EH-M Microwave Induction Dimmer and Switch
Product Information: Microwave Induction Dimmer &
Switch
Model No.: EH-M
The Microwave Induction Dimmer & Switch is a ceiling-mounted
motion detector that operates on a high frequency system of
10.525GHz. It features a built-in daylight sensor and can output 1
channel of 0/1-10V signal, which can be connected to a 0/1-10V
dimmable driver. The device has a high voltage AC input and a high
voltage AC relay output with zero-cross detection. It can also
function as an RF remote and output RF 2.4G signal, which can be
paired with an RF LED controller or RF dimmable LED driver. The
detection area, time delay, and light threshold can be adjusted
using the knob potentiometer.
Product Usage Instructions:
- Mount the Microwave Induction Dimmer & Switch on the
ceiling using the included mounting hardware. - Connect the device to a 100-240VAC power source.
- Connect the device to a 0/1-10V dimmable driver using the
output channel. - To use the device as an RF remote, pair it with an RF LED
controller or RF dimmable LED driver. Follow the pairing
instructions provided with your controller or driver. - Adjust the detection area, time delay, and light threshold
using the knob potentiometer. - The device will automatically detect motion and turn on/off the
lights as needed. The built-in daylight sensor will help conserve
energy by only turning on the lights when necessary.
Note: This product is compliant with LVD regulations and has a
maximum output signal of 0/1-10V (Max.30mA), RF 2.4GHz. The maximum
output current is 4A (AC) and the power consumption is dependent on
usage.
Microwave Induction Dimmer & Switch
Model No.: EH-M
Motion detector/ 0-10V output/AC relay output/RF 2.4G remote/Ceiling mounting
Features
Ceiling mounting microwave motion detectors with HF system 10.525GHz, built-in daylight sensor. Output 1 channel 0/1-10V signal, connect with 0/1-10V dimmable driver. High voltage AC input, High voltage AC relay output with zero-cross detection. Work as RF remote, output RF 2.4G signal, matched with RF LED controller or RF dimmable LED driver optional. Detection area, time delay and light threshold can be set via knob potentiometer.
LVD
Technical Parameters
Working voltage
100-240VAC
Output signal
0/1-10V (Max.30mA), RF 2.4GHz
Output current
Max 4A (AC)
HF system
10.525GHz
Power consumption
<1.6W(Operation)
Detection zone
Max.(DxH) 20 x 10m
Detection sensitivity
10%/25%/50%/75%/100%
Hold time
10s/30s/90s/3min/10min/30min/+
Stand-by time
0s/30s/90s/3min/10min/30min/+
Daylight threshold
10lux/30lux/50lux/100lux/150lux/200lux/Disable
Expected light
50lux/100lux/150lux/200lux/250lux/300lux/400lux
Mounting height
10m Max.
Motion detection
0.5-3m/s
Detection angle
360°(ceilling installation)
Operation temperature IP rating Warranty
Ta: -20 OC ~ +50 OC IP20 5 years
86.00 mm
Ceiling (drill hole O 86mm)
95.00 mm
95.00 mm
40.00 mm
User Manual Ver 1.0.0
Page 1
Mechanical Structures and Installations
Dim +
OUTPUT 0/1-10V (Max.30mA)
DIMMER SWITCH 2
0-10V 1-10V 1
INPUT 100-240VAC
NL
Dim DIP switch for 0-10V or 1-10V select and switch or dimmer select
AC Lout AC L iutput AC N iutput
Light sensing
10.525GHz
50%
Detection area
25%
75% 100%
10%
SENS
Time adjustment
TIME 200 15050 100
Light adjustment
100 5010 30
++
300 251050 200
LIGHT
MATCH
SENSING
RUN
LUX TIME 10S -+: Hold Time 0S -+: Standby Time
LUX 10-off: Threshold 50-400: Expected
LED indicator
Match key
400 400
100 5010 30
++
300 251050 200
Detection Pattern
10.525GHz
25%
10%
50% SENS
75% 100%
TIME 200 15050 100
LIGHT
MATCH
SENSING
RUN
LUX TIME 10S -+: Hold Time 0S -+: Standby Time
LUX 10-off: Threshold 50-400: Expected
10 8
6
4
2.5
10% 2.5
25% 4
50% 75% 100%
6
8 10
Ceilling mounting(Unit:m) Suggested installation height: 2.5-10m
Page 2
Wiring diagram
Used as dimmer or switch, connect with 0/1-10V dimming driver (no use AC OUT)
EH-M
Microwave Induction Dimmer & Switch Vin= 100-240VAC Out= 0/1-10V + RF 2.4G L1 out= 4A Max. No Load Power 1.6W Ta: -20~+50
OUTPUT 0/1-10V (Max.30mA)
DIMMER SWITCH 2
0-10V 1-10V 1
INPUT 100-240VAC
N L L1
DIM+
ACN 0/1-10V
DIM-
ACL Dimmable Driver V+
V-
+
Single color LED strip
AC110-220V Used as dimmer or switch, connect with 0/1-10V dimming driver (use AC OUT)
EH-M
Microwave Induction Dimmer & Switch Vin= 100-240VAC Out= 0/1-10V + RF 2.4G L1 out= 4A Max. No Load Power 1.6W Ta: -20~+50
OUTPUT 0/1-10V (Max.30mA)
DIMMER SWITCH 2
0-10V 1-10V 1
INPUT 100-240VAC
N L L1
DIM+
ACN 0/1-10V
DIM-
ACL Dimmable Driver V+
V-
+
Single color LED strip
AC110-220V Used as switch, connect with non-dimmable LED light (use AC OUT)
Non-dimmable LED light
EH-M
Microwave Induction Dimmer & Switch Vin= 100-240VAC Out= 0/1-10V + RF 2.4G L1 out= 4A Max. No Load Power 1.6W Ta: -20~+50
OUTPUT 0/1-10V (Max.30mA)
DIMMER SWITCH 2
0-10V 1-10V 1
INPUT 100-240VAC
N L L1
Page 2
AC110-220V
EH-M Microwave Induction Dimmer & Switch
0-10V or 1-10V dimming setting
Select 0-10V dimmer or 1-10V dimmer according to dimmable LED driver.
0-10V Dimmer
1-10V Dimmer
1100.0
99.0
88.0
77.0
P0-1W0MV ldeutvye(l(%V))
66.0
55.0
44.0
33.0
22.0
11.0
10 20 30 40 50 60 70 80 90 100
Brightness(%)
ON 0-10V 1 1-10V
Note: When the output channel is off, the output dimming signal is 0V or 1V. Please read the dimming section of the dimming driver manual. If the dimming characteristic curve is the same as right, you must select 1-10V dimmer and use AC OUT function, otherwise you can`t turn off the lights.
P1-1W0MV ldeutvye(l(%V))
Output current
1100.0 99.0 88.0 77.0 66.0 55.0 44.0 33.0 22.0 11.0
10 20 30 40 50 60 70 80 90 100
Brightness(%)
ON 0-10V 1 1-10V
100% 90% 80% 70% 60% 50% 40% 30% 20% 10% 1V 2V 3V 4V 5V 6V 7V 8V 9V 10V
Dimming input
Work as RF Remote (two match ways)
The microwave induction Dimmer & Switch can be matched with one or multiple RF LED controller or RF dimmable LED driver, including single color, dual color, RGB, RGBW, RGB+CCT or switch light type, turn on or turn off light by motion detection. End user can choose the suitable match/delete ways. Two options are offered for selection:
Use the controller’s Match key
Match: Short press the match key of the controller, immediately press the match key of the microwave induction Dimmer & Switch.
Delete: Press and hold the match key of the controller for 5s to delete all match, The light blinks 5 times means all matched remotes were deleted.
Use Power Restart
Match: Switch off the powerof the controller, then switch on power, repeat again. Immediately short press the match key of the microwave induction Dimmer & Switch 3 times. The light blinks 3 times means match is successful.
.DSwelietcteh: off the powerof the controller, then switch on power, repeat again. Immediately short press the match key of the microwave induction Dimmer & Switch 5 times. The light blinks 5 times means all matched remotes were deleted.
Page 3
Typical application 1: used as a switch
Turns on the light upon detection of motion, and turns off after a pre-selected hold time when there is no movement.
1. With sufficient ambient light, the sensor does not turn on the light.
2. With insufficient ambient light, the sensor turns on the light when motion is detected.
3. After hold time, the light turns off if no motion detected.
100 5010 30
++
25%
10%
DIMMER SWITCH 2
50%
SENS
TIME 200 15050 100 LUX
400
300 251050 200
75% 100%
Select the DIP Switch 2 OFF to set as SWITCH type firstly, then select the combination on knob potentiometer for each specific application.
Detection area: Detection area can be reduced by rotate knob to fit precisely each application.
Hold time: Refers to the time period remains light on and 100% brightness state after no motion is detected. Stand-by time: Refers to the time period remains light on and dim to 20% brightness state after elapse of hold time if no new motion is detected. Holding down the match key, adjust the knob to set thestand-bytime (mustbe0s) firstly, then stop press the match key, adjust the knob to set theholdtime.
Daylight sensor: The sensor can be set to only allow the lamp to illuminate when below a defined ambient brightness threshold. Whensettooff(Disable)mode,thedaylight sensor will switch on the lamp when motion is detected regardless of ambient light level. 50lux: twilight operation. 30 lux: evening operation. 10 lux: darkness operation. Note that daylight sensor is active only when lamp totally switches off, and the ambient lux level refers to internal light reaching the sensor.
Setting on this demonstration:
Detection area: 50%
Hold time: 90S Stand-by time: 0S Daylight sensor: 50lux
User Manual Ver 1.0.0
Page 5
EH-M Microwave Induction Dimmer & Switch
Typical application 2: used as a switch with two-step dimming
Turns on the light upon detection of motion, after a pre-selected hold time, dim to 20% brightness, and turns off after a pre-selected stand-by time when there is no movement.
1. With sufficient ambient light, the sensor does not turn on the light.
2. With insufficient ambient light, 3. After elapse of hold time,
4. After elapse of stand-by time,
the sensor turns on the light and the sensor dim to 20% brightness the sensor turns off the light if no
dim to 100% brightness when if no new motion detected.
motion detected.
motion is detected.
100 5010 30
++
25%
10%
DIMMER SWITCH 2
50%
SENS
TIME 200 15050 100 LUX
400
300 251050 200
75% 100%
Select the DIP Switch 2 OFF to set as SWITCH type firstly, then select the combination on knob potentiometer for each specific application.
Detection area: Detection area can be reduced by rotate knob to fit precisely each application.
Hold time: Refers to the time period remains light on and 100% brightness state after no motion is detected. Stand-by time: Refers to the time period remains light on and dim to 20% brightness state after elapse of hold time if no new motion is detected. Holding down the match key, adjust the knob to set thestand-bytime (must>0s)firstly, then stop press the match key, adjust the knob to set theholdtime (mustbenot +).
Daylight sensor: The sensor can be set to only allow the lamp to illuminate when below a defined ambient brightness threshold. Whensettooff(Disable)mode,thedaylight sensor will switch on the lamp when motion is detected regardless of ambient light level. 50lux: twilight operation. 30 lux: evening operation. 10 lux: darkness operation. Note that daylight sensor is active only when lamp totally switches off, and the ambient lux level refers to internal light reaching the sensor.
Setting on this demonstration:
Detection area: 50%
Hold time & Stand-by time: 90S
Daylight sensor: 50lux
Typical application 3: used as a dimmer
Turns on the light and dim up to expected brightness level upon detection of motion, and turns off after a pre-selected hold time when there is no movement.
1. The sensor turns on the light and dim up to expected brightness level when motion is detected.
2. After hold time, the light turns off if no motion detected.
25%
10%
DIMMER SWITCH 2
50%
SENS
75% 100%
Select the DIP Switch 2 ON to set as DIMMER type firstly, then select the combination on knob potentiometer for each specific application.
Detection area: Detection area can be reduced by rotate knob to fit precisely each application.
TIME 200 15050 100
LUX
400
300 251050 200
Hold time: Refers to the time period remains light on state after no motion detected. If set +, the lights will stay on.
Daylight sensor: The sensor can be set to allow the lamp to illuminate to expected brightness level. If the detected brightness is less than the expected brightness, the output will dim up to full brightness(100%). If the detected brightness is larger than the expected brightness, the output will dim down to min brightness(1%). Note that daylight sensor is active only when lamp switches on, and the ambient lux level refers to internal light reaching the sensor.
Setting on this demonstration:
Detection area: 50%
Hold time: 90S
Daylight sensor: 150lux
100 5010 30
++
User recommended settings
Scenarios
Settings
Passage, staircase
Detection distance 4-6m
Balcony, corridor
4-6m
Cloakroom, storeroom
2-3m
Garage Kitchen Dinning room Toilet
2-3m 3-4m 3-4m 2-3m
Meeting room
2-3m
Indoor public access Underground public access
4-6m 4-6m
Hold time
10s 10s 90s 90s 90s 3min 3min 10min 10min 10min
Daylight sensor
Twilight(50lux) / Darkness(10lux) Twilight(50lux) / Darkness(10lux) Evening(30lux) Evening(30lux) Evening(30lux) Evening(30lux) / Twilight(50lux) Daytime(>50lux) / Evening(30lux) Evening(30lux) Daytime(>50lux) Daytime(>50lux)
Application notice
1. The sensor is designed for indoor use only. The raining or wind blowing may trigger the microwave sensor even if without human motion when outdoor use.
2. The sensor should be installed by a professional electrician. please turn off the power before installing, wiring and changing setting of the knob.
3. The distance between any two sensors should be at least 3m to avoid interference each other. 4. When the microwave sensor is installed in space with large reflector, for example
a warehouse with metal roof, the microwave signal will be reflected and cause the lights permanent illuminated even if without motion signal. Please reduce the detection area to solve the problems. 5. Make sure the sensor not close to or be blocked by high density materials, such as metal, glass, concrete walls etc. The materials will reduce or block microwave signal and cause false trigger. 6. The light sensitivity threshold is in a sunny environment, no shadow and ambient light diffuse reflection. Ambient lux level could be different in different environment, weather, climate, time-of-delay and season. 7. Make sure there are no fans, DC motor, or other vibrating objects in installation area. The movement will trigger sensor as well.
Page 6
Page 7
Page 8