Lennox 54w27 Lontalk Control Kit Instruction Manual

Lennox 54w27 Lontalk Control Kit Instruction Manual

LENNOX logo

CONTROLS
KITS AND ACCESSORIES

508137-01 3/2021
Supersedes 506693-02

LonTalk® Module Kit

INSTALLATION INSTRUCTIONS FOR
LonTalk® MODULE (54W27) USED WITH COMPATIBLE ROOFTOP UNITS

LENNOX 54W27 LonTalk Control Kit

warning 4CAUTION
Electrostatic discharge can affect electronic components.
Take precautions during unit installation and service to protect the unit’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by
putting the unit, the control and the technician at the same electrostatic potential. Neutralize electrostatic charge by touching hand and all tools on an unpainted unit surface
before performing any service procedure.

warning 4IMPORTANT
Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property.
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.

warning 4 IMPORTANT
When adding this module to an existing M2 Unit Controller, the M2 firmware must be v7.07 or higher.
Look on LennoxPros.com for the latest firmware, or call Lennox technical support at 800-453-6669 for firmware update information.

General

The LonTalk® module allows communication between the Lennox M2, M3, and M4 unit controllers and a LonWorks® network. The module is LonMark® certified to design
guidelines version 3.4.
For assistance, contact Lennox Technical Support at 800453-6669.

Installation

warning 4 IMPORTANT
A small flat-head screwdriver is required to connect the communication wire to the SmartWire connector.

  1. Remove power to the unit.
  2. Open the compressor access doors.
  3. Plug the LonTalk module onto the M2, M3, or CORE Unit Controller (M4). Guide pins will align the module with the Unit Controller connector.
  4. Connect the LonTalk SmartWire connector.
    LENNOX 54W27 LonTalk Control Kit - bar code
  1. Upon powering up the unit controller, the following is applicable:

PRODIGY M2 UNIT CONTROLLER

This controller will automatically recognize the LonTalk module and begin communications provided the network as been correctly configured.

To configure the LonTalk Network, go to: SETTINGS > CONTROL = LONTALK PRODIGY M3 UNIT CONTROLLER

To enable the LonTalk module, go to: SETUP > INSTALL and run the setup wizard.

When Configuration ID 1 appears on the screen, configure position 5 as L. This will enable the LonTalk module.

To configure the LonTalk Network, go to:

SETUP > NETWORK INTEGRATION = LONTALK LENNOX® CORE UNIT CONTROLLER (M4)

To enable the LonTalk module,

  1. Go to RTU MENU > SETUP > INSTALL
  2. When CONFIGURATION ID 1 appears on the screen, configure position 5 as This will enable the LonTalk module.
  3. To configure the LonTalk Network

Go to RTU MENU > NETWORK INTEGRATION > NETWORK SETUP WIZARD = LONTALK

Operation and Functional Description

LONWORKS NETWORK CONNECTION
The LonTalk module has an FTT-10A Free Topology Transceiver for network communication. The FTT-10A transceiver network supports free topology wiring and will accommodate bus, star, loop, or any combination of these topologies. The module can be located at any point along the network wiring. This capability simplifies system installation and makes it easier to add nodes when required.

LONWORKS NETWORK CABLE
The LonWorks TP/FT-10 network requires Echelon qualified twisted-pair communication cables such as Belden 8471 or NEMA Level 4 cables. Other Echelon approved equivalent cables may also be used depending on the application. The Belden 8471 or NEMA Level 4 cables are rated for plenum use.

The network cable should be routed using best practices to avoid induced noise. Do not route alongside power lines, or in proximity to high voltage or high-frequency devices, such as ignition controls and variable frequency drives. The average temperature of the wire must not exceed 131°F (55°C).

NETWORK LIMITS (FREE TOPOLOGY)
The LonWorks TP/FT-10 free topology network is limited to a maximum of 64 nodes per segment. The maximum total bus length and the maximum node-to-node length is1640

ft. (500 m) for Belden 8471 or NEMA Level 4. Maximum lengths are less for other smaller wire size cables.
Only one termination circuit module is required at any location along with the network. Refer to Echelon LonWorks FTT- Transceiver User’s Guide for additional details.

FREE TOPOLOGY NETWORKS
Free topology segments require a termination circuit for proper performance. Only one termination circuit module is required at any location along with the network.

LENNOX 54W27 LonTalk Control Kit - Figure 1

NETWORKS LIMITS (DOUBLYTERMINATED TOPOLOGY)
The LonWorks TP/FT-10 Doubly-Terminated topology network is limited to a maximum of 64 nodes per segment. The maximum total bus length is 5000 feet (1524 meters) for Belden 8471 or NEMA Level 4. Maximum bus lengths are less for other smaller wire-size cables. The maximum stub length is 9.8 ft. (3 m). In many cases, this bus network is connected in a daisy chain manner where the bus is wired directly to each node, so the stub length is zero.

Two field-provided termination circuit modules are required for each segment. One must be located at each end of the network.

LENNOX 54W27 LonTalk Control Kit - Figure 2

NETWORK BUS TERMINATION
To install the network bus terminal module 37X75, connect the brown and yellow wires to the network bus that requires single termination and connect the brown and orange wire to the network bus that requires double termination. The unused termination module wire must be covered with a wire nut to prevent potential grounding problems.

NETWORK INTEGRATION
A network configuration tool such as LonMaker® is required to commission the LonWorks network. Press the service button on the LonTalk module to generate a service message that contains the Neuron ID.

Other commissioning methods may be used. The Neuron address is located on the LonTalk module. An External Interface File (XIF) is available for configuration prior to installation.

PRODIGY RESET
The Prodigy unit controller may be reset using nviRequest with enumeration RQ_RESET sent to NodeObject function block.

ZONE OR ROOM SENSOR CONTROL
In order to use room temperature setpoints, the Prodigy unit controller must be configured for Zone Temperature control mode. This may be done through the Prodigy display.

PRODIGY – M2 ZONE SENSOR CONTROL CONFIGURATION
PROCEDURE
In order to use nviSpacelAQ, nviSpaceRH, or NVI SpaceTemp, the Prodigy M2 unit controller must be configured.

  1. Go to the M2 Unit Controller user interface.
  2. Use the select button to enter the menu, and use the up/ down buttons to scroll through the options.
  3. Go to SETTINGS > CONTROL > LONTALK > CONTROL MODE and select ZONE for the Zone Temperature control mode.

This is the same as setting the Prodigy ECTO (Electronic Config To Order) parameter 6.01 to a value of 1.

PRODIGY – M3 ROOM SENSOR CONTROL CONFIGURATION
Procedure

In order to use nviSpacelAQ, nviSpaceRH or nviSpaceTemp, the Prodigy M3 unit controller must be configured.

Go to the M3 Unit Controller user interface.

  1. Go to SETTINGS > GENERAL > CONFIGURATION ID 1 and verify or change position 5 is set to
  2. Go to: SETUP > NETWORK INTEGRATION and set to TALK.
  3. Set CONTROL MODE to either MONITOR ONLY or ROOM SENSOR. If ROOM SENSOR is selected, then enabled the applicable sensors (CO2, RH or TEMP).

CORE UNIT CONTROLLER (M4) ROOM SENSOR CONTROL
CONFIGURATION PROCEDURE

In order to use nviSpacelAQ, nviSpaceRH or nvi SpaceTemp, the CORE unit controller must be configured.

Go to the LENNOX® CORE SERVICE APR

  1. Go to RTU MENU > INSTALL > CONFIGURATION ID 1 and verify or change position 5 is set to L.
  2. Go to SETUP > NETWORK INTEGRATION and set to
  3. Set CONTROL MODE to either MONITOR ONLY or ROOM SENSOR. If ROOM SENSOR is selected, then enabled the applicable sensors (CO2, RH or TEMP).

DATA UPDATE RATE

If nviSpaceTemp, nviOutdoorTemp, nviSpaceRH, or nviSpacelAQ are used, the data needs to be updated within five minutes to be valid.

LANDMARK FUNCTION PROFILES
The Prodigy LonTalk module contains two LonWark functional profile function blocks, space comfort controller-rooftop and discharge air controller. It also contains a Lennox specified functional block, a virtual function block containing the network configuration variables and a node object.

NVI DUPLICATION
nviOccSchedulel, (in sccRooftop), and nviOccSchedjle, (in dischargeAirCont), are duplicate network variable inputs and only one should be used.
Also, nviFanSpeedCmd and nviSupFanCap have the same functionality and only one should be used.
Both nviSetpoint and nviHCSetpoints change the effective temperature setpoints and only one of them should be used.

DEVICE FUNCTION BLOCKS

LENNOX 54W27 LonTalk Control Kit - Figure 4LENNOX 54W27 LonTalk Control Kit - Figure 5

Table 1. Network Variables (Sorted Alphabetically)

SNVT NameSNVT IndexSNVT NameSNVT IndexSNVT NameSNVT Index
nciBldgStaticSP40nviSetpoint8nvoOAFlow101
nciBypassTime104nviSetptOffset9nvoOutdoorTemp35
nciDACISP38nviSpaceDehumSP53nvoRATemp63
nciDAHtSP39nviSpacelAQ20nvoRecentEvent_171
nciDuctStatSP41nviSpaceRH19nvoRecentEvent_272
nciFanOperation66nviSpaceTemp7nvoRecentEvent_373
nctocation1nviSupFanCap48nvoRecentEvent_474
nciMinOAFIowSP43nvoAirflow100nvoRecentEvent_575
nciOAMinPos5nvoBldgStatPress60nvoRecentEvent_676
nciOATSP42nvoBlowRPM102nvoRecentEvent_777
nciSetpoints4nvoBlowTorque103nvoRecentEvent_878
nciSndHrtBt0nvoBuildVersion86nvoRecentEvent_979
nciSpaceRHSetpt6nvoCatalogNo85nvoRecentEvent1080
nciSupAFSP67nvoCoolPrimary32nvoRunTimeBlower99
nviApplicMode22nvoCurrentAlarms70nvoRunTimeComp_188
nviAuxHeat Enable15nvoDehumidifier65nvoRunTimeComp_289
nviBldgStaticSP50nvoDischAirTem129nvoRunTimeComp_390
nviComprEnable14nvoDischAirTemp54nvoRunTimeComp_491
nviDACISP46nvoDuctStatPress57nvoRunTimeFrCool92
nviDAHtSP47nvoEconEnabled61nvoRunTimeHeat195
nviDuctStaticSP45nvoEffDATempSP56nvoRunTimeHeat_296
nviEconEnable16nvoEffectOccup26nvoRunTimeHeat_397
nviEmergOverride17nvoEffectSetpt25nvoRunTimeHeat_498
nviExhFanCap49nvoEffSpaceDHSP64nvoRunTimeHotGas93
nviFanSpeedCmd13nvoExhFanStatus59nvoRunTimeMaint87
nviHCSetpoints68nvoFanSpeed28nvoRunTimePowrOn94
nviOAMinPos21nvoHCSetpoints69nvoSerialNo84
nviOccManCmd11nvoHeatPrimary30nvoSetpoint27
nviOccSchedule44nvoHeatSecondary31nvoSpaceCO236
nviOccSchedulel10nvoLocalOATemp62nvoSpaceRH34
nviOccSensor12nvoLocalSpaceCO281nvoSpaceTemp23
nviOutdoorTemp18nvoLocalSpaceRH82nvoStatus3
nviPriCool Enable51nvoLocalSpaceTmp37nvoSupFanStatus58
nviPriHeatEnable52nvoModelNo83nvoUnitStatus24
nviRequest2nvo0ADam per33nvoUnitStatus155

Table 2. Network Variable Definitions

IndexSVT N81119SVT TYPOFunctional BlockSend
heartbeat
A ppl lCatlOn DeeCtiptlOn
0nciSndHrtEllSeNT_Ime_secVirtual Film tonal Brea· Avatar of 0(zero). We off the send heal beat breast

· Values be been .01 seconds and 104ffe treated as 10 seconds.

·  Ten (10) seconds is the mailman heartbeat *waled rate.)

1colocationSVT let oleoVirtualock Roc tonal StLocation label Meng.
2SNVT_ctuesuestNodeOtyect·Request an operation a mode for a Motional block will a device.

requests as: RONORMAL. RO_UPDATE_STATUS. RQ REPORT_

·  RQ RESET and RQ CLEAR RESET are suppated for the NaleOtetot Anatol brat to reset the Pricbgy conirceet.

3nvoStatusSWr_ot_stabsNxleCtyectNoRepots the stylus bra f stabile! dock.
4noiSebantsSVT fornp_setotVirtual Febbast No*· Sets default zone temperature setting for the unit.

· Vaktranges are 40-95•F.

·The cooing setwinb must be above the ccasswacfmg heating sent by the unify aubchangeover dead-band (3•F default).

·The standby setpoints as not used by the Appicaka

5ncitJAMnPosSWTkwpercentVirtual Functional Stock· Sets the outdoor* dancer Strain position.

·Used M modes were outdoor *ventilation Sr eared. except when nviOAPWce if wad.

6nciSpeceRHSetptSNP/T .ev percentVirtual Roc tonal

back

· Defines a deburnktecalca serpent for Me controlled space.

· Not used when neSpaceDebumkISP is valet.

7nviSpaceTerroSMILlernp_psc.:Rooftop· Stop led range: 36254o-100•F.

· Mail be updated %ebb 5 nimble,.

· Must be enabled %eh ECTO 5.27 (Feature not *Sable ei Prodigy 20 Meat release).

8nv.SetxxntStni_leinp j)sccRcolle:· Used beet tie temperature setpoints fa the occupied mode. NOTE: The unoccupied spawns are not changed.

· I a yak, value is not present tie appropriate select% as configured ei noSetweds vat be used. The “syrnnwerbal method is used.

· The efface..e healkoct help:Mte for the occupied node me derived from

viewpoint plus / minus had the occupied headbands yet          Prodigy ECT06.15
(3T default) a Prodigy 2.0 Parameter 152:

elfecive_occupiedcod • mtSetpokil +0.5 (clengener_deedband ) efleciveoccupiedfieet= miSetpcint -0.5 (cAangeoner_deadband)

9nviSe veersSNYTIamppscroopUsed lo shift the effective occupied lemperakse sellers by adding neSelp1011sel b the anent satanic
10nviOccSonedulatSNYTbdeventscroopOnly arrant stale occupancy models were swooned.
11nytOccManCnx1SNYT_occupencyscroopUsed to command be Space Canton Conttler into oillerent occupancy node
12nviOccSentaSNYT_occupencyscroopUsed to Mcketethe; the essence of occupants in tie contracted space.
13nviFariSpeedCrndSNVT_verithscroopUsed to set the unite Mower speed.
14nviComprEnatteSNVT MahnsccRoollopUsed lo dater commit:4 operation.
15nviAuxHeatEnatieSVT swishso rooftopUsed to cleat* anctiary heel operation.
16nviEconEnetteSENT sw=anSCCRcollopUsed lo enabled dater economizer operator.
17SNVT_hvacemagsccRoolto;_· Used to command the device at different emergency modes.
·Swooned eturnerallons:EMERG NORMAL
EMERGPRESSUFIZE
EMERG DE PRESSUReE
EMERG PURGE
EMERG_SHUTDOV*4 EMERG_NUL
18nvrNiloaTernoSleafernp_psocRooftop· Supported range: -30.6 b 131,F.

·  Input must be updated! Shin 5 minutes.

19nviSpaceRHSWilev_percentsccRooflop· bout must be updated Lett 5 Stubs.

· Must be enabled velhECTO 5.27

RnviSpace1A0SWT_ppmsccRcoftop·   Supported range: 0 to 2,000 Mee

· We mule be updated vathit 5 minutes.

· Must be enabled x4th ECTO 127 (Feast not available in Prodigy 20 mien rebate).

21nviOAMnPosSWT_Mv_percentsccRooftop· Used to provide a dynamic narlirriuni post., seawall for an OuteXt as damps.

· Wien wad it all supersede nclOAMInPce.

22nviAppe:MadeSVT hvac_rmdeso rooftop·Used legit IT trip mode. Swooned values: AUTO. HEAT ONLY.
POOL· Must be updated weir the 120 rules, if used.
23nvoSpaceTempSNVT_Iarp_psccRcc41:9Yes·The output S is the effective space temperature value that I control ks using.

· The support range’s 38 b 100T.

24nvoUrstStatusSNVOivac_statusScroobyYesRepots lie controller status.
25nvoEffedSeplSNVT_terrp_psccRoof bpYesRepots Pe current effective space temperature setpoint
26′nvoEffectOccupSNVLoccupancyscollopNoReports are effective occupancy able (see Appendix B).
27nvoSetpcMilSVT terrp_psccRoof bpNoReports Pe current special without the app aka of nviSetplOffset
28rwoFanSpeedSNVItseltchsccRcofIcgYesReports the current unit blower speed
29rwc0ischArTernpSNVItterrp_pCCRC of kgNo·Repots tie discharge temperature value.

·  Supported range. -8 b +163°F.

30rwoHealPrimaySNVItlev_percenlCCRC of lopYesReports the current pinky heal outul value.
31nvoHeatSeccodatySVT lev_percemsccRooltopYesReports fie current secondary heal output value (heal pumps coy).
32nvoCcoPrimatySNVItlev_percenlCCRC of kgYesReports the current ccceing output %due.
33nvo0ADamperSVT lev_percentsccRoof bpYesReports fie current outdoor as dancer post ion.
34nvoSpaceRHSNVIllev_percentscollopYesReports to effective space relative hun*Iffy *Due.
35mcOuldocifempSVT terrp_pscollopYes· Reports the &leave outdo:. temperature value.

· Supported range. -30 b •130T.

38nvoSpaceCO2SNVT_pynCCRC of IcyYes· Repot; the effective space is eaten dioxide W.

· Supported range.° b 2.000 ppm.

37moLocalSpacermpSNVf_temp_pscollopYes· Report the space temperate moused by the Pc* eke sauce.

· Suppyled range. 38 b 100T.

38noDACISPSNVT_Ierrp_pVirtual Funacnal Block· Sets the debut! discharge air cooking temperate set pont

·Supported range: 40 b 100T.

39noDAHtSPSNVT_ternp_pVirtual Fundaial Block· Sets the default discharge air heating temperature selpc.e.

· Supported range: 60 b 1407.

40noCiuttSPISPSNVT_press_pVirtual Functicaal Block· Sets re-debut! duct Pak pressure sal pont

·Supported range: 0 lo 1245Pa.

41nciOATSPSNVT_terrp_pVirtual Functional Block· Sets tie outdoes’ sir temperature special loanable free-cooking for units with escapades.

·                Supported range:40 b 75T.

42noBldgSlakSPSNVf_press_pVirtual Functional Block·Sets tie debit, basking slat pressure set pool for exhaust miter &

·Supported range -124.5 b 1245 Pa.

43noMerOARowSPSNVf_flowdual Virt Fundicoal Brick·Set to delauel outdoor at lbw for SmanAalbw Ty enabled roof by units.

· Supported range -0 b 150cfmAco

· Mulkoly the CFMAco value term Mirage of fie unit b drove be value in CF M.

44NEC scheduleSVT tote**dischargeArCcrilOnly the current slate is supported.
45nvOudSlaticSPSNVT_Ixess_pckschargeArCcal· Sets re dud abbe pressure afloat.

·Suspected range:0 b 1245Pa.

48neDACISPSNVT_Ierrp_pdischargeAirCon1· Selo tie discharge* cooking temperature selp*A

· Swiveled range:40 b 100T.

47nv0AHSPSNVT_Ierrp_pckschargeASCcol· Sets lie discharge* heating tempera* setpoint

·Supported range: 60 b 140W.

48nviSupFanCapSVT lev_percen1cbschargeAtecttSets the unit’s blower speed.
49msExhranCaPSNVT_Iev_percen1duchargeArCcolSet the unit’s exhaust fan speed.
50neEllOgStalcSPSNVT_press_pckschargeketcril– Sets re building abbe pressure sepont kr exhaust carol.

– Supply range -124.5 to 124.5 Pa.

51menCcolEnableSNVT snitchcbschargeArCcmUsed lo disable cant: ream’ opera.
52nviPnHeatEnableSNVT svalchdtschargeks-CcalUsed to disable primary heating operation.
53neSpaceDehurnSPSNVT_Iev_percenlduchargeArCcolSet the dehurnidficabco RH sepcinl.
54mcDschArTenpSNVT_IerppscRcolopno·Repot te dschage *terfamatue.

·Supported range: -8 b 131T..

55rwoUnitStalus1SNVT_hvac_stalusduchargeArCoilYesReports be cetera* status. Same as nvoUnitStalus in sccRcollop functico block.
56nvoEfIDATempSPSNVf_ternp_pdechargeArCcalYesReports fie effective discharge as a temperate percent
57nvoDuctSlatPressSN VT _roes s_pdischargeArCcalYes· Report the duct slack pressure.

· Suppyled range: 0 b 1245Pa.

58nvoSupFariStatusSNVLswecticbschargeArCcmYesReports um blower speed.
59nvoExhFanStalusSNVT_svelchdischarge-CyrilYesReports exhaust fan speed.
60nvoEconEnatledSNVT_seetchdischargeArCcolYesReports tee-access status of economizing
61mollIdg.SiatRessSNVT_press_pdischergeturContYes·   Report the budding static pressure.

·   Suspected range: -124.5 to +1245 Pa.

62nvoLoctiOATetrpSFrtetrp_pdechergeturContYeS·   Reports boat’   meastsed cutter temperature.

·   Supported range: -30 to +13ot

63nvcRATempSNVT tempt’disc hargeAirOontYes·   Ribcvls eff Galva glum ars temPeralure.

·   Supported range: -810 +1631.

64moEffSpaceCHSPSNVT_press_pclochargeAkCcntYesReport effedne *save humidity seeing for clehutradifican.
85moDelumktrierSWT switchdechargsfurCentYesReport status of dehuniddicenn cymbal.
66nciFenOperafenSCPTbnOperaticnVaal F unapt* BlockSets the operation male for the unit *cam Outing occupied slats
67noSupAFSPUNVT SupPF_SpsVerbal Funcional Back·   Set the defaultAirflow stenos for a Smartairllowns enabled roof Count in 10 sec Una.

·   Fa vied ranges please refer b theAppendock

68insHCSebanisSWT temp semiLennox·     Valkil raves are 4043451 (ceding).

·   The cooing setpoints must be above the corresponda hoeing sent by the units Aulochangeerva Deadband (ECTO 615. 31-cleavage or PICOicy 2.0 Pararneex 152).

·   The standby set pants ate not used by the Application

69nvonGSacintsSVT Iterp_selptLennoxNo·   Reports zone “Immature setpoints.

·     Standby setpoints a not teed and are returned %Mt to unoccupied values.

70nvoCurentAlemisUNVT_arrentNarrnsLennoxYesReports currently active alarm codes.
71moReceneamm_lUNVT eventLennoxYesReams most recta Sinn Cole.
72moRecenEven1_2UNVT eventLennoxNoReams second most menu &M.
73nvoRecenlEvent_3UNVIlevent1011110XNoReport alarm.
74nvoReoenlEven1_4UNVIleventLennoxNo
75nvoRecenEvenl_5UNVT_ewsnt!sonarNo
78nvoRecenlEvent_6UNVT_eventLennoxNo
77moRecenEvent_7UNVT eventlennoxNo
78nvoReceellEvent_8UNVT eventlennoxNo
79nvORICe11Evillnl9UNVIleventkenosNo
80meReCettlEwIn410UNVT eventLennoxNo
81molocalSpaceCO2SVT _ppmlemmaNo·   REpats locally measured apace carbon der** level.

·   Suspected range: 0 to 2.000 ppm.

82moiccalSpaceRHsave 1ev_CercenbranNoReport IcceY measured space relative tumidly level.
83nvoMoceiNoSWT s V_ascLennoxNoReport unit model neater.
84NV senate,SWT stawLennoxNoRepaid unit serial number.
85nvoCatelegNoSWT sv_ascLennoxNoReport unit catalog number.
86nvoStuildVersbnSNYT s v_ascbowsNoReport flarraetevetson siring.
87moRunTinebtentUNVItmairtnnimesLennoxNoRepot air filer. Mosta be and INlamp mn-taws.
88nvoRunTirner..cap_lUNVIlminutes_cyclesWaxNoReport nut-same and cycle count for cars:testa 1.
89nvoRtmTmeCcep_2UNVT_rrenufes_cyclesLennoxNoRenege run-bme and cycle count for canpressa 2.
90nvoRunTmeCarp_3UNIVT_mriules_cyclesLennoxNoReport run-bme and cycle count for empresses 3.
91nvoRunTmeCarp_4UNVT_mates_cyclesLennoxNoReport nut-ere and cycle count for cars: gasser 4.
92nvoRunTrneFrOsolUNVT rrinuies_cyclesLennoxNoReport 111141110 and cycle count br free cooing operation.
93nvoRunTenelistGasUNVT rrinuies_cyclesLennoxNoReports 111141110 and cycle count to hot gas Mimes dehunelfIcatiOn.
94nvoRunTimelaavrOnUNVIIrrinutes_cycleskenosNoReport run-frne and cycle count for unit poems cc.
95nvoRunTineHeat_1UNVIIninutes_cyclesLennoxNoReport nn-one and cycle count for heat stage 1.
98nvoRtmTmeHeat_2UNVT_rnnuies_cyclesLennoxNoReport run-lime and cycle count for heat stage 2.
97nvoRunTmeHeat_3UNWT_mrittles_crlesLennoxNoRocca run-lime and cycle count for heal stage 3.
98moRunTineHeat 4UNVT rrinuies_cyclesbowsNoReport 1111-1010 and cycle count for heat stage 4.
99moRunTrneElkwerUNVT rrinuies_cyclesWinosNoReams 1111-1010 and cycle count to Meer.
100overflowSNYT flowseRookopYea·   Reports the amount of current supply* low
·   Supported range: 0480 admin
101nvo0A1lowSVT flowclischarceeirCcalYes·   Reports the amount of cutloco airflow.
·   Supported range: 0490 min
102moBlovARPMSNVT_rpm1011110XYes·   Risme the blower moor weed
·   Suppabd range: 01500 rpn
 103nvoBlowTorqueSNVTlev_percentLennoxYes• Reports the PWM of an ECM blower motor.
• Supported range: 0 – 100 %
 104nciBypassTimeSNVT_time_minVirtual Function
Block
 –• This configuration defines the maximum amount of time that the controller can be in the bypass (occupancy) mode following a single bypass request from either a local
(hardwired) bypass switch or nviOccManCmd.
• Additional Bypass requests can restart the timer.
Table 3. Variable Type Definitions
SNVT TypeDefinition
SCPTfanOperationfan_operation_t Enumeration, 1 byte Value Identifier Notes -1 (OxFF) HVF_NUL Invalid Value 1HVF_CYCLE Fan cycles with heating and cooling 2 HVF_CON_CYCLE Continuous in occu pied, cycles in occupied standby
SNVT_hvac_emergemerg_tEnumeration, 1 byte
SNVT hvac _modehvac tEnumeration, 1 byte
SNVT_hvac_statustypedef struct { hvac t mode; signed long heat_output_primary; signed long heat_output_secondary; signed long cool_output; signed long econ_output; signed long fan_output; unsigned short in alarm; } SNVT_hvac_status;
SNVT_lev_percentSigned Long, 2 bytes
Valid Type Range: -163.840 .. 163.830 Type Resolution: 0.005
Invalid Value: 32,767 (0x7FFF)
SNVT_occupancyoccup_tEnumeration, 1 byte
SNVT_ppmUnsigned Long, 2 bytes Valid Range: 0 .. 65,535 Parts per Million (ppm)
SNVT_press_pSigned Long, 2 bytes
Valid Type -32768 .. 32,766 Pascals Invalid Value 32,767 (0x7FFF)
SNVT_str_ascASCII character string with NUL terminator 30 characters max, 31 bytes
SNVT_switchtypedef struct { unsigned value; signed state; } SNVT_switch; value: percentage of full scale, resolution 0.5% state: can either be -1 (NULL), 0 (OFF), or 1 (ON)
SNVT_temp_pTemperature
Signed Long 2 bytes
Valid Range: -273.17 .. 327.66 Resolution: 0.01 Degrees Celsius Invalid Value: 32,767 (0x7FFF)
SNVT_temp_setpttypedef struct { signed long occupied_cool; signed long standby_cool; signed long unoccupied_cool; signed long occupied_heat; signed long standby_heat; signed long unoccupied_heat } SNVT_temp_setpt;
SNVT_flowFlow Volume
Unsigned Long, 2 bytes
Valid Range: 0 .. 65,534 lit/sec Resolution: 1 lit/sec
Convert to CFM
1 cfm = 0.4719474432 lit/sec
SNVT_rpmRevolutions per minute
Unsigned Long, 2 bytes
Valid Range: 0 .. 65,534 RPM Resolution: 1 RPM
SNVT_time_minElapsed Time
Signed Long, 2 bytes
Valid Range: 0 .. 65,535 Minutes Resolution: 1 Minute
SNVT_time_secElapsed Time
Signed Long, 2 bytes
Valid Range: 0 .. 6,5535 Seconds Resolution: .01 Seconds
SNVT time stamptypedef struct { signed long year; unsigned short month; unsigned short day; unsigned short hour; unsigned short minute; unsigned short second; } SNVT_time_stamp;
SNVT_tod_eventtypedef struct { occup_t current_state; occup_t next_state; unsigned long time_to_next_state; }SNVT_tod_event
UNVT_currentA !armstypedef struct { unsigned short AlarmCount; event_code_t AlarmCode1; event_codet AlarmCode2; event_code_t AlarmCode3; event_ cadet AlarmCode4; event_code_t AlarmCode5; event_code_t AlarmCode6; event_code_t AlarmCode7; }U NVT_currentAlarms;
UNVT eventtypedef struct { event_code_t Event; struct EventStatus { unsigned reserved :1; unsigned currentlyActiveAlarm :1; unsigned UnitOffOnAlarm :1; unsigned reserved5bits :5; }; SNVT time stamp EventTime; };UNVT_event
UNVT_maint_run timestypedef struct { signed quad filter_time_minutes; signed quad belt_time_minutes; signed quad UV Jamp_time_minutes;}UNVT_maint_runtimes;
UNVT min utes cyclestypedef struct { signed quad minutes; signed quad cycles; }UNVT_minutes cycles;
UNVT_SupAF_Stpstypedef struct { unsigned long HeatSP; unsigned long HiCoolSP; unsigned long MHCooISP; unsigned long MLCooISP; unsigned long LoCoolSP; unsigned long VentSP; unsigned long SmokeSP; }UNVT_SupAF_Stps

All the above parameters follow the same unit convention as SNVT flow.

Network Configuration Parameter Implementation

The following table show which Prodigy ECTO (Electronic Config-To-Order) parameters are updated with Network Configuration Parameter (nci) parameter updates.

Parameters Refer to Prodigy Application Guide for ECTO details.

Table 4. Network Configuration Parameter to Prodigy M2
Electronic-Config-To-Order Parameter Relationships

NCIECTO
nciBldgStaticSP8.20
nciBypassTime6.06
nciDACISP7.16
nciDAHtSP7.10
nciDuctStatSP0.16
nciFanOperation6.17
nciMin0AFlowSp10.17
nciSupAFSPHeatSP — 10.5 HiCoolSP — 10.2 MHCooISP— 10.4 MLCooISP — 10.3 LoCoolSP — 10.1 VentSP 10.6

SmokeSP — 10.7

nciOAMinPos5.24
nciOATSP6.26
nciSetpoints6.02 — 6.05
nciSpaceRHSetpt4.25

The following table shows which Prodigy 2.0 Parameters are updated with Network Configuration Parameter (nci) parameter updates.

Parameters Refer to Prodigy 2.0 Application Guide for

Parameter details.

Table 5. Network Configuration Parameter to Prodigy M3 and CORE (M4) Parameter Relationships

NCIParameter
nciBldgStaticSP215
nciBypassTime141
nciDACISP180
nciDAHtSP174
nciDuctStatSP37
nciFanOperation154
nciMinOAFlowSp237
nciSupAFSPHeatSP — 13 HiCoolSP — 14 MHCooISP— 15 MLCooISP — 16 LoCoolSP — 17 VentSP 18

SmokeSP — 12

nciOAMinPos132
nciOATSP160, 161, 162, 163
nciSetpoints137 – 140
nciSpaceRHSetpt106

Supply Airflow Targets

The maximum and minimum values of Supply Airflow

Targets in CFM units are as below in CFM.

Table 6. Energence® A Standard and High-Efficiency Box Supply
Airflow Targets

UNIT SIZE (A Boxes)364860
Maximum High-Speed Target and Heat Mode Target (480 CFM/ton)145019252400
Minimum High-Speed Target (280 CFM/ton)85011251400
Minimum Low-Speed Target (220 CFM/ton)6508751100
Minimum Ventilation Target (150 CFM/ton)450600750
Minimum Heat Mode Target Standard Gas Heat (S,W)975975975
Minimum Heat Mode Target Medium Gas Heat (M, Q, U, Y)112511251125
Minimum Heat Mode Target High Gas Heat Minimum (H, T, X, Z)130013001200
Minimum Heat Mode Target High Gas Modulating Heat W1 (D)N/AN/A1300
Minimum Heat Mode Target High Gas Modulating Heat W2 (D)N/AN/A1300
Minimum Heat Mode Target Electric Heat107512751600
Maximum Outdoor Airflow (150 cfm/ton)450600750
Note:

1.  Maximum Ventilation Target should be less than High-Speed Target or Heat Mode Target
2.  Maximum Low-Speed Target should be less than High-Speed Target
3.  CFM units to liters/sec units conversion factor: 1 CFM = 0.4719474432 lit/sec
4.  All CFMs are rounded to the nearest 25 CFM increment.

Table 7. Energence® A Standard and High Efficiency
Box Supply Airflow Targets

UNIT SIZE (A Boxes)36486074
Maximum High-Speed Target and Heat Mode Target (470 CFM/ton 36­60; 390 CFM/ton 74)1400187523502350
Minimum High-Speed Target (300 CFM/ton)900120015001800
Maximum Low-Speed Target (280 CFMlton)850112514001675
Minimum Low-Speed Target (170
CFMlton 36-60; 140 CFM/ton 74)
500675850850
Minimum Ventilation Target (170 CFMlton)5006758501025
Minimum Heat Mode Target Standard Gas Heat (B, S, W)975975975975
Minimum Heat Mode Target Medium Gas Heat (M, Q, U, Y)1125112511251125
Minimum Heat Mode Target High Gas Heat Minimum H, T, X, Z)N/A130013001300
Minimum Heat Mode Target High Gas Modulating Heat W1 (D)N/A125012501250
Minimum Heat Mode Target High Gas Modulating heat W2 (D)N/A150015001500
Minimum Heat Mode Target Electric Heat1075127516001600
Maximum Outdoor Airflow (150 cfm/ ton)450600750900
Note:

1.   Maximum Ventilation Target should be less than High-Speed Target or Heat Mode Target
2.  Maximum Low-Speed Target should be less than High-Speed Target
3.  CFM units to liters/sec units conversion factor: 1 CFM = 0.4719474432 lit/sec
4.  All CFMs are rounded to the nearest 25 CFM increment.

LonTalk Occupancy Signals and Blower Operation

This section describes how LonTalk occupancy signals are combined to produce effective occupancy along with the applicable unit controller parameter setting.

PRODIGY M2 UNIT CONTROLLER BLOWER OPERATION WITH EFFECTIVE OCCUPANCY

This section describes how LonTalk occupancy signals are combined to produce effective occupancy.

The blower runs to service heat and cool demands, regardless of the space occupancy. But when there is no heating or cooling demand there are options for how the blower should operate in conjunction with occupancy signals to keep the space ventilated, or the air stirred.

In SETTINGS > CONTROL menus the option for BLOWER ON OCP is selected as CYCLES or ALWAYS ON. These correspond to ECTO 6.17 settings of 0 or 1, respectively. These settings govern whether the blower runs continuously when the space is considered occupied (=1), or cycles on/ off with the heating and cooling demand (=0). ECTO 6.17 only applies to the room sensor control modes, and not to the local or network thermostat modes. In those modes, the blower is controlled by the G thermostat or DDC signal.

To comply with the California Energy Commission Title 24 standard there are two additional blower/occupancy settings that are set directly by changing ECTO 6.17 from the SETTINGS > CONTROL > ECTO menu. These two additional options are available when using LonTalk and supply a room occupancy signal (in addition to the scheduled occupancy).

There are two new CEC Title 24 settings for ECTO 6.17. Those two options are 2 and 3 and a description of both are provided in table 8.

Table 8. ECTO 6.17 Description

ECTO 6.17Occupancy Blower Duty Description
0Blower cycles on/off with demand. (Legacy usage.)
1The blower runs when either the occupancy sensor or schedule or both, indicates occupied. (Legacy usage.)
2The blower runs when both the occupancy sensor and schedule indicate occupied.
3The same as option 2, but the blower runs for 30 minutes and is off for 90 minutes when the schedule is occupied but the occupancy sensor is not occupied.

Table 9. Blower Operation Description

ECTO 6.17Occupancy Blower Duty Description
OnBlower runs continuously
CyclesBlower cycles onto with demand.
Cycles with StirBlower cycles on/off with demand; during off-cycle blower is on 30 minutes of 120.

Table 10. Blower Operation Schedule

ManualScheduleSensorEffective OccupancyM2 ECTO 6.17Blower Operation
0, 2N/AN/AOccupied0Cycles
1On
2On
3On
1N/AN/AUnoccupied0Cycles
1Cycles
2Cycles
3Cycles
3-25500, 2-255Occupied0Cycles
1On
2On
3On
3-25501Occupied0Cycles
1On
2Cycles
3Cycles with stir
3-2551-255N/AUnoccupied0Cycles
1Cycles
2Cycles
3Cycles

Table 11. Tak Occupancy Points

ModeLonTalkValue
ManualnviOccManCmd Index = 110space occupied
1space unoccupied
2refresh space occupied override timer
3-255auto; clear timer and return to the scheduler
SchedulenviOccSchedl Index = 100space occupied
1-255space unoccupied
SensornviOccSensor Index = 120space occupied
1space unoccupied
2-255auto; return to occupancy scheduler state
Effective OccupancynvoEffectOccup Index = 261space occupied
2space unoccupied
3space occupied (timed override)

PRODIGY M3 UNIT CONTROLLER BLOWER OPERATION WITH EFFECTIVE OCCUPANCY

This section describes how LonTalk occupancy signals are combined to produce effective occupancy.

The blower runs to service heat and cool demands, regardless of the space occupancy. However when there is no heating or cooling demand there are options for how the blower should operate in conjunction with occupancy signals to keep the space ventilated, or the air stirred.

  1. California Energy Commission Title 24:
    a. The legacy option settings for OCC Blower Mode are AUTO CYCLES or ON-CONTINUOUS 1. These settings govern whether the blower runs continuously when the space is considered occupied or cycles on/off with the heating and cooling demand.
    b. To comply with the California Energy Commission Title 24 standard there are two additional values for OCC Blower Mode which are ON-CONTINUOUS 2 and ON-CONTINUOUS 3. See table 13 for their descriptions.
    c. These two new options are available when using LonTalk that supplies a room occupancy signal (in addition to the scheduled occupancy).
  1. Enabling Network Type To enable the network module, go to SETUP > INSTALL and run the setup wizard. When Configuration ID 1 appears on the screen, configure position 5 to L = LonTalk.
  1. Menu Setup Procedure Method for OCC Blower Mode These blower control options are handled by the OCC Blower Mode. These setting can be changed using the following menu path:

Go to SETUP > NETWORK INTEGRATION > NETWORK = LONTALK > (additional prompts concerning network configuration and sensor types will be asked) CONTROL MODE = ROOM SENSOR >  ROOM SENSOR OCC BLOWER MODE =.

Table 12. Blower Operation Description

ECTO 6.17Occupancy Blower Duty Description
OnBlower runs continuously
CyclesBlower cycles on/off with demand.
Cycles with StirBlower cycles on/off with demand during off-cycle blower is on 30 minutes of 120.

Table 13. Blower Operation Description

OCC Blower
Mode
Description
AUTO CYCLESBlower cycles on/off with demand. (Legacy usage.)
ON CONTINUOUS

1

The blower runs when either the occupancy sensor or schedule or both, indicates occupied. (Legacy usage.)
ON CONTINUOUS

2

The blower runs when both the occupancy sensor and schedule indicate occupied.
ON CONTINUOUS

3

The same as option 2, but the blower runs for 30 minutes and is off for 90 minutes when the schedule is occupied but the occupancy sensor is not occupied.

Table 14. Blower Operation Schedule

ManualScheduleSensorEffective OccupancyOCC Blower ModeBlower Operation
0, 2N/AN/AOccupiedAUTO-CYCLESCycles
ON-CONTINOUS 1On
ON-CONTINOUS 2On
ON-CONTINOUS 3On
1N/AN/AUnoccupiedAUTO-CYCLESCycles
ON-CONTINOUS 1Cycles
ON-CONTINOUS 2Cycles
ON-CONTINOUS 3Cycles
3-25500, 2-255OccupiedAUTO-CYCLESCycles
ON-CONTINOUS 1On
ON-CONTINOUS 2On
ON-CONTINOUS 3On
3-25501OccupiedAUTO-CYCLESCycles
ON-CONTINOUS 1On
ON-CONTINOUS 2Cycles
ON-CONTINOUS 3with
stir
3-2551-255N/AUnoccupiedAUTO-CYCLESCycles
ON-CONTINOUS 1Cycles
ON-CONTINOUS 2Cycles
ON-CONTINOUS 3Cycles

CORE UNIT CONTROLLER (M4) BLOWER OPERATION WITH EFFECTIVE OCCUPANCY

This section describes how LonTalk occupancy signals are combined to produce effective occupancy.

The blower runs to service heat and cool demands, regardless of the space occupancy. However, when there is no heating or cooling demand there are options for how the blower should operate in conjunction with occupancy signals to keep the space ventilated, or the air stirred.

  1. California Energy Commission Title 24:
  2. The legacy option settings for OCC Blower Mode are AUTO CYCLES or ON-CONTINUOUS 1. These settings govern whether the blower runs continuously when the space is considered occupied or cycles on/off with the heating and cooling demand.
  3. To comply with the California Energy Commission Title 24 standard there are two additional values for OCC Blower Mode which are ON-CONTINUOUS 2 and ON-CONTINUOUS 3. See table 13 for their
  4. These two new options are available when using LonTalk and supplies a room occupancy signal (in addition to the scheduled occupancy).
  5. Enabling Network Type To enable the network module, go to SETUP > INSTALL and run the setup wizard. When Configuration ID 1 appears on the screen, configure position 5 to L = LonTalk.
  6. Menu Setup Procedure Method for OCC Blower Mode These blower control options are handled by the OCC Blower Mode. These settings can be changed using the following menu path:

Go to RTU MENU > SETUP > NETWORK INTEGRATION > NETWORK= LONTALK > (additional prompts concerning network configuration and sensor

types will be asked) CONTROL MODE = ROOM
SENSOR > ROOM SENSOR OCC BLOWER MODE =.

Table 15. Blower Operation Description

ECTO 6.17Occupancy Blower Duty Description
OnBlower runs continuously
CyclesBlower cycles on/off with demand.
Cycles with StirBlower cycles on/off with demand; during off-cycle blower is on 30 minutes of 120.

Table 16. Blower Operation Description

OCC Blower ModeDescription
AUTO CYCLESBlower cycles on/off with demand. (Legacy usage.)
ON CONTINUOUS

1

The blower runs when either the occupancy sensor or schedule or both, indicates occupied. (Legacy usage.)
ON CONTINUOUS

2

The blower runs when both the occupancy sensor and schedule indicate occupied.
ON CONTINUOUS

3

The same as option 2, but the blower runs for 30 minutes and is off for 90 minutes when the schedule is occupied but the occupancy sensor is not occupied.

Table 17. Blower Operation Schedule

ManualScheduleSensorEffective OccupancyOCC Blower ModeBlower Operation
0. 2N/AN/AOccupiedAUTO-CYCLESCycles
ON-CONTINOUS 1On
ON-CONTINOUS 2On
ON-CONTINOUS 3On
1N/AN/AUnoccupiedAUTO-CYCLESCycles
ON-CONTINOUS 1Cycles
ON-CONTINOUS 2Cycles
ON-CONTINOUS 3Cycles
3-25500, 2-255OccupiedAUTO-CYCLESCycles
ON-CONTINOUS 1On
ON-CONTINOUS 2On
ON-CONTINOUS 3On
3-25501OccupiedAUTO-CYCLESCycles
ON-CONTINOUS 1On
ON-CONTINOUS 2Cycles
ONCONTINOUS 3Cycles with stir
3-2551-255N/AUnoccupiedAUTO-CYCLESCycles
ON-CONTINOUS 1Cycles
ON-CONTINOUS 2Cycles
ON-CONTINOUS 3Cycles

©2021 Lennox Industries Inc. Dallas, Texas, USA

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals