Verasys Vec100 Generic Rtu Heat Pump Controller User Guide

Verasys Vec100 Generic Rtu Heat Pump Controller User Guide

VERASYS VEC100 Generic RTU Heat Pump Controller User Guide
VERASYS VEC100 Generic RTU Heat Pump Controller

About this guide

This quick start guide provides the basic information you need to configure and install the Verasys® Equipment Controller (VEC), LC-VEC100-0, using the Verasys generic rooftop unit (RTU) heat pump controller application. The application controls a third-party changeover bypass (COBP) system or a third-party variable air volume (VAV) unit.

For further information, refer to the Verasys Equipment Controller (VEC) Installation Guide (24-10143-1272) and the VEC100 Generic RTU Heat Pump Controller Application Note (12013452).

Options availablePossible values
Number of Heat Pump Stages Installed0 to 2
Supplemental Heat Installed
  • State 0: No
  • State 1: Yes
Economizer Installed
  • State 0: the economizer is not available.
  • State 1: the economizer is available.
Air Proving Switch Setup
  • State 0: fan status device
  • State 1: duct static pressure sensor
  • State 2: none
Runtime Equalization
  • State 0: heat pump activation is not based on runtime.
  • State 1: heat pump activation is based on runtime.
Rooftop Controller Type
  • State 0: changeover bypass
  • State 1: VAV
Cancel ASCD Timers
  • State 0: false
  • State 1: true
Demand Ventilation Feature
  • State 0: demand ventilation is off.
  • State 1: demand ventilation is on.
Reversing Valve Config
  • State 0: on for heating
  • State 1: on for cooling
Condensate Alarm
  • State 0: the condensate alarm does not shut down the system.
  • State 1: the condensate alarm shuts down the whole system.

Mounting the controller

To mount the controller, complete the following steps:

  1. Mount a 20 cm (8 in.) section of 35 mm (1.3 in.) DIN rail horizontally.
    Note: Mount the controller in the horizontal position.
  2. On the back of the controller, extend the two mounting clips.
    Mounting the controller
    Figure 1: Pull down lower mounting clips
  3. Place the controller on the DIN rail.
  4. Push the bottom mounting clips inward (up) to secure the controller on the DIN rail.
    Mounting the controller
    Figure 2: Push up lower mounting clips

Wiring the controller

Zone bus terminal block

The zone bus terminal block is a grey, removable, 4- terminal plug that fits into a board-mounted jack. Wire the removable zone bus terminal block plugs on the controller on the top row of the stacked connector, and other field controllers in a daisy-chain configuration using 3-wire twisted, shielded cable as shown in the following figure.
Wiring the controller
Figure 3: Zone bus terminal block wiring

1Terminating device on the zone bus
2Zone bus terminal block plugs
3Daisy-chained device on a zone bus segment
4Connects to the next device on the zone bus.

Table 2: Zone bus daisy chaining configuration

Icon Note: The zone bus shield (SHD) terminal is isolated and can be used to connect (daisy chain) the shields for zone bus wiring.

Sensor bus terminal block

The sensor bus terminal block is a brown, removable, 4- terminal plug that fits into a board-mounted jack. Wire the removable sensor bus terminal block plugs on the lower port of the dual stacked connector to the controller, and other sensor bus devices in a daisy-chain configuration using a 4-wire twisted, shielded cable as shown in the following figure.
Wiring the controller
Figure 4: Sensor bus terminal block wiring

1Terminating device on the sensor bus
2Sensor bus terminal block plug on the terminating device
3Daisy-chained device on a sensor bus segment
4Sensor bus terminal block plug on the daisy-chained device
5Cable shield connection
6Connects to the next device on the sensor bus.

Table 3: Sensor bus daisy chaining configuration

Icon Note: The PWR terminal supplies 15 VDC. The PWR terminal can be used to connect (daisy chain) the 15 VDC power leads on the sensor bus.

Supply power terminal block

The 24 VAC supply power terminal block is a gray, removable, 3-terminal plug that fits into a board-mounted jack on the top right of the controller. Wire the 24 VAC supply power wires from the transformer to the HOT and COM terminals on the terminal plug, as shown in the following figure. The middle terminal on the supply power terminal block is not used.
Disconnect supply power to controller by unplugging supply Power plug from supply power jack.
Wiring the controller

Icon Note: The supply power wire colors may be different on transformers from other manufacturers. Refer to the transformer manufacturer’s instructions and the project installation drawings for wiring details.

Setting the VEC address using the local display

To set the VEC address using the local display, complete the following steps:

  1. To access the menu, press the ENT (Enter) button.
  2. Navigate to the Controller menu with the up and down arrows, and press the ENT button.
  3. In the Controller menu, navigate to Network and press the ENT button.
  4. In the Network Parameters section, navigate to Address and press the ENT button. The display shows the default address value.
  5. Press the ENT button. The address blinks.
  6. Use the up or down arrow to increase or decrease the address to the value you want. Press the ENT button. The address stops blinking and the display shows the old address.
  7. Press either the up or down arrow. The screen refreshes to the new address.
  8. Press ESC (Escape) repeatedly, until you return to the main screen. Ensure that the main screen shows that the system is operational.

Configuring sensors

To configure the installed sensors, complete the following steps:

  1. Navigate to the Details menu.
  2. Navigate to the Service menu and select the Inputs section.
  3. Select the installed sensors using the drop-down menus for each parameter.

Updating the VEC

To update the VEC with the heat pump application, complete the following steps:

  1. Go to verasyscontrols.com, and log in with your credentials.
  2. Navigate to Product Information & Support > Device Updates.
  3. Download the package file for the application to the root folder of a USB 2.0 drive. The package file name is the following: VEC100-Heat Pump_xxxx.pkg
    Icon Note: Ensure that the USB drive is formatted as FAT or FAT32.
  4. Insert the USB drive into the USB port on the VEC.
  5. If the download does not start immediately, then in the controller’s local display, select the Update and Load Firmware option, then choose the package file on the USB drive, and press Enter.
  6. When the application update finishes, use the Verasys Smart Building Hub (SBH) or the local display to configure the controller.

COBP wiring diagram

COBP wiring diagram
Figure 6: Changeover bypass wiring diagram – VEC100

NumberDescriptionObject name (if given)
1Economizer Damper Output (optional)MAD-O
2Supply fan output (to fan VFD)SF-O
3Supply fan command (to fan VFD)SF-C
4Compressor stage 1 commandCOMP1-C
5Reversing valve 1 commandREV1-C
6Compressor stage 2 commandCOMP2-C
7Reversing valve 2 commandREV2-C
8Supplemental heat commandSUPHTG-C
924 V HOT to damper motorn/a
1024 V COM to damper motorn/a
1124 V COMn/a
1224 V HOTn/a
13From last devicen/a
14To next devicen/a
15Zone humidity sensor – monitor only (optional)ZN-H
16Return air CO2
Range: 0 ppm to 2,000 ppm, 0 VDC to 10 VDC
RA-CO2
NumberDescriptionObject name (if given)
17Return air temperature sensorRA-T
18Outside air temperature sensor
Note: This is a required sensor if the VEC100 controls the economizer. Position the sensor in a shaded area on the north side of the building.
OA-T
19Discharge air static pressure sensor
Range: 0 in. W.C. to 5 in. W.C., 0 VDC to 5 VDC
DA-P
20Discharge air temperature sensorDA-T
21Condensate alarmCOND-A
22Supply fan status (air proving switch, optional)SF-S
23Purge input (optional)PURGE-S
24Filter status (optional)FILTER-S

Table 4: Changeover bypass wiring diagram

VAV wiring diagram

wiring diagram

NumberDescriptionObject name (if given)
1Economizer Damper Output (optional)MAD-O
2Supply fan output (to fan VFD)SF-O
3Supply fan command (to fan VFD)SF-C
4Compressor stage 1 commandCOMP1-C
5Reversing valve 1 commandREV1-C
6Compressor stage 2 commandCOMP2-C
7Reversing valve 2 commandREV2-C
8Supplemental heat commandSUPHTG-C
924 V HOT to damper motorn/a
1024 V COM to damper motorn/a
1124 V COMn/a
1224 V HOTn/a
13From last devicen/a
14To next devicen/a
15Zone humidity sensor – monitor only (optional)ZN-H
16Return air CO2
Range: 0 ppm to 2,000 ppm, 0 VDC to 10 VDC
RA-CO2
NumberDescriptionObject name (if given)
17Return air temperature sensorRA-T
18Outside air temperature sensor
Note: This is a required sensor if the VEC100 controls the economizer. Position the sensor in a shaded area on the north side of the building.
OA-T
19Discharge air static pressure sensor

Range: 0 in. W.C. to 5 in. W.C., 0 VDC to 5 VDC

DA-P
20Discharge air temperature sensorDA-T
21Condensate alarmCOND-A
22Supply fan status (air proving switch, optional)SF-S
23Purge input (optional)PURGE-S
24Filter status (optional)FILTER-S

Table 5: VAV wiring diagram

Commissioning the system

To activate the outputs and verify system operation, navigate to the Commissioning menu, change Start Commissioning to Trigger, and adjust outputs individually.

The following table describes the Details > Service > Factory menu options.

Object or parameterDescriptionAdjustableDefaultsEnum set or range
Number of Heat Pump Stages InstalledSets the number of heat pump stages installed.Adjustable20 to 2
Supplemental Heat InstalledSets whether supplemental heating is installed.AdjustableNo0 = No

1 = Yes

Economizer InstalledSets whether the economizer is installed.AdjustableNo0 = No

1 = Yes

Air Proving Switch SetupSelects the type of setup for airflow proof.AdjustableNone0 = Fan Status Device 1 = Duct Static Pressure Sensor 2 = None
Runtime EqualizationEnables the device based on runtime.AdjustableNo0 = No

1 = Yes

OAT Cooling Lockout
Temperature
Sets the temperature at which outside cooling lockout occurs.Adjustable50°F (10°C)0°F to 100°F (-18°C to 38°C)
Economizer Minimum Position SetpointSets the minimum outside air damper position.Adjustable20%0% to 100%
Rooftop Controller TypeSets the controller type to changeover bypass or VAV.AdjustableChangeover Bypass0 = Changeover Bypass 1 = VAV
Variable Speed DriveSets whether the VEC100 controls a VFD fan instead of a bypass damper when the rooftop controller type is set to changeover bypass.AdjustableFalse0 = False

1 = True

Supply Air Temperature Alarm OffsetIf SAT is not in this value range, the SAT alarm delay starts. Examples: If the supply air setpoint is 55°F and this is set to 5°F, then the supply air must be under 60°F, or the delay timer starts. If the supply air setpoint is 110°F and this is set to 5°F then the supply air must be above 105°F, or the delay timer starts.Adjustable5 delta °F (2.78 delta °C)0 delta °F to 25 delta °F (0 delta °C to 14 delta °C)
Supply Air Temperature

Alarm Delay

Sets the amount of time that must pass before the SAT alarm occurs.Adjustable20 min0 min to 120 min
Cancel ASCD TimersResets the minimum on and off timers.AdjustableFalse0 = False

1 = True

Demand Ventilation FeatureEnables or disables the demand ventilation feature.AdjustableOff0 = Off

1 = On

Reversing Valve ConfigSets the reversing valve for heating or coolingAdjustableOn for Clg0 = On For Htg 1 = On For Clg
Condensate AlarmIf you set this parameter to Yes, the condensate alarm shuts down the whole system.AdjustableNo0 = No
1 = Yes

Table 6: Details : Service : Factory

Product warranty

This product is covered by a limited warranty, details of which can be found at www.johnsoncontrols.com/buildingswarranty.

Software terms

Use of the software that is in (or constitutes) this product, or access to the cloud, or hosted services applicable to this product, if any, is subject to applicable end-user license, open-source software information, and other terms set forth at www.johnsoncontrols.com/techterms. Your use of this product constitutes an agreement to such terms.

Single point of contact

APACEurope

NA/SA

JOHNSON CONTROLSJOHNSON CONTROLSJOHNSON CONTROLS
C/O CONTROLS PRODUCT MANAGEMENTWESTENDHOF 3 45143 ESSEN507 E MICHIGAN ST MILWAUKEE WI 53202
NO. 32 CHANGJIJANG RD NEW DISTRICTGERMANYUSA
WUXI JIANGSU PROVINCE 214028
CHINA

Contact information

Contact your local branch office: www.johnsoncontrols.com/locations
Contact Johnson Controls: www.johnsoncontrols.com/contact-us

Logo

 

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals