Cencon Mstp And Ip Communication Manual For Modbus And Bacnet User Guide

Cencon Mstp And Ip Communication Manual For Modbus And Bacnet User Guide

CenCon logoCenCon logo 2Communication Manual for
Modbus and BACnet (MSTP and IP)
Manual Revision 1.02
CenCon logo 1© 2021 Airtex Manufacturing Partnership. All rights reserved.
www.engineeredair.com

MSTP and IP Communication Manual for Modbus and BACnet

If any errors or omissions are noted please contact the nearest Engineered Air Technical Service Department. To ensure warranty is honored, only qualified personnel should be employed for service or troubleshooting. If further information is required please contact the nearest Engineered Air sales office.
Copyright
This document and the information in it are the property of Engineered Air, and may not be used or reproduced in whole or in part without written permission. Engineered Air reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.

CONTACT INFORMATION

Canadian Head Office and Factory
1401 Hastings Cres. SE
Calgary, Alberta, Canada
T2G 4C8
PH: (403) 287 2590
FX: 1 888 364 2727
Email: [email protected]
USA Head Office and Factory
32050 W. 83rd Street
De Soto, Kansas, USA
66018
PH: (913) 583 3181
FX: (913) 583 1406
Canadian Eastern Factory
1175 Twinney Drive
Newmarket, Ontario, Canada
L3Y 5V7
PH: (905) 898 1114
FX: (905) 898 7244
This Manual is designed to be used and read in conjunction with the CenCon User Manual. A digital printable copy of all manuals can be found at https://www.engineeredair.com/manuals/
The CenCon is a configurable logic controller designed to be the primary controller of Engineered Air heating, cooling and ventilation equipment. This manual should be used in conjunction with the CenCon operation manual. The CenCon is designed to control the cooling, heating, and mixing economizer. In this manual, the primary setpoint and sensor refer to the final leaving temperature. All temperature register readings are based on degrees Fahrenheit. Conversion to degrees Celsius can be accomplished at the front end software.
The CenCon is equipped with two RS485 ports equipped for Modbus RTU the BACnet® MS/TP protocols and an Ethernet port equipped for the BACnet® TCP/IP protocol. This manual describes the BACnet® objects and the information contained in each object. In this manual, BACnet® objects that can be written to are said to be EMS (Energy Management System) commanded, identified by R/W (Read/ Write).

INTRODUCTION

The CenCon supports Modbus RTU, BACnet MS/TP RS-485 and BACnet/IP. The Baud rate is fixed at 19200 for Modbus RTU networks and can be adjusted from 19200 to 38400 for MS/TP networks. This manual describes the BACnet objects and the information contained in the CenCon. In this manual object points that can be written to are said to be EMS (Energy Management System) commanded.
Wiring
The CenCon can be connected to either an RS-485 network or a to an Ethernet/IP network. The BACnet MS/TP RS-485, & BACnet/IP communication cables must conform to BACnet specifications.
RS485
The CenCon has a gray terminal strip that is used for all RS-485 communication connections.
Terminals SmA and SmB have been designated and must be used to connect to the RS-485 Modbus network terminals.
Terminals BnA and BnB have been designated and must be used to connect to the RS-485 BACnet network.
The RS-485 communication cable to the CenCon should be a 24awg shielded twisted pair (STP) with a shunt capacitance of 16pF per foot and 100 ohm characteristic impedance.
Ethernet
The CenCon is equipped with a standard RJ45 Ethernet port located on the top of the controller. The Ethernet port is designed to be incorporated with a BACnet® over IP network that is used to communicate with the building EMS.
BACnet Communication Default Factory Settings
These default settings can be configured on the CenCon service display.=
Modbus RTU

Baud Rate19200
Address1

BACnet MSTP

Instance270000
Baud Rate38400
Address3
Max Master10
Max Info Frames20

BACnet IP

Instance270000
IP192.168.0.10
Subnet255.255.255.0
Gateway000.000.000.000
DNS 1000.000.000.000
UDP Port#47808 (not adjustable)

Note:
After making any changes to the default communication setting you must cycle the power to the controller to reset it and force the updates.
PICS & BTL Approved
BACnet PICS (Protocol Implementation Conformance Statement) defines the options available by BACnet that are implemented in the CenCon. These PICS are available from the factory upon request. The following defines the BACnet objects available on the network. EMS is used to describe the objects that can be commanded by any 3rd party ‘Energy Management System’.

CenCon POINTS LIST

Depending on the style and type of appliance, not all points will be valid.
Read / Write

DESCRIPTIONIn / OutMODBUS
Register
BACnet
Address
TYPER/W
Discharge Air SetpointO40001AO0Int/10 °FR/W
Damper Minimum PositionO40002AO1Integer mVR/W
VFD Minimum SpeedO40003AO2Integer mVR/W
Humidification SetpointO40004AO3Integer %R/W
Dehumidification SetpointO40005AO4Integer %R/W
Supply Fan EnableO00001BO00/1R/W
C-XM EnableO00002BO10/1R/W
J-XM EnableO00003BO20/1R/W
G-XM EnableO00004BO30/1R/W
M-XM EnableO00005BO40/1R/W
S-XM EnableO00006BO50/1R/W
H-XM EnableO00007BO60/1R/W
ER-XM EnableO00008BO70/1R/W
C-XM Dehumidification EnableO00009BO80/1R/W

Read Only

DESCRIPTIONIn / OutMODBUS
Register
BACnet
Address
TYPER/W
Modulating CoolingO40003AO2Integer mVR
Modulating EconomizerO40002AO1Integer mVR
Modulating HeatingO40001AO0Integer mVR
VFD Command SpeedO40004AO3Integer mVR
VFD Feedback SpeedI30007AI6Integer mVR
Supply Duct PressureI30002AI1IntegerR
Outside HumidityI30003AI2Integer %R
Return/ Room HumidityI30006AI5Integer %R
Feedback DamperI10002BI11/0R
Damper End SwitchI10005BI4I/OR
AlarmO00005BO41/0R
Supply AirO00003BO21/0R
Damper ActuatorO00002BO11/0R
Occupied/ UnoccupiedI10006BI51/0R
Time Clock BypassI10007BI61/0R
Enable FanI10008BI71/0R
Secondary BACnet AlarmI10001BI01/0R
Mixed Air TemperatureI30019AI18Int/10 °FR
Discharge Air TemperatureI30021AI20Int/10 °FR
Ambient Air TemperatureI30020AI19Int/10 °FR
Return/ Room TemperatureI30017AI16Int/10 °FR
Modulating Room ThermostatI30009AI8Integer %R
Remote VFD SetpointI30010AI9Integer %R
Modulating HumidityI30006AI5Integer %R
DX Coil TemperatureI30018AI17Int/10 °FR
DehumidificationI10009BI81/0R
VFD BypassI10004BI31/0R
Heating DemandO40005AO4Integer %R
Cooling DemandO40006AO5Integer %R
Humidification DemandO40007AO6Integer %R
Recovery DemandO40008AO7Integer %R
Dehumidification DemandO40009AO8Integer %R

EXPANSION MODULES POINTS LIST

The following points are read only.
C-XM

DESCRIPTIONIn / OutMODBUS
Register
BACnet
Address
TYPER/W
Modulating CompressorO40001AO0Integer mVR
Modulating Condenser Fan #1O40002AO1Integer mVR
Modulating Condenser Fan #2O40003AO2Integer mVR
Modulating ReheatI40004AO3Integer mVR
Cooling stage #1O00001BO01/0R
Cooling stage #2O00002BO11/0R
Cooling stage #3O00003BO21/0R
Cooling stage #4O00004BO31/0R
Cooling stage #5O00005BO41/0R
Cooling stage #6O00006BO51/0R
Condenser Fan Stage #1O00007BO61/0R
Condenser Fan Stage #2O00008BO71/0R
Stepped Reheat Stage #1O00009BO81/0R
Stepped Reheat Stage #2O00010BO91/0R
Digital Output (SSR)I10001BI11/0R
Dehumidify SetpointI30021AI21Integer %R
Enable ReheatI10001BI01/0R
Enable CoolingI10002BI11/0R

J-XM

DESCRIPTIONIn / OutMODBUS
Register
BACnet
Address
TYPER/W
Feedback GasI30003AI2Integer mVR
Feedback AirI30004AI3Integer mVR
Modulating Ball ValveO40001AO0Integer mVR
Combustion Air SwitchI10003BI21/0R
Blocked Flue SwitchI10001BI01/0R
Enable HeatI10002BI11/0R
Pilot ValveO00005BO41/0R
Safety RelayO00006BO51/0R
Flame RelayO00007BO61/0R
High LimitI10005BI41/0R
Condensate ProbeI30005AI4IntegerR
MX ValveO40005AO4IntegerR

G-XM

DESCRIPTIONIn / OutMODBUS
Register
BACnet
Address
TYPER/W
Feedback GasI30003AI2Integer mVR
Feedback AirI30004AI3Integer mVR
Modulating Ball ValveO40001AI0Integer mVR
Modulating Combustion AirO40002AI1Integer mVR
Combustion Air SwitchI10003BI21/0R
Blocked Flue SwitchI10001BI01/0R
Enable HeatI10002BI11/0R
Combustion BlowerO00001BO01/0R
Pilot ValveO00005BO41/0R
Safety RelayO00006BO51/0R
Flame RelayO00007BO61/0R
High LimitI10005BI41/0R
Condensate probe sensorI30005AI4Integer ΩR

M-XM

DESCRIPTIONIn / OutMODBUS
Register
BACnet
Address
TYPER/W
Feedback GasI30003AI2Integer mVR
Modulating Ball ValveO40001AO0Integer mVR
Profile Pressure ActuatorO40002AO1Integer mVR
High Speed EnableI10001BI01/0R
Enable HeatI10002BI11/0R
High SpeedO00001BO01/0R
Exhaust Fan InterlockO00002BO11/0R
Dual Flame RodO00003BO21/0R
Water PumpO00004BO31/0R
Pilot ValveO00005BO41/0R
Safety RelayO00006BO51/0R
Flame RelayO00007BO61/0R
High LimitI10005BI41/0R
MX ValveO40005AO4IntegerR

ER-XM

DESCRIPTIONIn / OutMODBUS
Register
BACnet
Address
TYPER/W
Modulating By-Pass DamperO40001AO0Integer mVR
Modulating Energy RecoveryO40002AO1Integer mVR
Enable HeatI10001BI01/0R
Rotation SensorI10002BI11/0R
By-Pass DamperO00001BO01/0R
Enable WheelO00005BO41/0R
Leaving Air TemperatureI30020AI19Int/10 °FR
Exhaust Air TemperatureI30021AI20Int/10 °FR

S-XM

DESCRIPTIONIn / OutMODBUS
Register
BACnet
Address
TYPER/W
Feedback GasI30003AI2Integer mVR
Modulating High LimitI30004AI3Integer mVR
Modulating Ball ValveO40001AO0Integer mVR
Duct High LimitI10003BI21/0R
Blocked Flue SwitchI10001BI01/0R
Enable HeatI10002BI11/0R
Fill ValveO00001BO01/0R
Mixing ValveO00002BO11/0R
Drain ValveO00003BO21/0R
Fill Valve SideO00004BO31/0R
Pilot ValveO00005BO41/0R
Safety RelayO00006BO51/0R
Flame RelayO00007BO61/0R
High LimitI10005BI41/0R
Direct Humidity ControlI30001AI0IntegerR
Drain SensorI30016AI15Integer ΩR
Condensate ProbeI30005AI4Integer ΩR
Fill Water ProbeI30007AI6Integer ΩR
Low Water ProbeI30006AI5Integer ΩR
MX ValveO40005AO4IntegerR

H-XM

DESCRIPTIONIn / OutMODBUS
Register
BACnet
Address
TYPER/W
Modulating OutputO40002AO1Integer mVR
Enable HeatI10001BI01/0R
Heating Stage #1O00001BO01/0R
Heating Stage #2O00002BO11/0R
Heating Stage #3O00003BO21/0R
Heating Stage #4O00004BO31/0R
Heating Stage #5O00005BO41/0R
Heating Stage #6O00006BO51/0R
Heating Stage #7O00007BO61/0R
Door SwitchI10004BI31/0R
High LimitI10005BI41/0R

CD-XM

DESCRIPTIONIn / OutMODBUS
Register
BACnet
Address
TYPER/W
Combustion BlowerO00001BO01/0R
Safety RelayO00002BO11/0R

P-XM

DESCRIPTIONIn / OutMODBUS
Register
BACnet
Address
TYPER/W
Pressure SwitchO00002BO11/0R
Pressure SensorO30001AI0Integer “wcR
Pressure TransducerO40001AO0Integer mVR

POINT DESCRIPTIONS

Read / Write
The following Software point list are commandable (Read/Write) by BACnet or Modbus. Available points depend on appliance type and arrangement.
Discharge Air Setpoint
Final calculated discharge setpoint.
Damper Minimum Position Setpoint
Minimum outside air setpoint.
VFD Minimum Speed Setpoint
VFD minimum speed setpoint; Refer to unit function for requirements.
Humidification Setpoint
Room or return air humidity setpoint.
Dehumidification Setpoint
Room or return air dehumidification setpoint.
Supply Fan Enable
Enable start for system operation.
Read Only
CenCon
Modulating Cooling
Chilled water coil valve actuator.
Modulating Economizer
Modulating economizer / mix box actuator.
Modulating Heating
Hot water coil valve actuator.
VFD Command Speed
VFD control signal.
VFD Feedback Speed
Confirmation of VFD speed.
Supply Duct Pressure
Duct pressure sensor.
C-XM Enable
Mechanical cooling expansion module.
J-XM Enable
Indirect fired gas heating expansion module for DJS, DJE, DJX (up to 140) appliances.
G-XM Enable
Indirect fired gas heating expansion module for DG anDJX 200/300 appliances.
M-XM Enable
Direct fired gas heating expansion module.
S-XM Enable
Gas fired humidifier expansion module.
H-XM Enable
Electric heat expansion module.
ER-XM Enable
HRW heat wheel energy recovery enabled.
C-XM Dehumidification Enable
Mechanical cooling with reheat appliances.
Outside Humidity
Outside / ambient air relative humidity sensor.
Return/ Room Humidity
Room / return air relative humidity sensor.
Feedback Damper
Economizer / mix box damper actuator position feedback signal.
Damper End Switch
Mechanical damper end switch.
Alarm
General alarm output annunciation.
Supply Air
Blower enable status.
Damper Actuator
Damper actuator status.
Occupied/ Unoccupied
Enable occupied mode
Enable Fan
Appliance enable.
Secondary BACnet Alarm
Spare alarm input for BACnet annunciation
Mixed Air Temperature
Economizer or mixing damper leaving air temperature.
Discharge Air Temperature
Final leaving temperature.
Ambient Air Temperature
Ambient/outside air temperature.
Return/ Room Temperature
Return or room air temperature.
Modulating Thermostat
Roomstat heating / cooling signal.
Remote VFD Setpoint
VFD speed demand signal.
Modulating Humidity
Humidity demand signal.
DX Coil Temperature
Pre-cool leaving air temperature.
Dehumidification
Dehumidification mode enabled.
VFD Bypass
VFD bypass mode active.
C-XM
Modulating Compressor
Output to modulating compressor.
Modulating Condenser Fan #1 & #2
Output to variable speed condenser fans.
Modulating Reheat
Output to modulating hot gas reheat coil.
Cooling stage #1 to #6
Cooling stages enabled.
Condenser Fan Stage #1 & #2
Ambient temperature based condenser fan #1 or #2 enabled.
Stepped Reheat Stage #1 & #2
Stepped / staged reheat output.
Dehumidify Setpoint
RH% setpoint for dehumidification operation.
Enable Reheat
Hot gas reheat enabled.
Enable Cooling
Mechanical cooling enabled.
J-XM
Feedback Gas
Modulating gas valve actuator feedback signal.
Modulating Ball Valve
Modulating gas valve actuator output.
Combustion Air Switch
Proof of combustion air flow.
Blocked Flue Switch
Opens on blocked flue.
Enable Heat
Expansion module heating function enabled.
Pilot Valve
Pilot valve operation is interrupted once main flame sensing is established.
Safety Relay
Secondary safety lockout contact.
Flame Relay
Flame relay contact enabled.
High Limit
Opens on high heat exchanger section temperature.
Condensate Probe
Condensate probe sensor (Ω).
MX Valve
DC current output to the magnetic style modulating gas valve.
G-XM
Feedback Gas

Modulating gas valve actuator feedback signal.
Feedback Air
Modulating combustion air actuator feedback signal.
Modulating Ball Valve
Modulating gas valve actuator output.
Combustion Air Switch
Proof of combustion air flow.
Blocked Flue Switch
Normally closed, opens on blocked flue.
Enable Heat
Expansion module heating function enabled.
Pilot Valve
Pilot valve operation is interrupted once main flame sensing is established.
Safety Relay
Secondary safety lockout.
Flame Relay
Flame relay enabled.
High Limit
Normally closed, opens on high temperature
Condensate Probe
Condensate probe sensor
M-XM
Feedback Gas
Modulating gas valve actuator feedback signal.
Modulating Ball Valve
Modulating gas valve actuator output.
Profile Pressure
Modulating profile pressure damper actuator position.
High Speed Enable
Initiate high speed operation.
Enable Heat
Expansion module heating function enabled.
High Speed
High speed fan start contact.
Exhaust Fan Interlock
Single or low speed exhaust fan start contact.
Dual Flame Rod
Relay output to switch flame rods.
Water Pump
Enable evaporative (swamp cooler) water pump.
Pilot Valve
Pilot valve operation is interrupted once main flame sensing is established.
Safety Relay
Secondary safety lockout contacts.
Flame Relay
Flame relay enable contacts.
High Limit
Normally closed, opens on high temperature.
MX Valve
DC current output to the modulating gas valve.
ER-XM
Modulating By-Pass Damper
Modulating output to bypass damper actuator.
Modulating Energy Recovery
Modulating output to heat wheel drive motor, heat pipe tilt actuator, or heat plate damper actuator.
Enable Heat
Expansion module energy recovery operation.
Rotation Sensor
Input from rotation sensor.
By-Pass Damper
Bypass damper enabled.
Enable Wheel
Wheel motor start enabled.
Leaving Air Temperature
Temperature of the air at heat recovery device’s discharge plenum, in ⁰F
Exhaust Air Temperature
Temperature of the air at heat recovery device’s exhaust plenum, in ⁰F
S-XM
Feedback Gas
Compares the ball valve actuator feedback signal to the demand signal.
Modulating High Limit
Optional analog input for duct mounted high humidity sensing.
Modulating Ball Valve
Modulating gas valve actuator output.
Duct High Limit
Duct mounted high humidity sensing opens on high humidity.
Blocked Flue Switch
Normally closed, opens on blocked flue.
Enable Heat
Gas fired humidifier expansion module enabled.
Fill Valve
Enable side tank (SHX) fill valve.
Pilot Valve
Pilot valve operation is interrupted once main flame sensing is established.
Safety Relay
Secondary safety lockout contacts.
Flame Relay
Flame relay enable contacts.
High Limit
Normally closed, opens on high temperature.
Direct Humidity
Input for direct control of humidifier.
Drain Sensor
Drain probe sensor input.
Condensate Probe
Condensate probe (SHX) sensor input.
Fill Water Probe
Fill water level sensor.
Low Water Probe
Low water level sensor.
MX Valve
DC current output to the modulating gas valve.
H-XM
Modulating Output
Modulating output to external SCR controller.
Enable Heat
Expansion module electric heating enabled.
Heating Stage #1 to #7
Staged heating output.
Door Switch
External safeties input
High Limit
Normally closed, opens on high temperature
CD-XM
Combustion Blower
Modulating output command to combustion air blower motor.
Safety Relay
Contact open on failure.
P-XM
Pressure Switch
Output contact.
Pressure Sensor
Pressure sensor output 0-4”w.c.
Pressure transducer
Pressure transducer scaled output from 0 to 10 VDC based on 0-4 “wc.

CenCon logoCenCon logo 2IOM65
August 2021 R2