S G Torrice Tem4a0b31m31sb Convertible Air Handler Instruction Manual

TEM4A0B31M31SB Convertible Air Handler

Product Information

  • Product Name: Air Handler Model A TEM4A0B31M31SB
  • Manufacturer: Not specified
  • Model Number: TEM4A0B31-SUB-1D-EN
  • Dimensions: Crated (In.) HxWxD 48-1/4 x 22-1/2 x 25-1/2,
    Uncrated 46-3/4 x 18-1/2 x 21-1/8
  • Weight: Shipping (Lbs.) / Net (Lbs.) 145/138
  • Rated Voltage/Phase/Hertz: 208-230/1/60
  • Refrigerant: R-410A
  • Heater Model Numbers: BAYHTR1504BRK, BAYHTR1504LUG,
    BAYHTR1505BRK, BAYHTR1505LUG, BAYHTR1508BRK, BAYHTR1508LUG,
    BAYHTR1510BRK, BAYHTR1510LUG, BAYHTR1517BRK, BAYHTR3517LUG,
    BAYHTR3510LUG, BAYHTR1523, BAYHTR1525

Product Usage Instructions

To install and use the Air Handler Model A TEM4A0B31M31SB:

  1. Ensure that the unit is approved for installation clearances to
    combustible material as stated on the unit rating nameplate.
  2. Refer to the Split System Outdoor Unit Product Data Guides for
    performance data and approved combinations of Air Handlers and
    Heaters.
  3. Install the air handler according to the outline drawing
    provided in the user manual.
  4. Connect the refrigerant line using a 3/8-inch coupling or
    connection size for the liquid line and a 3/4-inch coupling or
    connection size for the gas line.
  5. Connect the ducts to the indoor fan, which is a centrifugal
    type with a diameter-width of 11 x 8 inches and one direct drive –
    five speeds. Refer to the fan performance table for more
    information.
  6. Install the heater racks and connect them to the appropriate
    heater model number as listed in the user manual.
  7. Turn on the air handler and adjust the airflow speed according
    to your needs using the minimum heat speed tap. Refer to the heater
    pressure drop table for more information.

Submittal
2­1/2 Ton Convertible Air Handler TEM4A0B31M31SB

September 2022

TEM4A0B31-SUB-1D-EN

Outline Drawing
NOTE: THIS UNIT IS APPROVED FOR INSTALLATION CLEARANCES TO COMBUSTIBLE MATERIAL AS STATED ON THE UNIT RATING NAMEPLATE

Air Handler Model

A

TEM4A0B31M31SB

46.77

All dimensions are in inches

B 18.50

PRODUCT DIMENSIONS

C

D

E

16.50

16.75

4.68

F 7.33

H 20.09

Flow Control
TXV

Gas Line Braze
3/4

2

TEM4A0B31-SUB-1D-EN

Product Specifications

MODEL RATED VOLTS/PH/HZ RATINGS(a) INDOOR COIL — Type Rows — F.P.I. Face Area (sq. ft.) Tube Size (in.) Refrigerant Control Drain Conn. Size (in.)(b) DUCT CONNECTIONS INDOOR FAN — Type Diameter-Width (In.) No. Used Drive – No. Speeds CFM vs. in. w.g. No. Motors — H.P. Motor Speed R.P.M. Volts/Ph/Hz F.L. Amps FILTER Filter Furnished? (c) REFRIGERANT Ref. Line Connections Coupling or Conn. Size — in. Gas

TEM4A0B31M31SB 208-230/1/60
See O.D. Specifications Plate Fin 4 – 14 3.44 3/8 TXV 3/4 NPT
See Outline Drawing Centrifugal 11 X 8 1 Direct – 5
See Fan Performance Table 1 – 1/3 1050
208-230/1/60 2.8
No R-410A Brazed
3/4

Coupling or Conn. Size — in. Liq.

3/8

DIMENSIONS Crated (In.)

HxWxD 48-1/4 x 22-1/2 x 25-1/2

Uncrated

46-3/4 x 18-1/2 x 21-1/8

WEIGHT

Shipping (Lbs.) / Net (Lbs.)

145/138

(a) These Air Handlers are A.H.R.I certified with various Split System Air Conditioners and Heat Pumps (AHRI STANDARD 210/240). Refer to the Split System Outdoor Unit Product Data Guides for performance data.
(b) 3/4″ Male Plastic Pipe (Ref: ASTM 1785­76) (c) Remote filter required.

Minimum Airflow CFM

TEM4A0B31M31SB

Heater

Minimum Heat Speed Tap

With Heat Pump

Without Heat Pump

BAYHTR1504BRK,

BAYHTR1504LUG, BAYHTR1505BRK,

Low

Low

BAYHTR1505LUG

BAYHTR1508BRK, BAYHTR1508LUG, BAYHTR1510BRK, BAYHTR1510LUG

Med-High

Med-Low

BAYHTR1517BRK, BAYHTR3517LUG, BAYHTR3510LUG

High

Med

TEM4A0B31-SUB-1D-EN

3

Heater Pressure Drop Table TEM Air Handler Models

Airflow CFM
1800 1700 1600 1500 1400 1300 1200 1100 1000 900 800 700 600

1
0.02 0.02 0.02 0.02 0.02 0.02 0.01 0.01 0.01 0.01 0.01 0.01 0.01

Number of Racks

2

3

Air Pressure Drop — Inches W.G.

0.04 0.04 0.04 0.04 0.04

0.06 0.06 0.06 0.06 0.06

0.04 0.04 0.03 0.03 0.03 0.03 0.02 0.02

0.05 0.05 0.05 0.04 0.04

4
0.14 0.14 0.13 0.12 0.12 0.11 0.10 0.09 0.09 0.08

Heater Racks

Heater Model

No. of Racks

BAYHTR1504

1

BAYHTR1505

1

BAYHTR1508

2

BAYHTR1510

2

BAYHTR3510

3

BAYHTR1517

3

BAYHTR3517

3

BAYHTR1523

4

BAYHTR1525

4

4

TEM4A0B31-SUB-1D-EN

Performance and Electrical Data

1. See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters. 2. Heater model numbers may have additional suffix digits.

Table 1. Air Flow Performance

TEM4A0B31M31SB (a)

EXTERNAL STATIC (in w.g)
0.1 0.2 0.3 0.4 0.5 0.6 0.7

High 1192 1148 1103 1057 1009 961 911

Med-High 1127 1079 1031 980 929 875 820

AIRFLOW Speed Taps: 208 ­ 230 VOLTS
Med 1070 1021 971 919 865 810 753

Med-Low 995 943 890 834 775 714 651

1. Values are with wet coil, no filter, and no heaters 2. CFM Correction for dry coil = Add 3% 3. = Factory Setting 4. Low = Tap 1, Med-Low = Tap 2, Med = Tap 3, Med-High= Tap 4, High = Tap 5
(a) For the TEM4A0B31M31SB in downflow applications, airflow must not exceed 1200 cfm due to condensate blow off.

Low 940 885 828 767 702 635 564

Table 2. Electrical Data

TEM4A0B31M31SB

Heater Model No.
No Heater BAYHTR1504BRK BAYHTR1504LUG BAYHTR1505BRK BAYHTR1505LUG BAYHTR1508BRK BAYHTR1508LUG BAYHTR1510BRK BAYHTR1510LUG BAYHTR1517BRKCircuit 1 (a) BAYHTR1517BRKCircuit 2 BAYHTR3510LUG

No. of Circuits/ Phases
1/1 1/1 1/1 1/1
2/1
1/3

Capacity kW BTUH

240 Volt

Heater Amps per
Circuit

Minimum Circuit
Ampacity

2.8 *

4

3.8 13100

16.0

24

Maximum Overload Protection
15
25

4.8 16400

20.0

29

30

7.7 26200

32.0

44

45

9.6 32800

40.0

54

60

9.6 32800

40.0

54

60

4.8 16400

20.0

25

25

9.6 32800

23.1

32

35

BAYHTR3517LUG

1/3

14.4 49100

34.6

46

50

BAYHTR1517BRK

with single circuit power source kit

1/1

14.4 49100

60.0

83

90

BAYSPEKT201A

* = Motor Amps

(a) MCA and MOP for circuit 1 contains the motor amps.

Capacity kW BTUH

208 Volt

Heater Minimum Amps per Circuit
Circuit Ampacity

2.8 *

4

2.9 9800

13.8

21

3.6 12300 17.3

25

5.8 19700 27.7

38

7.2 24600 34.6

47

7.2 24600 34.6

47

3.6 12300 17.3

22

7.2 24600 20.0

28

10.8 36900 30.0

41

10.8 36900 51.9

73

Maximum Overload Protection
15 25
25
40
50
50
25 30 45
80

TEM4A0B31-SUB-1D-EN

5

Features and Benefits
· Painted metal cabinet with captured foil face insulation
· 2% or less air leakage · R-4.2 Insulating Value · Multi-Position UP/Down Flow, Horizontal Left /Right · ALL Aluminum Coil · Electric Heaters with polarized plug connections
(sold as accessory) · R-410A Thermal Expansion Valve · ECM Motor (3.5 ­ 5 Ton Models ) · Low Voltage Pigtail Connections

· Draw Through Design · Horizontal Drain pan · Fused 24V Power · 3 year warranty · 10-year warranty registered · Optional extended warranty available
Important: Condensate management kit is required for all 5 ton air handler models installed in downflow applications.

6

TEM4A0B31-SUB-1D-EN

About Trane and American Standard Heating and Air Conditioning Trane and American Standard create comfortable, energy efficient indoor environments for residential applications. For more information, please visit www.trane.com or www.americanstandardair.com.

The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

TEM4A0B31-SUB-1D-EN 16 Sep 2022 Supersedes TEM4A0B31-SUB-1C-EN (March 2022)

©2022