Mean Well Dm10x Hvac Controller User Guide

DM10x HVAC Controller

Product Information:

DM10x HVAC Controller

The DM10x HVAC Controller is a versatile controller designed for
use in heating, ventilation, and air conditioning (HVAC) systems.
It is capable of controlling various components and functions
within an HVAC system, providing efficient and reliable
operation.

Product Specifications:

  • Datasheet Rev: 1.05
  • Dimensions: 12 (refer to the manual for detailed
    dimensions)
  • Header Assignment: DM101 and DM102

Product Usage Instructions:

Installation:

Follow the steps below for installing the DM10x HVAC
Controller:

  1. Refer to the manual for detailed installation instructions and
    safety precautions.
  2. Select an appropriate location for the controller, ensuring
    proper ventilation and accessibility.
  3. Connect the necessary power supply and wiring according to the
    system requirements.
  4. Securely mount the DM10x HVAC Controller in place.

Diagnostics:

The DM10x HVAC Controller provides diagnostic capabilities for
troubleshooting and monitoring the system. Refer to the manual for
detailed instructions on accessing and interpreting the
diagnostics.

Usage Scenarios:

DM101 Controlling a Fan Coil Unit:

The DM10x Controller can be used to control a fan coil unit
(FCU). The controller features five relays that are galvanically
decoupled, allowing independent control of each load. If the
heating and cooling valves share the same power, external wiring is
required to connect these signals to the DM10x controller. Refer to
the manual for a diagram and detailed instructions on configuring
the controller for this application.

DM102 Controlling a Fan Coil Unit with Proportional
Valves:

The DM10x Controller can also be used to control a fan coil unit
(FCU) with proportional valves. This application requires
additional configuration and setup. Refer to the manual for a
diagram and detailed instructions on configuring the controller for
this application.

DM10x Front-Side Bus as Low-Voltage I/O:

The DM10x Controller features two four-pin bus headers that can
be used as additional low-voltage input/output (I/O) ports. Each
port can be individually configured as a communication bus or as a
digital I/O. When configured as a digital I/O, each header provides
one digital input and one digital output. Refer to the manual for
instructions on configuring and utilizing these low-voltage I/O
ports.

DM10x Controlling Master Contactor Relay:

The DM10x Controller can be used to control a master contactor
relay. This application requires the use of a compatible relay,
such as the chassis-mount T9AP1D52-12 by TE Connectivity Potter
& Brumfield Relays. It is important to ensure that all local
electrical code requirements are met when deploying such a setup.
Refer to the manual for detailed instructions on configuring and
connecting the master contactor relay.

DM10x HVAC Controller
DM10x Controller
· Controller for FCU, PTAC and other HVAC equipment · 5 line-voltage relays · Low voltage digital inputs and outputs · Analog inputs and outputs · NTC temperature probe inputs · Built-in 802.15.4 radio · Removable headers · DIN-rail mounted · Slim package for high density controller setup

Datasheet Rev 1.05

Contents
OVERVIEW ………………………………………………………………………………………………………………………………………………..2
APPLICATIONS …………………………………………………………………………………………………………………………………………..3
DM101 CONTROLLING A FAN COIL UNIT …………………………………………………………………………………………………………………..3 DM102 CONTROLLING A FAN COIL UNIT WITH PROPORTIONAL VALVES……………………………………………………………………………….4 DM10X FRONT-SIDE BUS AS LOW-VOLTAGE I/O………………………………………………………………………………………………………….5 DM10X CONTROLLING MASTER CONTACTOR RELAY………………………………………………………………………………………………………6 DM10X OVERCOMING RF LIMITATIONS IN SHEET METAL HOUSINGS…………………………………………………………………………………..7
INSTALLATION …………………………………………………………………………………………………………………………………………..8
DIAGNOSTICS……………………………………………………………………………………………………………………………………………. 9
SPECIFICATIONS ………………………………………………………………………………………………………………………………………. 10
USER INTERFACE ………………………………………………………………………………………………………………………………………………10 RADIO ………………………………………………………………………………………………………………………………………………………….. 10 SOFTWARE …………………………………………………………………………………………………………………………………………………….. 10 DEVICE …………………………………………………………………………………………………………………………………………………………. 10 ENVIRONMENTAL AND PHYSICAL SPECIFICATION………………………………………………………………………………………………………….10 RELAYS …………………………………………………………………………………………………………………………………………………………. 11 DIGITAL INPUT …………………………………………………………………………………………………………………………………………………11 DIGITAL OUTPUT………………………………………………………………………………………………………………………………………………11 ANALOG INPUTS……………………………………………………………………………………………………………………………………………….11 ANALOG OUTPUTS…………………………………………………………………………………………………………………………………………….11 TEMPERATURE PROBE INPUTS……………………………………………………………………………………………………………………………….11 BUS PORTS……………………………………………………………………………………………………………………………………………………..11 ORDERING INFORMATION ……………………………………………………………………………………………………………………………………11
Page 1

DM10x HVAC Controller
DIMENSIONS ………………………………………………………………………………………………………………………………………….. 12 HEADER ASSIGNMENT ……………………………………………………………………………………………………………………………… 12
DM101 HEADER ASSIGNMENT……………………………………………………………………………………………………………………………..12 DM102 HEADER ASSIGNMENT……………………………………………………………………………………………………………………………..12
Disclaimer: This document contains information that is the proprietary and confidential property of AuVerte. By acceptance hereof, each recipient agrees to use the information contained herein only for the purpose anticipated by AuVerte, and not to disclose to others, copy or reproduce, any part hereof without the written consent of AuVerte. The recipient agrees to return this document to AuVerte immediately upon request.
Overview
The DM10x is a high-density DIN-rail mounted controller assembly. It is designed for room automation systems and is used in several different application situations. Common applications are the control of HVAC systems, such as Fan Coil Units (FCU) or Packaged Air Conditioning (PTAC). The controller is powered with 12VDC from an external power supply. For load control, five built-in relays can directly control line-voltage loads and there is full galvanic decoupling of the low voltage side from the line-voltage side. The controller features pluggable headers for a simplified maintenance should equipment have to be exchanged during the operating phase. The DM101 is a basic controller with just the five relays while the DM102 contains an array of low-voltage digital and analog inputs and outputs to support more advanced application scenarios. For networking, the DM10x controllers can daisy chained with other controllers that are part of a load center. Further, the DM10x has a built-in Rf radio for direct communication with other room automation system components.
Page 2

DM10x HVAC Controller
Applications
DM101 Controlling a Fan Coil Unit
The diagram below shows a basic configuration for controlling a fan coil unit (FCU). The five relays do not share any commons which means that each of the five loads is controlled galvanically decoupled. If for example the heating and cooling valve use the same power, then these power signals have to be wired together externally to the DM10x controller.
Page 3

DM10x HVAC Controller
DM102 Controlling a Fan Coil Unit with Proportional Valves
In the diagram below, we see a more elaborate HVAC control schema that utilizes the DM102. In this sample application, three relays are allocated to drive the fan motor of a FCU. A fourth relay is used to engage a secondary heat. The primary heating and cooling valves are based on a 0-10V analog signal and driven by the analog outputs of the DM102. An additional return-air temperature sensor in the form of a 10k NTC probe is attached to provide the control algorithm with a reading of the return air temperature.
Page 4

DM10x HVAC Controller
DM10x Front-Side Bus as Low-Voltage I/O
When configured correspondingly, the two four-pin bus headers can be used as additional low-voltage I/Os. Each port can be individually configured to either act as a communication bus or as a digital I/O. When configured as a digital I/O, each header features one digital input and one digital output.
The figure below shows an example how the front-side I/Os can be used. The left digital output (DO-L) is used to drive a relay with a 12VDC coil. DO-L and DO-R both feature a free-run diode to avoid damaging the output when the relay is turned off. The right digital output (DO-R) is driving directly an LED. Both outputs feature a current setting capability that run 1mA through the pushed output. This avoids that the LED will require an external current limiting resistor. The digital inputs (DI-L, DI-R) are connected to each a dry-contact input. This could be a momentary pushbutton or a toggle switch.
Page 5

DM10x HVAC Controller
DM10x Controlling Master Contactor Relay
If the signals on the right-side front connector are not otherwise used, then a master contactor relay coil can be directly operated by the DM101. To enable this feature, the function needs to be engaged as part of the device configuration. The DM10x can directly drive a 12VDC coil up and has all the necessary protection circuits built in. This master relay will be under software control and typically be engaged when the room is occupied. In this case, all outlets and loads that generally are not needed when the room is not occupied can be turned off when the occupant has left the space.
As an example, the chassis-mount T9AP1D52-12 by TE Connectivity Potter & Brumfield Relays can be used for such an application. The designer of such a deployment needs to assure that all local electrical code requirements have been met.
Page 6

DM10x HVAC Controller
DM10x Overcoming Rf Limitations in Sheet Metal Housings
The Rf communication with the DM10x might be negatively impacted if the device is housed in a sheet metal enclosure. It can often be observed in real deployment that some Rf capabilities still exist, such as when the AvEWB laptop is brought into proximity to the enclosure. However, the Rf signal is significantly attenuated and a reliable communication with equipment a bit further away might be questionable. Any further signal attenuation, such as if a mesh network should be formed with equipment in other rooms, is typically not achievable any longer. To overcome this condition, the DM10x controller can use a RD102.RFB (Rf Bridge). This matchbox sized device will reside outside the sheet metal enclosure and will provide nominal Rf performance to the controllers inside the enclosure. If multiple controllers reside inside the enclosure, only a single Rf bridge will be required. As the controllers inside the enclosure are daisy chained, they can share the Rf bridge resource. The diagram below shows only the key elements pertaining to the Rf bridge. There is no impact on the I/O headers of the controllers.
The image to the right shows how a number of daisy chained DM10x controllers use the RD102RFB device to provide communication capabilities when fully enclosed in a sheet metal housing. The RD102RFB is the smaller black device to the left of the Meanwell power supply
Page 7

DM10x HVAC Controller
Installation
The DM10x controller is mounted on a standard 35mm DIN rail. It features a clip that locks the product in place. All electrical connections are made through the pluggable terminals so that the product can be swapped out without requiring a full re-wiring of the device. The product is onboarded with the AuVerte workbench software.
Page 8

DM10x HVAC Controller
Diagnostics
The AvEWB features a built-in diagnostics capability that allows the user to monitor ongoing activities of the DM10x controller. This feature can be used to visualize the sensor and controls algorithms and how these signals are interfaced with the physical world.
Page 9

DM10x HVAC Controller

Specifications

User Interface
LED
Pushbutton

RGB LED for status indication To trigger setup and diagnostic functions

Radio
Standard Frequency band Interference immunity Data rate Antenna Indoor range Transmit power Receiver sensitivity Channels Protocol

IEEE 802.15.4 ISM 2.4 GHz DSSS (Direct sequence spread spectrum) 250 kbps Built-in Up to 50 m (150 ft) +3 dBm -95 dBm 16 (11 to 26, default 25) AuVerte mesh, IPv6 over 802.15.4 with forward error correction (FEC-ECC)

Software
IPv4 IPv6 Encryption Hashing Key Exchange Routing
App Security Cyber security

Not supported
ICMPv6, IP, UDP, CoAP
AES128
SHA256, AES-CMAC
ECDH UDP ­ AuVerte mesh IPv6 ­ IPv6 over 802.15.4 DTLS
Packet authentication, packet inspection, certificate-based access control, configurable encryption keys with no backdoors , JTAG disabled Configurable port-based firewall

Environmental and Physical Specification

Dimensions

Without headers: 86mm x 95mm x 26mm

With headers: 104mm x 95mm x 26mm

Weight

200g

Operating temperature

10 °C to 40 °C (50 °F to 104 °F)

Storage temperature -20 °C to 50 °C (–4 °F to 122 °F)

Operating humidity

10 % to 95 %RH, non-condensing

Storage humidity

5 % to 90 %RH, non-condensing

Electromagnetic emissions

FCC Part 15C EN 62311 (EMR)

ETSI EN 300 328 (2.5GHz ISM Band)

ETSI EN 301489 (EMC)

Safety approvals

EN62368-1

Environmental

RoHS

Cleaning

Mild cleaning liquid, soft towel

Recycling

Repairable by AuVerte. Recycling limited to housing with most of the weight attributed to the electronics.

Safety

All termination and connection work to be performed when electrical power to the installation box is removed

Installation location

Electrical enclosures meeting local codes

Device
Power
Mounting
Color

12VDC / 250mA DIN-rail mounted (35 rail) Dark gray

Page 10

DM10x HVAC Controller

Relays
Count / Type Contact rating
Application design ratings Color

5 SPST-NO, Form-A Rated load: 240VAC 16A Max switching voltage: 277VAC Max switching capacity: 3500VA 277VAC 10A per relay 5000VA for all five relays Dark gray

Digital Input
Count Type Actuation
Activation threshold

0 (DM101), 6 (DM102)
10k pull-up to 12VDC External pull-down (dry contact, optocoupler, NPN transistor) with at least 2mA driving capability.
Active: pull low to below 2VDC
Inactive: release to above 8VDC

Digital Output
Count Type
Typical applications

0 (DM101), 6 (DM102)
NPN pull-down transistors (to GND) with 1.2k current protection resistor on emitter.
Driving of external LED (10mA at 12VDC)
Driving of compatible digital inputs in other devices

Analog Inputs
Count
Type

0 (DM101), 2 (DM102) 0-10VDC

Input impedance ADC Resolution

100k 12 bits

Analog Outputs

Count

0 (DM101), 2 (DM102)

Type

0-10VDC

Drive capability

5mA

ADC Resolution

12 bits

Temperature Probe Inputs

Count

0 (DM101), 2 (DM102)

Type

10k NTC

Temperature range

0° – 110°C

Accuracy

± 2°C

Bus Ports
Count
Typical application
Alternate application

2
Bus interface for daisy chaining controllers
One low-voltage digital input and one lowvoltage digital output

Ordering Information

Part numbers

003044.DM101 , 003044.DM102

Package content

DM10x controller, screw terminals, short interconnect harness

Options

RD102RFB (external Rf bridge)

Power Supplies

Recommended power supplies:

· Meanwell MDR-10-12 · Meanwell MDR-20-12 · Meanwell MDR-40-12 · Meanwell MDR-60-12 · Meanwell MDR-100-12

Page 11

DM10x HVAC Controller
Dimensions

Header Assignment
DM101 Header Assignment

DM102 Header Assignment

Page 12

AuVerte AG Rothusmatt 14
CH-6300 Zug Switzerland www.auverte.com

FCC Warning
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Any Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
-Reorient or relocate the receiving antenna. -Increase the separation between the equipment and receiver. -Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. -Consult the dealer or an experienced radio/TV technician for help.
This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with minimum distance 20cm between the radiator & your body.

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals