Vimar 01523.1 250v 16a 4-output Actuator Knx Installation Guide

Vimar 01523.1 250v 16a 4-output Actuator Knx Installation Guide

VIMAR logoInstaller manualVIMAR 01523 1 250V 16A 4 Output Actuator KNX01523.1
Multifunction actuator, 4 relay outputs, NO 16 A 250 V~.
BUILDING AUTOMATION
WELL-CONTACT PLUS

For details of the Well-contact Plus system, consult the installer manual, which can be downloaded from the
Download section  Software   Well-contact Plus on the website www.vimar.com.

output device

General characteristics and functions 
Actuator with 4 NO relay outputs 16 A 250 V~, programmable with control function for lights, roller shutters with slat orientation, push buttons for local control, KNX standard, installation on DIN rails (60715 TH35), occupies 4 modules size 17.5 mm.

General characteristics

The device is designed to manage 4 generic outputs for typical applications in the service industry (access to offices, hospital or hotel rooms, swimming pools, saunas, sports facilities, restricted access areas, etc.).
It is also designed to work as a virtual pocket function for the presence control in the room.
Outputs 1-2 and 3-4 can be used to control roller shutters or Venetian blinds.

Functions

The functions available are the same for all channels.
For “Single outputs”, the following functions are available for the outputs:

  • Disabled channel without function;
  •  Switching module the output is switched according to the other parameters;
  •  Stair light depending on the other parameters, the output is switched for a period of time (one-position stable relay).
    Two outputs can be grouped together (OUT1/OUT2 and OUT3/ OUT4 to obtain the following functions:
  •  Roller shutter
  • Venetian blinds

Manual operation
Press the push button to enter manual mode to check the output connections. Press push buttons OUT1, OUT2, OUT3,  OUT4 to control the related outputs. During manual operation, outputs OUT1/OUT2 and OUT3/OUT4 are interlocked to prevent damaging any motors connected, and messages received from the bus are not managed.

Behavior after powering on/off the Bus
Bus off: depending on the parameter settings.
Bus on: depending on the parameter settings.
Behavior after reset
As for Bus power-on.

The KNX Secure protocol
The device is used to activate the “KNX SECURE” data encryption protocol, entering the QR code or the digits in ETS and also creating a password associated to the project.
Note: If the QR code printed on the label is too small, take a photo of it with a smartphone and enlarge it.
The password is mandatory in the following cases:
– when enabling the Secure part of the devices in the project – when entering the certificate of a Secure device in the project
If the Secure part of a device is disabled, it acts exactly like a device that does not support this protocol.
If you do not wish to enable the Secure part when importing the device into the project close the Secure request window as described in the following procedure.

  1. Add the Secure device to the ETS project.VIMAR 01523 1 250V 16A 4 Output Actuator KNX - fig
  2. Ignore the set password request.VIMAR 01523 1 250V 16A 4 Output Actuator KNX - fig 1
  3. The device is displayed with the Secure part disabled.VIMAR 01523 1 250V 16A 4 Output Actuator KNX - fig 2
  4. No password is associated to the project.VIMAR 01523 1 250V 16A 4 Output Actuator KNX - fig 3
  5. No certificate is associated to the project.VIMAR 01523 1 250V 16A 4 Output Actuator KNX - fig 4

List of existing communication objects
The following objects are available for each channel, depending on the function and settings; they are identical for every channel or for pairs of channels used for roller shutters. If a channel is not on there are no communication objects.

VIMAR 01523 1 250V 16A 4 Output Actuator KNX - fig 5

Communication objects per channel

NumberName in ETSFunction in ETSDescriptionLengthFlag 1
CRWTU
OUTPUTS                                                                 With outputs OUT1, OUT2, OUT3 and OUT4 configured as single outputs
1Out 1On/ off(If the output is enabled as “Switching module”) to switch the output On/ Off1 bitXXX
2Out 1Stair light(If the output is enabled as “Stair Light”) to switch the output on, with timed switch-off.1 bitXXX
3Out 1Force(If the output “Block” parameter is on, with “Force” function) to force the output On/Off from the Bus2 bitXX
4Out 1Block((If the output “Block” parameter is on, with “Block” function) to block the output control from the Bus1 bitXXX
5Out 1Scenario(If the output “Scenario” parameter is on), to activate and, if required, store (if the parameter is active) a scenario associated to the output 

1 byte

 

X

 

X

 

X

6Out 1State(If the output is enabled as “Switching module”) to know the output state1 bitXXX
7… 13Out 1Logic 1… 7(If the logic function for the output is on) A number of objects from 1 to 7 can be selected for OR, AND, XOR logics with the “On/off” object to determine the output state. 

