Carrier Fj4dnxa Fan Coil User Manual

FJ4DNXA Fan Coil

Product Information

Product Name: FJ4DNXA18 Fan Coils

Date: 6/30/2023

Products Affected: FJ4DNXA18 Fan Coils

Technical Information

Situation: The 018 fan coils will be redesigned to be like the
rest of the product fan coil family. Starting week 24 of 2023, the
018 fan coils will include a white wire in the harness between W
and motor tap 4 which will call for the fan to operate without a
call for G from the thermostat. Most thermostats energize G when W
is energized or can be programmed to function this way.

On units built prior to week 24, 2023, use a thermostat that can
be programmed to initiate a G call with either Y or W or add a wire
from W to the motor tap 4 connection.

Design through week 23, 2023:

  • Use a thermostat that can be programmed to initiate a G call
    with either Y or W
  • Add a wire from W to the motor tap 4 connection

Design after week 23, 2023:

  • The 018 fan coils will include a white wire in the harness
    between W and motor tap 4
  • This wire will call for the fan to operate without a call for G
    from the thermostat

Note: Only trained and qualified personnel should design,
install, repair, and service HVAC systems and equipment. All
national standards and safety codes must be followed when
designing, installing, repairing, and servicing HVAC systems and
equipment. It is the responsibility of the Dealer to ensure local
codes, standards, and ordinances are met.

Product Usage Instructions

1. For units built through week 23, 2023:

  • Ensure you have a thermostat that can be programmed to initiate
    a G call with either Y or W.
  • If your thermostat does not support this, you will need to add
    a wire from W to the motor tap 4 connection. This will enable the
    fan to operate when W is energized.

2. For units built after week 23, 2023:

  • The 018 fan coils will come with a white wire in the harness
    between W and motor tap 4.
  • This wire is responsible for calling the fan to operate without
    a call for G from the thermostat.

Ensure to follow all national standards and safety codes when
designing, installing, repairing, and servicing HVAC systems and
equipment. Only trained and qualified personnel should perform
these tasks. It is also important to comply with local codes,
standards, and ordinances.

TECHNICAL INFORMATION COMMUNICATION
Quality and Continuous Improvement

Number: TIC2023-0007 Title: FJ4DNXA Fan Coil ­ White Wire (Heating) Product Category: Fan Coils

Date: 6/30/2023

Products Affected

FJ4DNXA18 Fan Coils

Situation

The 018 fan coils will be redesigned to be like the rest of the product fan coil family. Starting week 24 of 2023 the 018 fan coils will include a white wire in the harness between “W” and motor tap 4 which will call for the fan to operate without a call for “G” from the thermostat. Most thermostats energize “G” when “W” is energized or can be programmed to function this way.

Technical Information

On units built prior to week 24, 2023; use a thermostat that can be programmed to initiate a “G” call with either “Y” or “W” or add a wire from “W” to the motor tap 4 connection.

Design through week 23, 2023

Design after week 23, 2023

Only trained and qualified personnel should design, install, repair and service HVAC systems and equipment. All national standards and safety codes must be followed when designing, installing, repairing and servicing HVAC systems and equipment. It is the responsibility of the Dealer to ensure local codes, standards, and ordinances are met.
© Carrier Corporation 2023
1