Hyfire Hfw-sim-01 Wireless Wall Sounder And Wall Sounder Vad Instruction Manual

HFW-SIM-01 Wireless Wall Sounder and Wall Sounder VAD

Product Information

The device is a Sagittarius Type B Wall Sounder that consists of
an HFW-SIM-01 Sagittarius system interface module and either an
HFC-WSR-03 conventional sounder or an HFC-SBR-2303 conventional
sounder with a visual alarm device. The sounder’s output is
activated following an alarm condition of the Sagittarius
system.

Installation Instructions

Before installing the device, it is important to follow your
national and/or international codes of practice and standards. Test
the device after installation to ensure proper functionality.

Sounder Opening Procedure

To detach the upper sounder body from the base:

  1. Insert the pins of the compatible key into the holes of one of
    the two side locking mechanisms.
  2. When assembling or removing the front operating section of the
    sounder to/from the back box, ensure the interconnection block is
    not twisted, which may cause damage. Perform such operations
    without using excessive force.
  3. Repeat step one for the second side locking mechanism; the
    locking mechanism appears as in picture 1 when in the open position
    (flush).
  4. Detach the sounder body from the base by pulling gently to
    separate (picture 2).

Module’s Extraction

To extract the module:

  1. Gently release the locking catch allowing the module to lift
    and rotate to release from the side wall.
  2. Remove the module.

Linking Instructions

The translator / expander module is waiting to achieve a
wireless child device. Follow these steps:

  1. Move the link switch’s cursor from ON to the opposite side
    (BLANK side); HFW-SIM-01 indicates Linking to the system.
  2. If the linking outcome is okay, HFW-SIM-01 stops indicating
    Linking to the system.
  3. If the linking outcome is not okay, perform the LINKING
    RECOVERY procedure.

Linking Recovery

If something goes wrong with the linking operation:

  1. Take out both batteries from their holders.
  2. Move alternatively the link switch to ON / BLANK five
    times.
  3. Move the link switch to ON.
  4. Reinsert both batteries into their holders, oriented as per
    polarity marks.
  5. Perform the LINKING procedure.

Wireless Link Quality Check

It is possible to check wireless link quality between the
sounder module and its linked-to translator or expander in this
way:

During all the duration of the linking phase, the module must be
only a few inches away from the translator / expander module you
are linking to.

Module’s Status

The module’s status is indicated by LED lights as follows:

StatusGreen LEDRed LED
Power up0.5 second green and red (amber) and 1 second off
Linking to the systemBlinking until linking is completed
Normal condition0.5 second on and 10 seconds off0.5 second on and 10 seconds off (orange tonality)
Main battery fault1 second green, then 0.5 second red for 4 times
Secondary battery fault0.5 second on and 10 seconds off
Both batteries fault0.5 second on and 10 seconds off (orange tonality)
Lost link with wire to wireless translator / wireless
expander
0.5 second on and 10 seconds off

Contact Information

Contact Hyfire Wireless Fire Solutions Limited at
[email protected] or Unit B12a, Holly Farm Business Park,
Honiley, Warwickshire, CV8 1NP, United Kingdom.

HFW-SIM-01 + HFC-WSR-03 HFW-SIM-01 + HFC-SBR-23-03
SAGITTARIUS TYPE B WALL SOUNDER SAGITTARIUS TYPE B WALL SOUNDER + VISUAL ALARM DEVICE
OVERVIEW This device is an assembly of an HFW-SIM-01 Sagittarius system interface module and a HFC-WSR-03 conventional sounder / HFC-SBR-2303 conventional sounder + visual alarm device. Sounder’s output is activated following an alarm condition of the Sagittarius system. INSTALLATION – IMPORTANT NOTES – The device must be installed following your national and/or international codes of practice and standards: check them before performing the
installation of this device. – Test this device after installation.
INSTALLATION
1) Detach the front operating section from the sounder back box ( SOUNDER OPENING PROCEDURE). 2) Extract the HFW-SIM-01 from the sounder’s back box ( MODULE’S EXTRACTION). 3) Set the HFW-SIM-01’s link switch to ON. 4) Extract the HFW-SIM-01’s battery covers. 5) Insert both batteries into their HFW-SIM-01 holders, oriented as per polarity marks. 6) Link the HFW-SIM-01 device to the Sagittarius system ( LINKING). 7) Reinstall the battery covers. 8) Check the wireless link quality of the HFW-SIM-01 positioned in the final installation location ( WIRELESS LINK QUALITY CHECK). 9) Install the sealing pad if the sounder is to be installed outdoors and/or in damp environments (not EN 54-3 approved)
( OUTDOORS AND DAMP ENVIRONMENTS INSTALLATION). 10) Fix the sounder back box to the wall on the final installation location ( WALL INSTALLATION). 11) Reinstall the HFW-SIM-01 into the sounder’s back box ( MODULE’S INSTALLATION). 12) Set sounder’s tone and volume ( OUTPUT TONE SETTING , OUTPUT VOLUME SETTING). 13) Reinstall the front operating section onto the sounder back box ( SOUNDER CLOSING PROCEDURE). 14) Test the HFW-SIM-01 + HFC-WSR-03 / HFC-SBR-23-03 to check if it works properly ( TESTING).

Hyfire Wireless Fire Solutions Limited – Unit B12a, Holly Farm Business Park, Honiley,

www.hyfirewireless.com

Warwickshire, CV8 1NP – United Kingdom

1

SOUNDER OPENING PROCEDURE

In order to detach the upper sounder body from the base:
1) Insert the pins of the compatible key into the holes of one of the two side locking mechanisms.
2) Turn the key 90° to the left whilst applying light pressure.

When assembling or removing the front operating section of the sounder to/from the back box be careful to ensure the interconnection block is not twisted which may cause damage. Perform such operations without using excessive force.

3) Repeat this step for the second side locking mechanism; the locking mechanism appears as in picture 1 when in the open positi on (flush).

4) Detach the sounder body from the base by pulling gently to separate (picture 2).

Picture 1

MODULE’S EXTRACTION 1) Gently release the locking catch allowing the module to lift and rotate to release from the side wall. 2) Remove the module.

Picture 2

[email protected]

Picture 3 L20-SGWSM-1400 (vA.6)
2

LINKING

The translator / expander module is waiting to achieve a wireless child device.

1) Move the link switch’s cursor from ON to the opposite side (BLANK side); HFW-SIM-01 indicates “Linking to the system”.

2) If linking outcome is ok: HFW-SIM-01 stops indicating “Linking to the system”.

3) If linking outcome is not ok: perform the LINKING RECOVERY procedure.

LINKING RECOVERY

In case something goes wrong with the linking operation: 1) Take out both batteries from their holders.

LED INDICATOR

LINK SWITCH

2) Move alternatively the link switch to ON / BLANK five times. 3) Move the link switch to ON. 4) Reinsert both batteries into their holders, oriented as per polarity marks. 5) Perform the LINKING procedure.

Picture 4

During all the duration of the linking phase, the module must be only a few inches away from the translator / expander module you are linking to.

MODULE’S STATUS Power up Linking to the system Normal condition
Main battery fault
Secondary battery fault
Both batteries fault Lost link with wire to wireless translator / wireless expander

GREEN LED

RED LED

1 second green, then 0.5 second red for 4 times

Blinking until linking is completed


0.5 second on and 10 seconds off

0.5 second on and 10 seconds off (orange tonality)

0.5 second on and

10 seconds off

(orange tonality)

0.5 second green and red (amber) and 1 second off

Table 1

WIRELESS LINK QUALITY CHECK

It is possible to check wireless link quality between the sounder module and its linked-to translator or expander in this way:

1) Move the link switch to the ON position.

2) Module’s LED indicator will start blinking according to the following table:

LINK QUALITY No connection Link margin is less than 10 dB

EVALUATION Fail Poor

DEVICE’S INDICATION Two red blinks One red blink

Robust communication with link margin from 10 dB to 20 dB Robust communication with link margin over 20 dB

Good Excellent

One green blink Two green blinks

3) Move the link switch to position BLANK again; device will NOT WORK if the link switch is on position ON !

