SRP-2305N-10CC100-500 10W DALI DT6 NFC Enabled LED Driver
Product Information
Product Name: 10W DALI DT6 NFC Enabled LED
Driver (Constant Current)
Function Introduction: This LED driver is
designed to provide constant current to LED lights. It features NFC
(Near Field Communication) technology, allowing for easy
programming and configuration of the driver using compatible NFC
devices.
Product Data:
- LED Channel: 1
- DC Voltage Output: 3-42V
- Output Current: 200-240VAC/176-280VDC
- Current Accuracy: 0/50/60Hz
- Rated Power: Max. 4.32A at 230VAC; 80s
duration - Input Voltage Range:
200-240VAC/176-280VDC - Frequency Range: 0/50/60Hz
- Power Factor (Typ.): >0.94 @ 230VAC Full
load - Total Harmonic Distortion (THD): 15% (@ full
load / 230VAC) - Efficiency (Typ.): 80% @ 230VAC full load
- AC Current (Typ.): 0.1A @ 230VAC
- Inrush Current (Typ.): Max. 4.32A at 230VAC;
80s duration - Leakage Current: < 5mA /230VAC
- Standby Power Consumption: 0.5W
- Dimming Interface: DALI Device Type 6 (DALI
consumption < 2mA)/ AC Push - Dimming Range: 0.01%-100%@ Max current
- Dimming Method: Amplitude/CCR dimming
- Dimming Curve: Linear/Logarithmic
optional - Safety Standards: EN61347-1, EN61347-2-13
- Withstand Voltage: I/P-O/P: 3.75KVAC
- Isolation Resistance: I/P-O/P: 100M Ohms /
500VDC / 25 / 70% RH - EMC Emission: En55015, EN61000-3-2,
EN61000-3-3 - EMC Immunity: En61547,
EN61000-4-2,3,4,5,6,8,11 - MTBF: 191350H, MIL-HDBK-217F @ 230VAC full
load and 25 ambient temperature - Dimension: 101x36x25mm (L*W*H)
- Warranty: 5 Years
Product Usage Instructions
Operation with DALI Master:
- Make sure to read the user manuals of compatible DALI Masters
for specific operations. - With the DALI master, assign a DALI address to the LED driver.
Each channel output requires a separate DALI address.
Operation with NFC Programming devices:
- Follow the wiring diagram and power on the DALI system.
- Before powering on the DALI devices, it is recommended to set
the parameters. - Ensure that your mobile phone or tablet has NFC function and is
enabled. - Download the SR NFC Tool app from the App Store or Google
Play. - Open the app and tap “+” to add DALI devices.
- If you are unable to download the SR NFC Tool app, please
contact us for assistance. - Add the device and give it a name.
- Unlock the device and enter the parameters configuring
page. - Configure the desired settings based on your requirements.
- Save the selected configuration via NFC and power on the
device.
Tips:
- NFC function does not require any power driver.
- Many functions can be configured using NFC. Check your desired
functions. - All of our DALI drivers perform best when used with our DALI
master/gateway.
10W DALI DT6 NFC Enabled LED Driver(Constant Current)
2
Important: Read All Instructions Prior to Installation Function introduction
AC/DC power input
DALI signal input AC Push input
DALI INPUT
INPUT
L N
DA
DA DALI Dimmable Driver
–
LED OUTPUT
LED Output
Product Data
LED Channel
DC Voltage
Output
Current Current Accuracy
Rated Power
Input
Voltage Range Frequency Range
Power Factor (Typ.) Total Harmonic Distortion Efficiency (Typ.)
AC Current (Typ.) Inrush Current (Typ.)
Leakage Current
Standby Power Consumption
Anti Surge
Dimming Interface
Control
Dimming Range Dimming Method
Dimming Curve
1
3-42V
100-500mA via NFC setting; Min.current gear lower to 0.1mA ±3%( ±1%@Certain full load) @ full load Max. 10W
200-240VAC/176-280VDC 0/50/60Hz
> 0.94 @ 230VAC Full load THD 15% (@ full load / 230VAC)
80% @ 230VAC full load 0.1A @ 230VAC
Max. 4.32A at 230VAC; 80s duration < 5mA /230VAC 0.5W L-N:2KV
DALI Device Type 6 (DALI consumption < 2mA)/ AC Push 0.01%-100%@ Max current
Amplitude/CCR dimming Linear/ Logarithmic optional
Short Circuit
Yes, recovers automatically after fault condition is removed
Protection
Over Current
Yes, recovers automatically after fault condition is removed
Over Temperature
Yes, recovers automatically after temperature drop
Working Temp.
-25 ~ +45
Max. Case Temp. Environment
Working Humidity
Storage Temp. & Humidity
Safety Standards
TC=85 (Ta=”45″) 10% ~ 95% RH non-condensing -40 ~ +80, 10% ~ 95% RH
EN61347-1, EN61347-2-13
Safety & EMC
Withstand Voltage Isolation Resistance
EMC Emission
I/P-O/P: 3.75KVAC I/P-O/P: 100M Ohms / 500VDC / 25 / 70% RH
En55015, EN61000-3-2, EN61000-3-3
EMC Immunity
En61547, EN61000-4-2,3,4,5,6,8,11
Others
MTBF
Dimension Warranty
191350H, MIL-HDBK-217F @ 230VAC full load and 25 ambient temperature
101x36x25mm (L*W*H) 5 Years
· In compliance with IEC 62386-101:2014, IEC 62386-102:2014, IEC 62386-207 Ed2 · Built-in DALI-2 interface, DALI DT6 device · Dimmable LED driver. Max. output power 10W · 100-500mA current selectable via NFC program tool. Min.current gear lower to 0.1mA · DALI Address/Group/Scene setting via NFC program tool. · Class power supply, full isolated plastic case · High power factor and efficiency · To switch and dim LED lighting luminaries · Amplitude/CCR dimming, smooth and deep dimming · Compatible with universal DALI masters that support DT6 commands · Error report function · IP20 rating, suitable for indoor LED lighting applications · 5 years warranty
Safety & Warnings
· DO NOT install with power applied to the device. · DO NOT expose the device to moisture.
Operation
With DALI master
1. DALI Address 1 DALI address for 1 channel output are assigned by DALI Master controller automatically, please refer to user manuals of compatible DALI Masters for specific operations.
With NFC Programming devices Note 1) Do wiring according to the wiring diagram and power on the DALI system . 2) Recommend setting parameters without power-on the DALI devices . 2) Please make sure your mobile phone has NFC function and enable it . Working with “SR NFC Tool” APP Step 1: Download the APP (searching “SR NFC Tool” from App Store and Google Play) .
Then open the APP .
Tap “+” to add DALI devices
Download “SR NFC Tool ”
Note: 1. Please Make sure that you have enabled NFC function with your mobile phone/ tablet . 2. Please Make sure that the “NFC position” is matched. 3. Please do not power on the device before setting. 4. If you can’t download “SR NFC Tool”. Please contact with us.
Step 2: Add device, and name it as you wish.
Step 3: Unlock device, enter parameters configuring page.
Locked
Unlock it
Note: 1. You have to unlock the device then do some settings 2. Only when the corresponding function is selected, the function interface will be displayed.
Step 4: Few parameter interface, you can choose the setting based on your requirements.
Step 5: After setting, please save the selected configuration via NFC and power on the device.
Tips
1. NFC function doesn’t require any power driver. 2. Many functions can be configured by NFC. Kindly check your desired functions. 3. All of our DALI drivers are in the best performance within our DALI master/ gateway.
Wiring Diagram
1. With DALI bus 1With single color LED luminarie
DALI Bus
LN
INPUT
DALI INPUT
DA DA
L
N DALI Dimmable Driver
–
LED
LED OUTPUT
LED OUTPUT
2. With PUSH dimmer
L N
AC PUSH SWITCH
INPUT
DALI INPUT
DA DA
L
N DALI Dimmable Driver
–
LED
AC Push Function
1) Click the button to switch ON/OFF 2) Press and hold down the button to increase or decrease light intensity to desired level and release it, then repeat the operation to adjust light intensity to opposite direction. The dimming range is from 1% to 100%.
Product Dimension
Operating window
Output voltage [V]
42 35 28 21 14 7
0
Dimming Curve
ULED (max), V
ULED (min), V
0,10 0,20 0,30 0,40 0,50 0,60 0,70 0,80 Output current [A]
Note: Test data under 500mA gear
Driver Performance
Note: Test data under 500mA gear
Driver Performance
Note: Test data under 500mA gear
MCB Load Quantity
Module Number
Ipeak Twidth
Max.quantity of LED Driver per MCB
B10 B13 B16 B20 B25 C10 C13 C16 C20 C25 D10 D13 D16 D20 D25
SRP-2305N-10CC100-500 4.32A 80s 34 45 55 69 86 57 75 920 115 144 80 104 128 160 200
SRP-2309N-10CCT100-500 4.32A 80s 34 45 55 69 86 57 75 92 115 144 80 104 128 160 200
I (A) Ipeak ½ Ipeak
t
T (ms)
Note:
1.Those MCB parameters are based on ABB S200 series circuit breakers.
2.For different brands and models of miniature circuit breakers, the quantity of drivers will have difference.
3.Please do not exceed the above-mentioned quantity during on-site installation, and the specific load quantity shall be subject to on-site installation.
4.When the installation environment temperature of MCBs exceeds 30°C or when multiple MCBs are installed side by side, the number of mounted drives will be reduced, which requires recalculation.
5.Type C MCB’s are strongly recommended to use with LED lighting
Update log
Date 2022-9-8
Version V1.2
Update content Parameter Update
NoteSubject to change without notice. Please contact us if you have any questions.
Update by Romeo