detection

Blind Option 2 — 180º Detection

Subject to change without notice.

HBIR29/SV-20201012-A0

2. HBIR29/SV/R (Reinforced Low-bay)
HBIR29/SV/R: Low-bay convex lens detection pattern for single person @ Ta = 20ºC (Recommended ceiling mount installation height 2.5m-6m)

A: Tangential movement

B: Radial movement

Mount height

2.5m

h = max.6m

h = max.6m

3m


Tangential:

max.

10m

# Radial: max. 5m

4m 5m

insensitive

sensitive

insensitive

sensitive

6m

Optional Accessory — Ceiling/Surface Mount Box: HA03

Tangential (A) max 79m2 (Ø = 10m) max 79m2 (Ø = 10m) max 64m2 (Ø = 9m) max 50m2 (Ø = 8m) max 50m2 (Ø = 8m)

Radial (B) max 20m2 (Ø = 5m) max 20m2 (Ø = 5m) max 20m2 (Ø = 5m) max 20m2 (Ø = 5m) max 20m2 (Ø = 5m)

Ø 94 4.2

75 44 66

Optional Accessory — Blind Insert for Blocking Certain Detection Angles
Valid Range

Valid Range

Blind Option 1 — Aisle Detection

Blind Option 2 — 180º Detection

Subject to change without notice.

HBIR29/SV-20201012-A0

3. HBIR29/SV/H (High-bay)
HBIR29/SV/H: High-bay lens detection pattern for forklift @ Ta = 20ºC (Recommended ceiling mount installation height 10m-15m)

A: Tangential movement

B: Radial movement

h = max.15m


Tangential:

max.

24m

h = max.15m
# Radial: max. 16m

insensitive

sensitive

insensitive

sensitive

Mount height 10m 11m 12m 13m 14m 15m

Tangential (A) max 380m2 (Ø = 22m) max 452m2 (Ø = 24m) max 452m2 (Ø = 24m) max 452m2 (Ø = 24m) max 452m2 (Ø = 24m) max 452m2 (Ø = 24m)

Radial (B) max 201m2 (Ø = 16m) max 201m2 (Ø = 16m) max 201m2 (Ø = 16m) max 177m2 (Ø = 15m) max 133m2 (Ø = 13m) max 113m2 (Ø = 12m)

HBIR29/SV/H: High-bay lens detection pattern for single person @ Ta = 20ºC (Recommended ceiling mount installation height 2.5m-12m)

A: Tangential movement

B: Radial movement

Mount height

2.5m

h = max.12m


Tangential:

max.

20m

h = max.12m
# Radial: max. 3m

6m 8m 10m 11m

insensitive

sensitive

insensitive

sensitive

12m

Optional Accessory — Ceiling/Surface Mount Box: HA03

Tangential (A)

Radial (B)

max 50m2 (Ø = 8m)

max 7m2 (Ø = 3m)

max 104m2 (Ø = 11.5m) max 7m2 (Ø = 3m) max 154m2 (Ø = 14m) max 7m2 (Ø = 3m)

max 227m2 (Ø = 17m) max 269m2 (Ø = 18.5m) max 314m2 (Ø = 20m)

max 7m2 (Ø = 3m) max 7m² (Ø = 3m) max 7m² (Ø = 3m)

Ø 94 4.2

75 44 66

Optional Accessory — Blind Insert for Blocking Certain Detection Angles
Valid Range

Valid Range

Blind Option 1 — Aisle Detection
Subject to change without notice.

Blind Option 2 — 180º Detection
HBIR29/SV-20201012-A0

4. HBIR29/SV/RH (Reinforced High-bay with 3-Pyro)
HBIR29/SV/RH: Reinforced high-bay lens detection pattern for forklift @ Ta = 20ºC (Recommended ceiling mount installation height 10m-15m)

A: Tangential movement

B: Radial movement

Mount height 10m

h = max.20m


Tangential:

max.

40m

h = max.20m
# Radial: max. 15m

insensitive

sensitive

insensitive

sensitive

11m 12m 13m 14m 15m 20m

Tangential (A)

Radial (B)

max 346m2 (Ø = 21m) max 660m2 (Ø = 29m)

max 177m2 (Ø = 15m) max 177m2 (Ø = 15m)

max 907m2 (Ø = 34m) max 154m2 (Ø = 14m)

max 962m2 (Ø = 35m) max 154m2 (Ø = 14m)

max 1075m2 (Ø = 37m) max 113m2 (Ø = 12m)

max 1256m2 (Ø = 40m) max 113m2 (Ø = 12m)

max 707m2 (Ø = 30m) max 113m2 (Ø = 12m)

HBIR29/SV/RH: Reinforced high-bay lens detection pattern for single person @ Ta = 20OC (Recommended ceiling mount installation height 2.5m-12m)

A: Tangential movement

B: Radial movement

Mount height

2.5m

h = max.12m


Tangential:

max.

30m

h = max.12m
# Radial: max. 4m

6m 8m 10m 11m

insensitive

sensitive

insensitive

sensitive

12m

Optional Accessory — Ceiling/Surface Mount Box: HA03

Tangential (A) max 38m2 (Ø = 7m) max 154m2 (Ø = 14m) max 314m2 (Ø = 20m) max 531m2 (Ø = 26m) max 615m2 (Ø = 28m) max 707m2 (Ø = 30m)

Radial (B) max 7m2 (Ø = 3m) max 7m2 (Ø = 3m) max 7m2 (Ø = 3m) max 13m2 (Ø = 4m) max 13m2 (Ø = 4m) max 13m2 (Ø = 4m)

Ø 94 4.2

75 44 66

7. Additional Information / Documents
1.Regarding precautions for PIR Sensors installation and operation, please kindly refer to www.hytronik.com/download ->knowledge ->PIR Sensors – Precautions for Product Installation and Operation 2.Data sheet is subject to change without notice. Please always refer to the most recent release on www.hytronik.com/products/bluetooth technology ->Partnership 3.Regarding Hytronik standard guarantee policy, please refer to www.hytronik.com/download ->knowledge ->Hytronik Standard Guarantee Policy

Subject to change without notice.

HBIR29/SV-20201012-A0

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.