Table 2

Hyfire Wireless Fire Solutions Limited – Unit B12a, Holly Farm Business Park, Honiley,

www.hyfirewireless.com

Warwickshire, CV8 1NP – United Kingdom

3

OUTDOORS AND DAMP ENVIRONMENTS INSTALLATION
When installing the sounder outdoors or in a damp environment, carefully apply the selfadhesive sealing pad to the back of the sounder base (picture 5).

Suitable, but not EN 54-3 approved for outdoor use.

WALL INSTALLATION

Fix the sounder base to the wall; the prepared location options for the fixing screws are highlighted in picture 6.

Picture 5

Picture 6

MODULE’S INSTALLATION 1) Insert the terminal edge of the module between the securing points on the wall of the back box. 2) Gently push down the module body so that the locking catch engages fully to hold the PCB in place. Check that it feels secure.

LOCKING CATCH

Picture 7

[email protected]

L20-SGWSM-1400 (vA.6) 4

OUTPUT TONE SETTING
Use the DIP switch on the back of the sounder body to select the tone required; for this function the first five switches are used, highlighted in picture 8.

Picture 8
The switches positioned upwards acquire value “1”; on the other hand, if positioned downwards acquire value “0”. 1) From the TONE SET table (table 4) select the output alarm tone triggered when the sounder is activated. 2) Refer to the corresponding line of the “DIP configuration” column to select the five switch selection settings. OUTPUT VOLUME SETTING Use the DIP switch at the back of the sounder body to select the output volume; in particular, switches 6 and 7, highlighted in picture 9, are used.

Picture 9
The switches positioned upwards acquire value “1”; on the other hand, if positioned downwards acquire value “0”. 1) Select the alarm volume required when the sounder is activated (table 3). 2) Refer to the corresponding line of the “DIP configuration” column to set the two volume selection switches.

Tone volume HIGH
MEDIUM HIGH MEDIUM LOW
LOW

DIP configuration – switch 6 and 7 11 01 10 00

dB(A) evaluation 100 dB(A) +/- 3

Notes All tones

Table 3

Hyfire Wireless Fire Solutions Limited – Unit B12a, Holly Farm Business Park, Honiley,

www.hyfirewireless.com

Warwickshire, CV8 1NP – United Kingdom

5

TONE SET

Tone number

Tone designation

Tone description

1 *

Warble Tone

800Hz for 500ms, then 1000Hz for 500ms

2 *

Continuous tone

970Hz continuous tone

3 *

Slow Whoop (Dutch)

500-1200Hz for 3500ms, then off for 500ms

4 *

German DIN tone

1200-500Hz swept every 1000ms (1Hz)

5

Alternate HF slow sweep

2350-2900Hz swept every 333ms (3Hz)

6

Alternative warble

800Hz for 250ms, then 960Hz for 250ms

7

Alternative warble

500Hz for 250ms, then 600Hz for 250ms

8

Analogue sweep tone

500-600Hz swept every 500ms (2Hz)

9

Australian Alert (intermittent tone) 970Hz for 625ms, then OFF for 625ms

10

Australian Evac (slow whoop)

500-1200Hz sweep for 3750ms, then OFF for 250ms

11

Alternative Warble

990Hz for 250ms, then 665Hz for 250ms

12

French tone AFNOR

554Hz for 100ms, then 440Hz for 400ms

13

HF Back up interrupted tone

2800Hz for 1s, then OFF for 1s

14

HF Back up interrupted tone ­ fast 2800Hz for 150ms, then OFF for 150ms

15

HF Continuous

2800Hz continuous

16

Interrupted tone

800Hz for 500ms,then OFF for 500ms

17

Interrupted tone medium

1000Hz for 250ms, then OFF for 250ms

18

ISO 8201 LF BS5839 Pt 1 1988

970Hz for 500ms, then OFF for 500ms

19

ISO 8201 HF

2850Hz for 500ms, then OFF for 500ms

20

LF Back up Alarm

800Hz for 150ms, then OFF for 150ms

21

LF Buzz

800-950Hz swept every 9ms

22

LF Continuous tone BS5839

800Hz continuous

23

Silent

No sound

24

Siren 2 way ramp (long)

500-1200Hz rising for 3000ms, then falling for 3000ms

25

Siren 2 way ramp (short)

500-1200Hz rising for 250ms, then falling for 250ms

26

Swedish all clear signal

660Hz continuous

27

Swedish Fire signal

660Hz for 150ms, then OFF for 150ms

28

Sweep tone (1 Hz)

800-900Hz swept every 1000ms

29

Sweep tone (3 Hz)

800-970Hz swept every 333ms (3Hz)

30

Sweep tone (9 Hz)

800-970Hz swept every 111ms (9Hz)

31

US Temporal Pattern HF

(2900Hz for 500ms ON, 500ms OFF) x3, then 1500ms OFF

32

LF Sweep (Cranford tone)

800-1000Hz swept every 500ms (2Hz)

* EN 54-3 certified tones

DIP switch configuration: 1,2,3,4 e 5 11101 01011 10101 00111 10010 11110 11100 10100 10001 10110 00001 00101 11011 11001 01001 01111 01101 01110 01100 11010 01010 11000 11111 00000 00010 00100 00110 10111 10011 01000 00011 10000
Table 4

[email protected]

L20-SGWSM-1400 (vA.6) 6

SOUNDER CLOSING PROCEDURE In order to assemble the sounder body to the base: 1) Assemble the sounder body to the base using gentle pressure (picture 10). 2) Insert the pins of the compatible key into the holes of one of the two side locking
mechanisms. 3) Turn the key 90° to the right. 4) Repeat this step for the second side locking mechanism, starting from point 2; the
locking mechanism appears as in picture 11 once closed (recessed). 5) To secure use the retaining screws, using the location holes on both sides of the
base (picture 12).
When assembling or removing the front operating section of the sounder to/from the back box be careful to ensure the interconnection block is not twisted which may cause damage. Perform such operations without using excessive force.

Picture 10

Picture 11

Picture 12

Hyfire Wireless Fire Solutions Limited – Unit B12a, Holly Farm Business Park, Honiley,

www.hyfirewireless.com

Warwickshire, CV8 1NP – United Kingdom

7

TAMPERING DETECTION AND NOTIFICATION Tampering attempts are detected by a pair of switches (one on the front, the other on the back of the module); once detected, a tampering event message is broadcasted to the system.
TESTING 1) Activate the fire security system’s alarm condition. 2) Check the HFW-SIM-01 + HFC-WSR-03 / HFW-SIM-01 + HFC-SBR-23-03 output activation. 3) Press the SILENCE SOUNDERS button (or equivalent) on the control panel. 4) Reset the system from the control panel. All devices must be tested after installation and, successively, on a periodic basis.
BATTERY REPLACEMENT When the translator module indicates a low battery condition on a child device, batteries must be replaced. When a low battery condition is indicated, both batteries must be changed altogether. During this procedure the linking switch must NOT be touched at all ! 1) Detach the front operating section from the sounder back box. 2) Extract the HFW-SIM-01 from the sounder’s back box. 3) Extract the HFW-SIM-01’s battery covers. 4) Extract the batteries. 5) Insert the new batteries into their holders, oriented as per polarity marks. 6) Reinstall the battery covers. 7) Reinstall the HFW-SIM-01 into the sounder’s back box. 8) Reinstall the front operating section onto the sounder back box. 9) Test the HFW-SIM-01 + HFC-WSR-03 / HFW-SIM-01 + HFC-SBR-23-03 to check if it works properly.

[email protected]

L20-SGWSM-1400 (vA.6) 8

Picture 13

Hyfire Wireless Fire Solutions Limited – Unit B12a, Holly Farm Business Park, Honiley,

www.hyfirewireless.com

Warwickshire, CV8 1NP – United Kingdom

9

TECHNICAL SPECIFICATIONS (HFW-SIM-01)

Communication range with the translator / expander

200 m (in open space)

Operating frequency

868 MHz

Operating frequency channels

7

Battery voltage range Batteries type Radiated power
Batteries lifespan
Parent expander’s check-up period

3 V
2 X CR123A (3V)
14 dBm (25 mW)
>3 years (with parent expander’s check-up period default setting); remains operational for up to 60 days from first appearance of the low battery warning
7 seconds (default setting)

TECHNICAL SPECIFICATIONS (HFW-SIM-01 + HFC-WSR-03)

Max current draw (at 3 V)
Acoustic emission frequency range. Valid for all tones Maximum acoustic intensity, volume set to HIGH. Valid for all tones Tolerated temperature range
Maximum tolerated humidity
Height
Diameter
Weight
IP rating (EN 54-3 certified)
IP rating (not certified) *

50 mA 440 – 2900 Hz

100 dB(A) ± 3

-10 °C / +55 °C 85% RH (without condensation) 185 mm
130 mm
350 g
33C Type B
65

* Independently assessed and certified to IPX5 (not part of the current EN54-3 certification).

TECHNICAL SPECIFICATIONS (HFW-SIM-01 + CWS100-AV)

Max current draw (at 3 V)

260 mA

Acoustic emission frequency range. Valid for all tones Maximum acoustic intensity, volume set to HIGH. Valid for all tones Visual Alarm Device (VAD) frequency
VAD flash coverage
Tolerated temperature range
Maximum tolerated humidity
Height (base included) Diameter
Weight
IP rating (EN 54-3 certified)
IP rating (not certified) *

440 – 2900 Hz
100 dB(A) ± 3
0.5 Hz W – 2.5 – 7 (122.5 m3) -10 °C / +55 °C 85% RH (without condensation) 192 mm 130 mm 380 g 33C Type B 65

7.0m (y) 2.5m (x)

7.0m (y)

Wall mounted device demonstration

[email protected]

L20-SGWSM-1400 (vA.6) 10

WARNINGS AND LIMITATIONS
Our devices use high quality electronic components and plastic materials that are highly resistant to environmental deterioration. However, after 10 years of continuous operation, it is advisable to replace the devices in order to minimize the risk of reduced performance caused by external factors. Ensure that this device is only used with compatible control panels. Detection systems must be checked, serviced and maintained on a regular basis to confirm correct operation. Smoke detectors may respond differently to various kinds of smoke particles, thus application advice should be sought for special risks. Detectors cannot respond correctly if barriers exist between them and the fire location and may be affected by special environmental conditions. Refer to and follow national codes of practice and other internationally recognized fire engineering standards. Appropriate risk assessment should be carried out initially to determine correct design criteria and updated periodically.
WARRANTY
All devices are supplied with the benefit of a limited 5 years warranty relating to faulty materials or manufacturing defects, effective from the production date indicated on each product. This warranty is invalidated by mechanical or electrical damage caused in the field by incorrect handling or usage. Product must be returned via your authorized supplier for repair or replacement together with full information on any problem identified. Full details on our warranty and product’s returns policy can be obtained upon request.

0051 16
SG0920CPR SG1020CPR

8504 22
SG0920UK SG1020UK

Hyfire Wireless Fire Solutions Limited – Unit B12a,
Holly Farm Business Park, Honiley, Warwickshire, CV8 1NP – United Kingdom

HFW-SIM-01 + HFC-WSR-03 HFW-SIM-01 + HFC-SBR-23-03
EN 54-25:2008 EN 54-3:2001+A1:2002+A2:2006
HFW-SIM-01 + HFC-SBR-23-03 (only)
EN 54-23:2010
For use in compatible fire detection and alarm system.
Category rating: W – 2.5 – 7
Duration of operation: Pass Provision for external conductors: Pass Flammability of materials: Pass Enclosure protection: Pass Access: Pass Manufacturer’s adjustments: Pass On-site adjustment of behaviour: Pass Requirements for software controlled devices: Pass Coverage volume: Pass Variation of light output: Pass Minimum and maximum light intensity: Pass Light colour: White Light temporal pattern / frequency of flashing: N/A / 0.5 Hz Marking and data: Pass Synchronization: Pass Durability: Pass Temperature resistance: Pass Humidity resistance: Pass Shock and vibration resistance: Pass Corrosion resistance: Pass Electrical stability: Pass
For use in compatible fire detection and alarm system

Hyfire Wireless Fire Solutions Limited – Unit B12a, Holly Farm Business Park, Honiley,

www.hyfirewireless.com

Warwickshire, CV8 1NP – United Kingdom

11

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals