KNX MONA Series Card Holder
Product Information: Mona Card Holder EAE KNX MONA Series
The Mona Card Holder R1 is designed for energy-saving purposes
in hotel guest rooms. It has a monoblock glass design and is
compatible with Mifare 13.56 MHz cards with contactless reading for
RFID card information. The device prevents mechanical wear and card
deformation and has a 60×60 mm easy mounting to standard junction
boxes. The card holder has configurable RGB illuminated buttons for
up to 6 independent programmable buttons for switching, dimming,
shutter/blind, value, scene control, and status notification.
Technical Data:
- Protection Type: IP20
- Safety Class: II
- Power Supply: KNX Voltage
- Current drawn from bus: < 27 mA
- LED (red) and LED (RGB)
- Dimensions: Front side: 90 x 100 mm
- Box Material: Surface – Glass; Flush Mounted Part –
Polycarbonate - Color: Surface – Black or White; Flush Mounted Part –
Black - CE compliant in accordance with the EMC guideline and low
voltage directives.
Installation Instructions:
- Installation of the product is done with a metal flange. It is
fixed to the junction box by using screws. - The switch has magnets and should be positioned with the card
slot upwards. - The device will stick on the flange by magnetization.
- Multiple devices can be combined up to 3. NOTE: Distance
between center of flanges is 71 mm.
Commissioning:
- The device default physical address is 15.15.255.
- Determination of the physical address and sending of parameters
are actualized with Engineering Tool Software (ETS4 or
higher). - .knxprod file must be imported to the ETS.
(http://www.eaetechnology.com/) - A detailed information about parameter configuration can be
found in Product Manual of device.
Usage Instructions:
- Use the card holder for energy-saving purposes in hotel guest
rooms. - Insert the compatible Mifare 13.56 MHz card into the card slot
facing upwards. - Use the configurable RGB illuminated buttons for switching,
dimming, shutter/blind, value, scene control, and status
notification. - Ensure that the device is not operated out of the specified
technical data which is stated. - Clean the device only with a dry cloth. Do not use wet cloths,
caustics, and solvents.
Installation Manual Mona Card Holder EAE KNX MONA Series
MONA Card Holder R1
Installaon Installaon of the product is done with metal flange. It is fixed to the juncon box by using screws. The switch has magnets and should be posioned the card slot upwards. The device will sck on flange by magnezaon. Mulple devices can be combined up to 3. NOTE: Distance between center of flanges is 71 mm.
Device Descripon EAE Card Holder is intended to be used for energy saving purposes in hotel guest rooms.
Monoblock glass design
Compable with Mifare 13.56 MHz card Contactless reading for RFID Card informaon. Prevents mechanical wear and card deformaon. 60×60 mm easy mounng to standard juncon boxes. Different glass color opons Configurable RGB illuminated buons Up to 6 independent programmable buons
Switching Dimming Shuer/Blind
Value Scene control Status noficaon
Operaon and Display
6
5
1
1. KNX Port Terminal 2. Programming LED 3. Programming Buon
Technical Data
4
4. Control Buons 5. Card IN-OUT LED 6. Card Inseron (Vercally)
Protecon Type Safety Class Connecons Power Supply Operang Elements Operang Temperature Humidity
Dimensions
Box Material
Color
CE
IP20 II KNX Voltage Current drawn from bus LED (red) LED (RGB)
EN 60 529 EN 61 140 Bus Connecon 21V… 30V DC, KNX < 27 mA Addr Prog. LED Status LEDs
Ambient
-5° C + 45° C
Max. Air humidity
95% no moisture
Front side
90 x 100 mm
Side Surface mounted part 12 mm
Side Flush mounted part 18.8 mm
Surface : Glass
Flush Mounted Part : Polycarbonate
Surface : Black or White
Flush Mounted Part : Black
In accordance with the EMC guideline and low voltage
direcves.
Commissioning Device default physical address is 15.15.255. Determinaon of the physical address and seng of parameters are actualized with Engineering Tool Soware (ETS4 or higher). “.knxprod” file must be imported to the ETS. (hp://www.eaetechnology.com/)
A detailed informaon about parameter configuraon can be found in Product Manual of device.
Installaon and commissioning of device may only be implemented by trained electricians. The relevant standards, direcves, regulaons and instrucons must be observed when planning and implemenng the electrical installaon. -Protect the device against moisture, dirt and damage during transport, storage and operaon!
-Do not operate the device out of the specified technical data which is stated.
-The device may only be operated in closed enclosures (Distribuon boards)
Cleaning If device becomes dirty, only a dry cloth can be used for cleaning. t is not suitable to use wet cloths, causcs and solvents.
© EAE Technology