1 bit

 

X

 

X

 

X

14… 26Out 2 (see similar objects for Out 1)As per Out 1
27… 39Out 3 (see similar objects for Out 1)As per Out 1
40… 52Out 4 (see similar objects for Out1)As per Out 1
OUTPUTS                                                                 With outputs OUT1/OUT2 and OUT3/OUT4 configured as roller shutter or Venetian blinds
1Out 1/2Roller shutter Up/Down(If the output is enabled as “Roller shutter” or “Venetian blinds”) To move the Venetian blinds/roller shutter.1 bitXXX
2Out 1/2Slats up/down/stop(If the output is enabled as “Venetian blinds”) To rotate/stop the slats.1 bitXXX
3Out 1/2Stop(If the output is on as “Roller shutter”) To stop the roller shutter.1 bitXXX
4Out 1/2Scenario(If the output is on as “Venetian blinds” or “Roller shutter” and “Scenario” is on) To call up the scenarios from the Bus.1 byteXXX
5Out 1/2Actual direction(If the output is on as “Venetian blinds” or “Roller shutter” and

“select objects for absolute position” is on) Object signalling the roller shut- ter direction of movement. Reading the state, the object responds with the last movement made or the current one if the roller shutter is moving (1 = up, 0 = down).

 

1 bit

 

 

X

 

 

X

 

 

X

6Out 1/2Position (Absolute)(If the output is on as “Venetian blinds” or “Roller shutter” and

“select objects for absolute position” is on) To set the roller shutter position from a supervisor (0% = all up, 100% = all down.

1 byte 

X

 

X

 

7

 

Out 1/2

 

Absolute slat position

(If the output is on as “Venetian blinds” and “select objects for absolute position” is on) To set the slat position from a supervisor (0% = open, 100% = closed).1 byte 

X

 

X

 

8

 

Out 1/2

 

Position (Actual)

(If the output is on as “Venetian blinds” or “Roller shutter” and

“select objects for absolute position” is on) To know the actual position of the roller shutter (0% = all up, 100% = all down.

1 byte 

X

 

X

 

X

9Out 1/2Current slat position(If the output is on as “Venetian blinds” and “select objects for absolute position” is on). To know the actual slat position.1 byteXXX
 

10

 

Out 1/2

 

Valid actual position

(If the output is on as “Venetian blinds” or “Roller shutter” and “select ob- jects for absolute position” is on) To know the actual roller shutter position.1 bit 

X

 

X

 

X

 

11

 

Out 1/2

 

Door to reference

(If the output is on as “Venetian blinds” or “Roller shutter” and “select objects for absolute position” is on) Object used to move

the roller shutter Up/Down: sends a bit= 1 to the Bus to raise or a bit=0 to lower (the device will ignore all other commands sent to the Bus until the output switches off within the set time)

 

1 bit

 

 

X

 

 

X

 

 

X

12Out 1/2Door at limit(If the output is enabled as “Venetian blinds” or “Roller shutter” and the “Driving Area – Limitation” is on) Object used to move the roller shutter Up/ Down: receives a bit =1 from the Bus to raise or a bit = 0 to lower.1 bit 

X

 

X

 

X

13Out 1/2Upper state – Position(If the output is on as “Venetian blinds” or “Roller shutter” and “select ob- jects for absolute position” is on) The device sends a bit to 1

when the upper limit stop is reached.

1 bit 

X

 

X

 

X

Continued

NumberName in ETSFunction in ETSDescriptionLengthFlag 1
CRWTU
 

14

 

Out 1/2

Lower state – Position(If the output is on as “Venetian blinds” or “Roller shutter” and “select ob-jects for absolute position” is on) The device sends a bit to 1 when the lower limit stop is reached. 

1 bit

 

X

 

X

 

X

 

15

 

Out 1/2

 

Automatic lock

(If the output is enabled as “Venetian blinds” or “Roller shutter” and “Automatic roller shutter operation” is on) To enable/disable the automatic operation (rain, wind, etc.). 

1 bit

 

X

 

X

 

X

16Out 1/2Lock mode manual(If the output is enabled as “Venetian blinds” or “Roller shutter”) To enable/ disable the manual operation (controlled from a button via Bus).1 bitXXX
 

17

 

Out 1/2

 

Move

(If the output is on as “Venetian blinds” or “Roller shutter” and

“select objects for absolute position” is on) An object that sends a bit = 1 when the movement starts, or a bit = 0 when the movement ends. It is also possible to read the current state.

 

1 bit

XXX
 

89

 

Out 1/2

 

Warning (Wind)

(If the output is enabled as “Venetian blinds” or “Roller shutter” and the “Warning Function” is on with “Warning Wind”) to move the roller shutter/ Venetian blinds to the position for this type of warning set in the specific parameters.1 bitXXX
 

90

 

Out 1/2

 

Warning (Rain)

(If the output is enabled as “Venetian blinds” or “Roller shutter” and the “Warning Function” is on with “Warning Rain”) to move the roller shutter/ Venetian blinds to the position for this type of warning set in the specific parameters.1 bitXXX
 

91

 

Out 1/2

 

Warning (Frost)

(If the output is enabled as “Venetian blinds” or “Roller shutter” and the “Warning Function” is on with “Warning Frost”) to move the roller shutter/ Venetian blinds to the position for this type of warning set in the specific parameters.1 bitXXX
 

92

 

Out 1/2

 

Block

(If the output is enabled as “Venetian blinds” or “Roller shutter” and the “Warning Function” is on with “Block”) to block the roller shutter at the limit stop with a bit to “1” (upper or lower, according to the parameters).1 bitXXX
 

97

 

Automatic A

Automatic operation 1 – Position(If the “Automatic operation” parameter of “Block-A” is on) To automatically control this roller shutter output object which can recall specific positions similar to scenarios.1 bitXX
 

98

 

Automatic A

Automatic operation 2 – Position(If the “Automatic operation” parameter of “Block-A” is on) To automatically control this roller shutter output object which can recall specific positions similar to scenarios.1 bitXX
 

99

 

Automatic A

Automatic operation 3 – Position(If the “Automatic operation” parameter of “Block-A” is on) To automatically control this roller shutter output object which can recall specific positions similar to scenarios.1 bit 

X

 

X

 

100

 

Automatic A

Automatic operation 4 – Position(If the “Automatic operation” parameter of “Block-A” is on) To automatically control this roller shutter output object which can recall specific positions similar to scenarios.1 bitXX
 

101

 

Automatic B

Automatic operation 1 – Position(If the “Automatic operation” parameter of “Block-B” is on) To automatically control this roller shutter output object which can recall specific positions similar to scenarios.1 bitXX
 

102

 

Automatic B

Automatic operation 2 – Position(If the “Automatic operation” parameter of “Block-B” is on) To automatically control this roller shutter output object which can recall specific positions similar to scenarios.1 bitX 

X

 

103

 

Automatic B

Automatic operation 3 – Position(If the “Automatic operation” parameter of “Block-B” is on) To automatically control this roller shutter output object which can recall specific positions similar to scenarios.1 bit 

X

 

X

 

104

 

Automatic B

Automatic operation 4 – Position(If the “Automatic operation” parameter of “Block-B” is on) To automatically control this roller shutter output object which can recall specific positions similar to scenarios.1 bitXX
VIRTUAL POCKET
105Virtual pocketFirst motion sensor(If the “Virtual pocket” function is on) To receive an indication from a motion sensor.1 bitXXX
 

106

 

Virtual pocket

Second motion sensor(If the “Virtual pocket” function is on and the “Second motion sensor” is enabled) To receive an indication from a second motion sensor. 

1 bit

XXX
107Virtual pocketActivity signaling(If the “Virtual pocket” function is on and “Activity signaling” is enabled) To receive an indication from a second motion sensor.1 bitXXX
108Virtual pocketDoor input(If the “Virtual pocket” function is on) To receive an indication on the door opening and closing.1 bitXXX
109Virtual pocketWait time(If the “Virtual pocket” function is on) To receive a value via bus for the Wait time.1 byteXXX
 

110

 

Virtual pocket

 

Presence in room

(If the “Virtual pocket” function is on) To transit a bit=1 to signal that the room is occupied and a bit=0 to signal that the room is free.1 bitXXX

Communication objects per channel: once for all channels

NumberFunctionUseDPTDirection
111 

Centralized function

Simultaneous on/off of more than one output configured as “Switching module” or “Stair light”. For “Stair light” the “Stair light time” is not considered and so the output must be switched off from the “Centralised function”.DPT 1.001In, Write

Standard communication object settings
Communication objects: default output/input settings

NumberName in ETSFunction in ETSLengthPriorityFlag 1
CRWTU
1Out 1On/off1 bitLowXXX
2Out 1Stair light1 bitLowXXX
3Out 1Force2 bitLowXXX
4Out 1Block1 bitLowXXX
5Out 1Scenario1 byteLowXXX
6Out 1State1 bitLowXXX
7Out 1Logic 11 bitLowXXX
8Out 1Logic 21 bitLowXXX
9Out 1Logic 31 bitLowXXX
10Out 1Logic 41 bitLowXXX
11Out 1Logic 51 bitLowXXX
12Out 1Logic 61 bitLowXXX
13Out 1Logic 71 bitLowXXX
14… 52Out 2, Out 3, Out 4As per Out 1
1Out 1/2Roller shutter Up/Down1 bitLowXXX
2Out 1/2Slats up/down/stop1 bitLowXXX
3Out 1/2Stop1 bitLowXXX
4Out 1/2Scenario1 byteLowXXX
5Out 1/2Actual direction1 bitLowXXX
6Out 1/2Position (Absolute)1 byteLowXX
7Out 1/2Absolute slat position1 byteLowXX
8Out 1/2Position (Actual)1 byteLowXXX
9Out 1/2Current slat position1 byteLowXXX
10Out 1/2Valid actual position1 bitLowXXX
11Out 1/2Door to reference1 bitLowXXX
12Out 1/2Door at limit1 bitLowXXX
13Out 1/2Upper state – Position1 bitLowXXX
14Out 1/2Upper – Lower state1 bitLowXXX
15Out 1/2Automatic lock1 bitLowXXX
16Out 1/2Manual lock mode1 bitLowXXX
17Out 1/2Move1 bitLowXXX
89Out 1/2Warning (Wind)1 bitLowXXX
90Out 1/2Warning (Rain)1 bitLowXXX
91Out 1/2Warning (Frost)1 bitLowXXX
92Out 1/2Block1 bitLowXXX
27… 43

93… 96

Out 3/4As per Out 1/2
97Automatic AAutomatic operation 1 – Position1 bitLowXXX
98Automatic AAutomatic operation 2 – Position1 bitLowXXX
99Automatic AAutomatic operation 3 – Position1 bitLowXXX
100Automatic AAutomatic operation 4 – Position1 bitLowXXX
101Automatic BAutomatic operation 1 – Position1 bitLowXXX
102Automatic BAutomatic operation 2 – Position1 bitLowXXX

Continued

NumberName in ETSFunction in ETSLengthPriorityFlag 1
CRWTU
103Automatic BAutomatic operation 3 – Position1 bitLowXXX
104Automatic BAutomatic operation 4 – Position1 bitLowXXX
111Centralized functionOn/off1 bitLowXXX
105Virtual pocketFirst motion sensor1 bitLowXXX
106Virtual pocketSecond motion sensor1 bitLowXXX
107Virtual pocketActivity signaling1 bitLowXXX
108Virtual pocketDoor input1 bitLowXXX
109Virtual pocketWait time2 byteLowXXX
110Virtual pocketPresence in room1 bitLowXXX

Reference ETS parameters
General
The following parameters are exclusive for all channels.
Output configuration
Define the output details.

ETS textValues availableComment
[Default value]
 

Outputs:

– Out 1/2

– Out 3/4

0 = Off 

For “Single output” you can choose “Switching module” or “Stair light” corresponding- ing to a two-position stable or one-position stable relay.

1 = Single output
2 = Venetian blinds
3 = Roller shutter
[0]
 

Interlock enabled

0=off 

Only one output (e.g. for the fan coil) can be on at a time

1=on
[0]
 

 

 

 

 

 

Enabled for outputs

3 = A B 

 

 

 

If “interlock enabled”: out- puts for which it will be on. If “A B” for example, it will not be possible to activate Out 1 and 2 at the same time

5 = A C
9 = A D
6 = B C
10 = B D
12 = C D
7 = A B C
11 = A B D
13 = A C D
14 = B C D
15 = A B C D
[7]

VIMAR 01523 1 250V 16A 4 Output Actuator KNX - fig 6

Channel configuration. (Example: Output 1 – Switching module, Output 2 – Stair light, Output 3/4 – Roller shutter)

Outputs
Output: switching module 1… 4
The following parameters are available for each channel and are identical for all of them.
Parameter configuration
Management of outputs 1/2/3/4 set as switching module.

ETS textValues availableComment
[Default value]
 

Type

0 = normally closedTo define if the relay output is normally open or closed
1 = normally open
[1]
Activation delay0… 30000 sActivation delay in seconds
[0]
Deactivation delay0… 30000 sDeactivation delay in seconds
[0]
 

Centralised control function

0 = offCentralized function (to control more than one output from the Bus at the same time)
1 = on
[0]
 

Block/Force

0 = no actionTo block or force output from the Bus
1 = Block
2 = Force
 

State at block state start

0 = OffIf block on
1 = On
2 = no change
[2]
 

State at block state end

0 = Off 

 

If block on

1 = On
2 = no change
[2]
 

Behavior at Bus power on

0 = Off 

To define the relay output state at bus power on

1 = On
2 = no change
[2]
Continued
ETS textValues availableComment
[Default value]
 

Behavior at Bus power off

0 = OffTo define the relay output state at bus power off
1 = On
2 = no change
[2]
 

Logic function

0 = offTo enable logics on the outputs (AND, OR, XOR) for up to 7 objects
1 = on
[0]
 

Scenario

0 = offScenario activation If on, an additional page is displayed (Output, second- any element scenario)
1 = on
[0]

VIMAR 01523 1 250V 16A 4 Output Actuator KNX - fig 7

Logic function
The on/off objects can be used with logic objects (1 to 7) to create AND/OR/XOR logic functions to enable or disable the related output (OUT1, OUT2, OUT3, OUT4).

Parameter configuration

ETS textValues availableComment
[Default value]
 

Logic inputs on

With 1 object 

To enable the objects required for the logic

….
With 7 objects
[With 1 object]
 

Logic operation

0 = OR 

To select the required logic operation

1 = AND
2 = XOR
[OR]
 

Logic type – input

Not invertedTo define if the selected in- put must be inverted or not
Inverted
[Not inverted]

 

VIMAR 01523 1 250V 16A 4 Output Actuator KNX - fig 8

Output, secondary element scenario
For each output, 8 scenario storage possibilities are available.
For each scenario, the scenario index and the On or Off value for the output can be selected.
Scenario parameters (8 scenarios per output)

ETS textValues availableComment
[Default value]
 

Store scenarios

0 = OffThe “Store scenarios” func- tion is used to store the state linked to a scenario with a message from the Bus (scene learn).
1 = On
[0]
 

Scenario 1

OffUsed to select the scenario index.
1… 64
[Off]
 

Scenario 1

0=OffTo define the relay output state when scenario called up.
1=On
[0]
 

Scenario 2

Off 

Used to select the scenario index.

1… 64
[Off]
 

Scenario 2

0=OffTo define the relay output state when the scenario is called up.
1=On
[0]
 

Scenario 3

OffUsed to select the scenario index.
1… 64
[Off]
 

Scenario 3

0=OffTo define the relay output state when the scenario is called up.
1=On
[0]
 

Scenario 4

OffUsed to select the scenario index.
1… 64
[Off]
 

Scenario 4

0=OffTo define the relay output state when the scenario is called up.
1=On
[0]
 

Scenario 5

OffUsed to select the scenario index.
1… 64
[Off]
 

Scenario 5

0=OffTo define the relay output state when the scenario is called up.
1=On
[0]
 

Scenario 6

OffUsed to select the scenario index.
1… 64
[Off]
 

Scenario 6

0=OffTo define the relay output state when the scenario is called up.
1=On
[0]
 

Scenario 7

OffUsed to select the scenario index.
1… 64
[Off]
 

Scenario 7

0=OffTo define the relay output state when the scenario is called up.
1=On
[0]
 

Scenario 8

OffUsed to select the scenario index.
1… 64
[Off]
 

Scenario 8

0=OffTo define the relay output state when the scenario called up.
1=On
[0]

VIMAR 01523 1 250V 16A 4 Output Actuator KNX - fig 9

Output, timed stair light
The following parameters are available for each channel and are identical for all of them. If a channel is configured as stairs the The following parameters are visible:
Stair light parameters (one-position stable output management)

ETS textValues availableComment
[Default value]
Type0=normally closedTo define if the relay output is normally open or closed
1=normally open
[0]
Stair Light time [s]0… 65535Output activation time
[120]
Warning off0=offTo be able to switch the warning function on
1=on
[0]
Duration

of warning [s]

0… 65535If “Off warning” is on: having set a “warning time” and a “prewarning time”, when the relay is switched off after the “stair light time” set, this remains Off for a time equal to the “warning time” and then comes on again for a time equal to the “prewarn- ing time”
[120]
Duration

of pre-warning [s]

0… 65535Warning time (if “Off warning” is on). Three times will be added. Having set a “warning time” and a “prewarning time”, when the relay is switched off after the “stair light time” set, this remains Off for a time equal to the “warning time” and then comes on again for a time equal to the “prewarn- ing time”
[120]
Manual off0=offIf manual off is active, on receiving an OFF message on the “Stair light” object, if on in one-position stable the output switches off
1=on
[0]
Centralized switching module function0=offTo control more than one output from the Bus at the same time
1=on
[0]
State at block state start0=OffIf block on
1=On
2=no change
[2]
State at the end of the block state0=OffIf block on
1=On
2=no change
[2]
Behavior when powering up the Bus0=OffTo define the relay output state at bus power on
1=On
2=no change
[2]
Behavior at Bus power off0=OffTo define the relay output state at bus power off
1=On
2=no change
[2]

VIMAR 01523 1 250V 16A 4 Output Actuator KNX - fig 10

Automatic parameter activation 
These settings activate objects. Each block has 4 objects, used to automatic controls on 4 objects calling up positions (similar to scenarios).

Parameters in automatic operation
ETS textValues availableComment
[Default value]
Block A0=offFor block A objects 1-4 are activated
1=On
[0]
Block B0=offFor block B objects 1-4 are activated
1=On
[0]

VIMAR 01523 1 250V 16A 4 Output Actuator KNX - Fig 20

Parameters

Venetian blinds parameters: characteristics relating to the control of Venetian blinds with slats

ETS textValues availableComment
[Default value]
Execution time (sec)1-10000Movement time if not stopped
[45]
 

Step time for slats (ms)

100-1000Sets the short press time for the button to interpret as slat control
[200]
Slat control time (ms)10-10000Sets the slat control time for each press
[1200]
Pause at change of direction (ms)1-1000Sets the delay time between the command and the change of direction
[500]
 

Motor start delay (ms)

0-255Sets the delay time between the command and the start of movement (useful for motor starting)
[0]
Motor power-off delay (ms)0-255Sets the delay time between the command and the end of the movement (limit stop)
[0]
 

Slat position at end of driving

0%-100%Sets the slat position at the end from the reference travel 0-100% having set the limit stop (100% closed)
[50]
 

Slat position at end of driving by absolute value.

0%-100%Sets the slat position at the end of the movement due to the “Position (absolute)” object
[50]
Object selection for absolute position0=offFor feedback on the position on a supervisor, if on, 0%=all up and 100%=all down
1=on
[0]
Reaction after driving to

reference

0=no reactionOnly if Position absolute
1=Door to the previous position
[0]
Driving area: Limitation0= offOnly if the limitation on: sets the upper/lower thresholds of the Venetian blind travel to stop it before the limit stop
1=on
[0]
Lower limit0%-100%Only if limitation on (driving area) (100% = closed)
[0%]

VIMAR 01523 1 250V 16A 4 Output Actuator KNX - fig 11Venetian blinds parameters

Continued

ETS textValues availableComment
[Default value]
 

Upper limit

0%-100%Only if limitation on (driving area) (100% = closed)
[100%]
 

Scenario

0= off 

Enables the Venetian blind to be included in scenarios

1=on
[0]
 

Automatic Operation

0= offDefines the possibility of having the Venetian blind possibilities with 4 objects devoted to their automatic control from the Bus (Rain, Wind, Frost, Block)
1=on
[0]
 

 

 

Warning Function

 

0= off

Used to view the section with “Warning-Out” parameters, to enable the ETS obtaining to be switched on/ off (e.g. a weather station) and obtain the automatic movement of the Venetian blinds in the event of rain, wind, frost, block-out
 

1=on

 

[0]

Roller shutter parameters: characteristics relating to the control of roller shutters (without slats)

ETS textValues availableComment
[Default value]
Execution time (sec)1-10000Movement time if not stopped
[45]
Pause at the change of direction (ms)100÷1000Sets the delay time between the command and the change of direction
[500]
Motor start delay0÷255Sets the delay time between the command and the start of movement (useful for motor starting)
[0]
Motor power-off delay0÷255Sets the delay time between the command and the end of movement (limit stop)
[0]
Select objects for absolute position0 = OffSelects the possibility or not to use communication objects to view the actual position of the roller shutter

(0%=all up, 100%=all down) for feedback of the position on a supervisor

1 = Door to previous position
[0]
Reaction after driv- ing to reference0 = No reactionIf “Select objects for absolute position” on
1 = Door to the previous position
[0]
 

Driving area: limi- tation

0 = OffOnly if the limitation on: sets the upper/lower thresholds. of the Venetian blind travel to make it stop before the limit stop
1 = On
[0]
Lower limit0%… 100%If “Driving area” on (100% = closed)
[0%]
Upper limit0%… 100%If “Driving area” on (100% = closed)
[100%]
Scenario0 = OffEnables the roller shutter to be included in scenarios
1 = On
[0]

VIMAR 01523 1 250V 16A 4 Output Actuator KNX - fig 12

Continued

ETS textValues availableComment
[Default value]
Automatic oper- ation0 = OffDefines the possibility of having the required roller shutter position with 4 objects devoted to their automatic control from the Bus (rain, wind, frost, block)
1 = On
[0]
Warning Function 

0 = Off

Used to view the section with “Warning-Out” parameters, to enable the ETS obtaining to be switched on/ off (e.g. a weather station) and obtain the automatic movement of the roller shutters in the event of rain, wind, frost, block-out
 

1 = On

 

[0]

Scenarios

For each channel, 8 scenarios can be stored and called up. For each scenario, it is possible to select the scenario index, the position of the roller shutter and slats (only for Venetian blinds).
Scenario parameters: scenario management

ETS textValues availableComment
[Default value]
Store scenarios0=offThe “Store scenarios” function is used to store the state linked to a scenario with a message from the Bus (scene learn).
1=on
[0]
Scenario 11-64Used to select the scenario index.
Off
[Off]
Scenario 1 Position0%-100%Used to select the roller shutter position when the scenario is called up
[0]
Scenario 1 – Slats position0%-100%Used to select the position of the slats when the scenario is called up (Venetian blinds only)
[0]
Scenario 8

The Store scenarios function is used to store the state linked to a scenario with a message from the Bus (scene learn).

VIMAR 01523 1 250V 16A 4 Output Actuator KNX - fig 13

Warnings Out 1/2 and 3/4
Warnings Parameters: if the “Warning Function” parameter is enabled on the output,  to define the operations to be performed automatically in the event of the objects “Rain,  Wind, Frost, Block” being activated by the Bus (by interaction with weather stations)

ETS textValues availableComment
[Default value]
 

Warning order

0 = Wind, Rain, Frost, BlockTo give a priority to the warnings
1 = Wind, Rain, Block, Frost
2 = Wind, Block, Rain, Frost
3 = Block, Wind, Rain, Frost
[0]
Action after warn- ings/block reset0 = No actionWhat the output does (Vene- tian blinds/roller shutter) when the warning or block ends
4 = Door to previous position
1 = Door to higher level
2 = Door to lower level
[0]
“Wind” warning0 = Off
1 = On
[0]
Cycle time (min, 0 = Off) 

0-120

From the moment the alarm is triggered, a time can be set after which the alarm condition is reset (if no other messages are received)
[30]
Action0 = No actionDefines what happens in the event of a “Wind” alarm
1 = Door to higher level
2 = Door to lower level
[0]
“Rain” warning0 = Off
1 = On
[0]
Cycle time (min, 0 = Off) 

0-120

From the moment the alarm is triggered, a time can be set after which the alarm condition is reset (if no other messages are received)
[30]
Action0 = No actionDefines what happens in the event of a “Rain” alarm
1 = Door to higher level
2 = Door to lower level
[0]
“Frost” warning0 = Off
1 = On
[0]

VIMAR 01523 1 250V 16A 4 Output Actuator KNX - fig 14

Continued

ETS textValues availableComment
[Default value]
Cycle time (min, 0 = Off) 

0-120

From the moment the alarm is triggered, a time can be set after which the alarm condition is reset (if no other messages are received)
[30]
Action0 = No actionDefines what happens in the event of a “Frost” alarm
1 = Door to higher level
2 = Door to lower level
[0]
Block0 = Off
1 = On
[0]
Action0 = No action
1 = Door to higher level
2 = Door to lower level
[0]

Automatic operation
In this point, the object block and required position are assigned, if the “Automatic operation” parameter is enabled on the output.

Automatic parameters

ETS textValues availableComment
[Default value]
Automatic objectsBlock AThe automatic operations are divided into 2 blocks A and B that can be associat- ed to outputs 1/2 and 3/4.
Block B
[Block A]
Automatic opera- tion 1 (-4) – Position0%-100%For each of the 4 automatic operations, it is possible to define the roller shutter position (100% = Closed)
[0%]
(-4) – Blind position0%-100%For each of the 4 automatic operations, it is possible to define the slat position (100% = Closed)
[0%]

Note.
Automatic 1 = position 1 – position 2 – position 3 – position 4.
Automatic 2 = position 1 – position 2 – position 3 – position 4.

VIMAR 01523 1 250V 16A 4 Output Actuator KNX - fig 15

Automatic operation parameters

Virtual pocket
The virtual pocket function can be enabled by selecting “Enabled” in the “Output Configuration” page. This function is used to check if a room is occupied and signal it in the 1 bit object “Presence in the room”. To implement the function, at least a motion sensor and a room access door opening and closing signal must be used. The use of another motion sensor or the configuration of an object signaling activity in the room are optional. The following parameters are available for this function

ETS textValues availableComment
[Default value]
Wait time0÷65535 minTo select the presence in room detection wait time from the bus
[5]
Second motion sensorDisabledTo enable a second motion sensor that can signal the presence in the room
Enabled
[Disabled]
Activity signallingDisabledIf this parameter is enabled, any command received on the “Activity signalling” object signals the presence in the room
Enabled
[Disabled]

VIMAR 01523 1 250V 16A 4 Output Actuator KNX - fig 17

The following graphics illustrate some cases of using the “virtual pocket” function. In all cases, the door opening and closing is signaled (received on the “Door input” object),  as is the movement on a PIR (received on the “First motion sensor” object) and the room occupied is sent (on the “Presence in room” object).
General note: The motion sensor disabling time must be less than the timeout (“Wait time” parameter or “Wait time” object) for leaving the room. In this way, at the end of the timeout, the “Presence in the room” signal is disabled and the room can be placed in the “not occupied” state. VIMAR 01523 1 250V 16A 4 Output Actuator KNX - fig 18

ecViale Vicenza 14

VIMAR logo36063 Marostica VI – Italy
www.vimar.com
01523.1IEN 01 2011

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals