Vents 53-115 Twinfresh Expert Rw-30 V.2 Single Room Ventilation System User Guide

Vents 53-115 Twinfresh Expert Rw-30 V.2 Single Room Ventilation System User Guide

logo

VENTS 53-115 TwinFresh Expert RW-30 V.2 Single Room Ventilation SystemVENTS 53-115 TwinFresh Expert RW-30 V.2 Single Room Ventilation System fig (14)

PURPOSE

This guide covers the connection of TwinFresh Expert RW V.2 (V.3) and TwinFresh Style Wi-Fi series of air handling units to a “Smart House” system.
Control is provided only by Master devices. Slave devices, mobile devices, and “Smart House” system components are connected to master devices over Wi-Fi. Slave devices are controlled by means of commands received from master devices.VENTS 53-115 TwinFresh Expert RW-30 V.2 Single Room Ventilation System fig (1)

There are two wireless connection patterns available:

  1. A master device with a Wi-Fi access point, which can accept up to eight slave connections. If all available eight connections of the master device are used, a mobile device or a “Smart House” system will not be able to connect to the master device.
  2. Master devices, slave devices, mobile devices and a “Smart House” system connect to the Wi-Fi access point of the network router. In this case, the maximum number of available Wi-Fi connections is limited by the router functionality. If the number of necessary ventilation units is more than the router can accept, you may use an additional Wi-Fi access point to connect the remaining ventilation units. The router network may include several master devices to provide control by zones.

VENTS 53-115 TwinFresh Expert RW-30 V.2 Single Room Ventilation System fig (2)

The connection is set up via the mobile application from the Connection – > Wi-Fi setup menu (see the unit data sheet).

NETWORK PARAMETERS

Data is exchanged via the UDP protocol (with broadcast support).

Master device IP address:

  • 192.168.4.1 – if the master device runs without a router (connection pattern 1).
  • If the master device is connected via a router (connection pattern 2), the IP address is set up via the mobile application (see unit data sheet) and can be defined as static or dynamic (DHCP).
    • Master device port: 4000.
    • Maximum packet size: 256 bytes.

PACKET STRUCTUREVENTS 53-115 TwinFresh Expert RW-30 V.2 Single Room Ventilation System fig (13)VENTS 53-115 TwinFresh Expert RW-30 V.2 Single Room Ventilation System fig (15)

  • protocol type (1 byte). Value = 0x02.
  • ID block size (1 byte). Value = 0x10.
  • controller ID. This number is printed on the label (16 characters) applied to the control circuit board or the unit casing.

You can also substitute the ID with “DEFAULT_DEVICEID” code word. The ID can be used:

  • To control the master device if it runs without a router (connection pattern 1).
  • To search for master devices on the network if a router is used (connection pattern 2). In this case, the device will respond to two parameters only: 0x007C and 0x00B9 (see parameter table).
  1. VENTS 53-115 TwinFresh Expert RW-30 V.2 Single Room Ventilation System fig (16)PWD block size (1 byte). Possible values: from 0x00 to 0x08.
  2. VENTS 53-115 TwinFresh Expert RW-30 V.2 Single Room Ventilation System fig (17)device password (permissible characters: “0…9”, “a…z”, and “A…Z”). The default password is “1111”.

This password can be changed via the mobile application from the Connection –> At home –> Settings menu (see the unit data sheet).

  • VENTS 53-115 TwinFresh Expert RW-30 V.2 Single Room Ventilation System fig (18)the function number (1 byte). It defines the action with the data and the DATA block structure:
    • 0x01: parameter read.
      0x02: parameter write. The controller does not send any response regarding the status of the given parameters.
    • 0x03: parameter write with subsequent controller response regarding the status of the given parameters.
    • 0x04: parameter increment with subsequent controller response regarding the status of the given parameters.
    • 0x05: parameter decrement with subsequent controller response regarding the status of the given parameters.
    • 0x06: controller response to the request (FUNC = 0x01, 0x03, 0x04, 0x05).
  • VENTS 53-115 TwinFresh Expert RW-30 V.2 Single Room Ventilation System fig (19)data block. It consists of parameter numbers and their values:

VENTS 53-115 TwinFresh Expert RW-30 V.2 Single Room Ventilation System fig (20)

Parameter numbers (see parameter table) consists of two bytes (the high byte is virtual). By default the high byte of each parameter number in each new packet equals 0x00. The high byte can be changed within a single packet using the special 0xFF command (see below).

VENTS 53-115 TwinFresh Expert RW-30 V.2 Single Room Ventilation System fig (21)is the low byte of the parameter number. Possible values: 0x00 – 0xFB. The 0xFC – 0xFF values are special commands:

VENTS 53-115 TwinFresh Expert RW-30 V.2 Single Room Ventilation System fig (22)

  • change function (FUNC) number. The following byte must be the new function number ranging from 0x01 to 0x05. This command is used to organise several functions with different actions into a single packet.
  • parameter not supported by the controller. The following byte is the low byte of the non-supported parameter. This command is used in controller response (FUNC = 0x06) to a non-supported parameter read or write request.
  • change a size of the Value for one parameter which follows. The following byte must be the new parameter size followed by the low byte of the parameter number, and then – by the Value itself.
  • change the high byte for parameter numbers within a single packet. The following byte must be the new high byte.

VENTS 53-115 TwinFresh Expert RW-30 V.2 Single Room Ventilation System fig (23)parameter value (the default size of value is 1 byte). Byte ordering from least significant byte to most significant byte.

VENTS 53-115 TwinFresh Expert RW-30 V.2 Single Room Ventilation System fig (24)checksum (2 bytes). This is calculated as the total of bytes beginning with the TYPE byte and ending with the final byte of the DATA block.

  • Chksum L: checksum low byte.
  • Chksum H: checksum high byte.

EXAMPLES OF USING SPECIAL COMMANDS IN THE DATA BLOCK

Write request (FUNC = 0x03) for parameters number 0x009B, 0x0070, and 0x0007VENTS 53-115 TwinFresh Expert RW-30 V.2 Single Room Ventilation System fig (3)

Write request details:

  • Parameter 0x009B to be assigned the value of 0x02.
  • Parameter 0x0070 to be assigned the value of 0x42378504. The value size is 4 bytes as indicated by the special command 0xFE + 0x04.
  • Parameter 0x0007 to be assigned the value of 0x01.

Controller response (FUNC = 0x06) to write requestVENTS 53-115 TwinFresh Expert RW-30 V.2 Single Room Ventilation System fig (4)

Controller response details

  • Parameter 0x009B equals 0x02.
  • Parameter 0x0070 equals 0x42378504. The value size is 4 bytes as indicated by the special command 0xFE + 0x04.
  • Parameter 0x0007 equals 0x01.

Read request (FUNC = 0x01) for parameters number 0x0101, 0x0104, and 0x0240VENTS 53-115 TwinFresh Expert RW-30 V.2 Single Room Ventilation System fig (5)

Controller response details:

  • Parameter 0x009B equals 0x02.
  • Parameter 0x0070 equals 0x42378504. The value size is 4 bytes as indicated by the special command 0xFE + 0x04.
  • Parameter 0x0007 equals 0x01.

Read request (FUNC = 0x01) for parameters number 0x0101, 0x0104, and 0x0240VENTS 53-115 TwinFresh Expert RW-30 V.2 Single Room Ventilation System fig (6)

Controller response (FUNC = 0x06) to write request

Controller response details:

  • Parameter 0x0101 is not supported by the controller as indicated by the special command 0xFD.
  • Parameter 0x0104 equals 0x05.
  • Parameter 0x0240 equals 0x6851. The value size is 2 bytes as indicated by the special command 0xFE + 0x02.

COMPLETE PACKET EXAMPLES

Sending “Smart House–> Controller” packet
This packet contains a read request (FUNC = 0x01) for parameters number: 0x0001, 0x0002.VENTS 53-115 TwinFresh Expert RW-30 V.2 Single Room Ventilation System fig (7)

Sending “Controller –> Smart House” packet
This packet contains the controller response (FUNC = 0x06) to the write request.VENTS 53-115 TwinFresh Expert RW-30 V.2 Single Room Ventilation System fig (8)

Controller response details:

  • Parameter 0x0001 equals 0x00.
  • Parameter 0x0002 equals 0x03.
  • Checksum: 0x00E6.

PARAMETER TABLE

Functions
  • R – 0x01
  • INC – 0x04
  • RW – 0x03
  • W – 0x02
  • DEC – 0x05
Parameter number [Dec./Hex.] 

Functions

 

Description

 

Possible values

Size [bytes]
 

1/0x0001

 

R/W/RW

 

Unit On/Off

0  — Off

1  — On

2  – Invert

 

1

 

2/0x0002

 

R/W/RW/INC/DEC

 

Speed number

1  – Speed 1

2  – Speed 2

3  – Speed 3

255 – manual speed setting mode (see parameter 68)

 

1

6/0x0006RBoost mode status0  – Off

1  – On

1
 

7/0x0007

 

R/W/RW/INC/DEC

Timer mode (see parameters 770 and 771)0  – Off

1  – Night mode 2 – Party mode

 

1

11/0x000B 

R

 

Current countdown of the Timer mode

Byte 1 – seconds (0…59)

Byte 2 – minutes (0…59) Byte 3 – hours (0…23)

 

3

15/0x000F 

R/W/RW

 

Humidity sensor activation

0  – Off

1  – On

2  – Invert

 

1

 

20/0x0014

 

R/W/RW

 

Relay sensor activation

0  – Off

1  – On

2  – Invert

 

1

 

22/0x0016

 

R/W/RW

 

0–10 V* sensor activation

0  – Off

1  – On

2  – Invert

 

1

25/0x0019R/W/RW/INC/DECHumidity threshold setpoint40…80 RH%1
36/0x0024RCurrent RTC battery voltage0…5000 mV2
37/0x0025RCurrent humidity0…100 RH%1
45/0x002DRCurrent 0–10 V* sensor signal value0…100 %1
50/0x0032RCurrent relay sensor state0  – Off

1  – On

1
58/0x003AR/W/RW/INC/DECSupply fan speed in 1st speed mode**10…2551
59/0x003BR/W/RW/INC/DECExhaust fan speed in 1st speed mode**10…2551
60/0x003CR/W/RW/INC/DECSupply fan speed in 2nd speed mode**10…2551
61/0x003DR/W/RW/INC/DECExhaust fan speed in 2nd speed mode**10…2551
62/0x003ER/W/RW/INC/DECSupply fan speed in 3rd speed mode**10…2551
63/0x003FR/W/RW/INC/DECExhaust fan speed in 3rd speed mode**10…2551
74/0x004ARFan 1 speed0…5000 rpm2
75/0x004BRFan 2 speed0…5000 rpm2
99/0x0063R/W/RW/INC/DECFilter replacement timer setup**70…365 days2
 

100/0x0064

 

R

Timer countdown to filter replacementByte 1 – minutes (0…59) Byte 2 – hours (0…23) Byte 3 – days (0…181) 

3

Parameter number [Dec./Hex.] 

Functions

 

Description

 

Possible values

Size [bytes]
101/0x0065WReset timer countdown to filter replacementAny byte1
102/0x0066R/W/RW/INC/DECSetpoint of the Boost mode deactivation delay0…60 minutes1
 

111/0x006F

 

R/W/RW

 

RTC time

Byte 1 – RTC seconds (0…59) Byte 2 – RTC minutes (0…59) Byte 3 – RTC hours (0…23) 

3

 

112/0x0070

 

R/W/RW

 

RTC calendar

Byte 1 – RTC number (1…31)

Byte 2 – RTC day of the week (1…7) Byte 3 – RTC month (1…12)

Byte 4 – RTC year (0…99)

 

4

 

114/0x0072

 

R/W/RW

 

Weekly schedule mode

0   — Off

1   — On

2   – Invert

 

1

 

Schedule setup

Byte 1 – day of the week: 0 – all days (write only)

1  – Monday

2  – Tuesday

3  – Wednesday

4  – Thursday

5  – Friday

6  – Saturday

7  – Sunday

8  – Mon…Fri (write only) 9 – Sat…Sun (write only) Byte 2 – period number: 1…4

Byte 3 – speed number: 0 – standby

1…3

Byte 4 – reserved:

any byte

Byte 5 – minutes to end of period: 0…59

Byte 6 – hours to end of period:

0…23

In the read request you should use
special command 0xFE and specify
the size of the 0x02 parameter value
required for selecting the necessary
day of the week and time period
number.
119/0x0077R/W/RWThe write request and the controller6
response use all the 6 bytes.
The first time period always starts at
00:00 while the start of each following
period begins at the end of the
previous one.
The final time period always ends at
24:00
124/0x007CRDevice search on the local network, IDText (“0…9”, “A…F”)16
125/0x007DR/W/RWDevice passwordText (“0…9”, “a…z”, “A…Z”)0–8
 

126/0x007E

 

R

 

Machine hours

Byte 1 – minutes (0…59) Byte 2 – hours (0…23)

Byte 3 and Byte 4 – days (0…65535)

 

4

128/0x0080WReset alarmsAny byte1
 

131/0x0083

 

R

 

Alarm/warning indicator

0   – no

1   – alarm (highest priority) 2 – warning

 

1

 

133/0x0085

 

R/W/RW

 

Cloud server operation permission

0   – Off

1   – On

2   – Invert

 

1

 

134/0x0086

 

 

R

 

Controller base firmware version and date

Byte 1 – firmware version (major) Byte 2 – firmware version (minor) Byte 3 – day

Byte 4 – month

Byte 5 and Byte 6 – year

 

 

6

Parameter number [Dec./Hex.] 

Functions

 

Description

 

Possible values

Size [bytes]
135/0x0087WRestore factory settingsAny byte1
136/0x0088RFilter replacement indicator0 – filter replacement not required 1 – replace filter1
148/0x0094R/W/RW/INC/DECWi-Fi operation mode1   – Client

2   – Access Point

1
149/0x0095R/W/RWWi-Fi name in Client modeText1…32
150/0x0096R/W/RWWi-Fi passwordText8…64
 

153/0x0099

 

R/W/RW

 

Wi-Fi data encryption type

48 – OPEN

50   – WPA_PSK

51   – WPA2_PSK

52   – WPA_WPA2_PSK

 

1

154/0x009AR/W/RW/INC/DECWi-Fi frequency channel1…131
 

155/0x009B

 

R/W/RW

 

Wi-Fi module DHCP

0   – STATIC

1   – DHCP

2   – Invert

 

1

156/0x009CR/W/RWIP address assigned to Wi-Fi moduleByte 1 – 0…255, Byte 2 – 0…255,

Byte 3 – 0…255, Byte 4 – 0…255

4
157/0x009DR/W/RWWi-Fi module subnet maskByte 1 – 0…255, Byte 2 – 0…255,

Byte 3 – 0…255, Byte 4 – 0…255

4
158/0x009ER/W/RWWi-Fi module main gatewayByte 1 – 0…255, Byte 2 – 0…255,

Byte 3 – 0…255, Byte 4 – 0…255

4
160/0x00A0WApply new Wi-Fi parameters and quit Setup ModeAny byte1
162/0x00A2WDiscard new Wi-Fi parameters and quit Setup ModeAny byte1
163/0x00A3RCurrent Wi-Fi module IP addressByte 1 – 0…255, Byte 2 – 0…255,

Byte 3 – 0…255, Byte 4 – 0…255

4
 

183/0x00B7

 

R/W/RW/INC/DEC

 

Ventilator operation mode

0   – ventilation

1   – heat recovery 2 – supply

 

1

184/0x00B8R/W/RW/INC/DEC0–10 V* sensor threshold setpoint5…100 %1
 

185/0x00B9

 

 

R

 

 

Unit type

3: TwinFresh Expert RW1-50 V.2, TwinFresh Expert RW1-85 V.2, TwinFresh Expert RW1-100 V.2

4: TwinFresh Expert Duo RW1-30 V.2

5: TwinFresh Expert RW-30 V.2

 

 

2

252/0x00FC 

Special commands

253/0x00FD
254/0x00FE
255/0x00FF
770/0x0302R/W/RWNight mode timer setpointByte 1 – minutes (0…59) Byte 2 – hours (0…23)2
771/0x0303R/W/RWParty mode timer setpointByte 1 – minutes (0…59) Byte 2 – hours (0…23)2
772/0x0304RHumidity sensor status0 – below setpoint 1 – over setpoint1
773/0x0305R0–10 V* sensor status0 – below setpoint 1 – over setpoint1

Available for all models except TwinFresh Expert RW-30 V.2
Available for TwinFresh Expert RW1-50 V.3, TwinFresh Style Wi-Fi, TwinFresh Style Wi-Fi Frost, TwinFresh Style Wi-Fi mini.VENTS 53-115 TwinFresh Expert RW-30 V.2 Single Room Ventilation System fig (9)VENTS 53-115 TwinFresh Expert RW-30 V.2 Single Room Ventilation System fig (10)VENTS 53-115 TwinFresh Expert RW-30 V.2 Single Room Ventilation System fig (11)VENTS 53-115 TwinFresh Expert RW-30 V.2 Single Room Ventilation System fig (12)

EXAMPLE OF PROCESSING PACKETS WRITTEN

www.ventilation-system.com

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals