Intesis Inbactos001r100 Digital Systems To Bacnet Mstp Interface Instruction Manual

Intesis Inbactos001r100 Digital Systems To Bacnet Mstp Interface Instruction Manual

Intesis - logoInterface INBACTOS001R100
INBACTOS001R100 Digital systems to BACnet MSTP Interface

Instruction Manual

Safety instructions

PROMATIC Partridge 4 Trap Trailer or Hi Lift - ICON 8 WARNING
Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the interface and/or the AC indoor unit.

  • This interface must be installed by accredited technical personnel (electrician, installer, or technical personnel) and following all the safety instructions.
  • Before manipulate the AC indoor unit be sure it is completely disconnected from Mains power.
  • In case of wall mounting of the interface beside the AC indoor unit, fix the interface safely following the instructions of the diagram below.
  • This interface must be installed in an access restricted location.

Installation instructions

  • Disconnect the Toshiba system from Mains Power.
  • Fix the interface beside the AC indoor unit (wall mounting) following the instructions in the diagram below (respect the safety instructions given above).
  • Connect the interface to AB bus in any point of the bus. The AB bus is the bus that connects the AC indoor unit and the wired remote controller, is a twowire bus connecting terminals AB of both, this AB connection has no specific polarity.
  • Connect the EIA485 bus to the connector EIA485 of the interface (for MS/TP connection).
  • Close the AC indoor unit and reconnect it to Mains Power.
  • Follow the instructions on the user manual for configuring and commissioning the interface.
  • Follow the instructions of the next page to configure the interface through on-board DIP-switches.

Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface

Important: If a wired remote controller of the AC manufacturer is connected in the same bus, communication may shut down. In case it happens, use an external power supply connected to the PS connector in our device to overcome this situation.
If using an external power supply, it must comply with NEC Class 2 or Limited Power Source (LPS) and SELV rated power supply. Respect the polarity. Apply always a voltage within the range admitted and of enough power (12V DC, min. 100 mA).
FCC: This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:

  1. This device may not cause harmful interference
  2. This device must accept any interference received, including interference that may cause undesired operation.

IMPORTANT: Keep the cable as far as possible from mains and ground wires. Do not bundle them together.

Configuration through DIP – switches

Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - fig

SW1 MS/TP – Device configuration and BACnet MS/TP baudrate

Valor binario Binary value b1…b5Interruptores SwitchesDescription
 1234 5 6 7 8
0xxxxxxxIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1xxxxxxxFollower (Default value) (valor por defecto – default value)
1xxxxxxx­ Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconxxxxxxxHeader
x0xxxxxxxIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1xxxxxxNot used
x0xxxxxxx­ Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconxxxxxxNot used
xx0xxxxxxxIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1xxxxxNot used
xx1xxxxxxx­ Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconxxxxxNot used
xxx0xxxxxxxIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1xxxxNot used
xxx1xxxxxxx­ Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconxxxxNot used
xxxx0xxxxxxxIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1xxxLow Power Mode
xxxx1xxxxxxx­ Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconxxxHigh Performance mode (valor por defecto – default value)
Valor binario Binary value B6…b8Interruptores SwitchesDescription
12345678
xxxxx000xxxxxIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Autobaudrate (valor por defecto – default value)
xxxxx100xxxxx­Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon19600 bps
xxxxx010xxxxxIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1­Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon119200 bps
xxxxx110xxxxx­Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon­Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon138400 bps
xxxxx001xxxxxIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1­Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon57600 bps
xxxxx101xxxxx­Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1­Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon76800 bps
xxxxx011xxxxxIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1­Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon­Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon115200 bps
xxxxx111xxxxx­Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon­Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon­Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconAutobaudrate

SW2 – MS/TP MAC address and temperature magnitude (ºC/ºF)

Binary value
b0…b7

Interruptores Switches

MAC address Description
12345678
0000000xIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1x0
1000000x­Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1x1
0100000xIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1x2
1100000x­Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1x3
….

­ ……………..

……..
1011111xIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconx125
0111111x­  Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconx126
1111111xIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconx127
xxxxxxx0xxxxxxxIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Temperature values in Bacnet are represented in Celsius degrees
(valor por defecto – default value)
xxxxxxx1xxxxxxxIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconTemperature values in Bacnet are represented in Fahrenheit degrees

* NOTE: The MAC address selected might affect on the Device Instance. Check the manual for more information.

SW3 – Polarization and termination

Valor binario Binary value B0…b2Interruptores Switches Description
 12
0xxIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1xxEIA485 bus without termination resistor. The gateway is not at one end of the EIA485 bus (valor por defecto – default value)
1xx­Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconxx120 Ω termination resistor active. The gateway is at one end of the EIA485 bus
x00xIntesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon1No bus polarization (valor por defecto – default value)
x11x­Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - icon­Intesis INBACTOS001R100 Digital systems to BACnet MSTP Interface - iconBus polarization active

LED information

LEDBehaviourDescription
L1
(red)
ON SteadyBACnet MS/TP link
BlinkingActivity on the BACnet MS/TP bus
OFFBACnet MS/TP link not performed
LED Behaviour Description
L2
(green)
ON SteadyCommunication error
BlinkingAC Error
FlashingCommunication OK
LED Behaviour Description
L3
(yellow)
ON SteadyExternal power supply connected
OFFExternal PS not connected

NOTE: Check the manual for more information about other LED operation modes.
The user manual is available at: https://intesis.com/products/ac-interfaces/toshiba-gateways/toshiba-bacnet-vrf-to-rc-bac-1l
WEE-Disposal-icon.png This marking on the product, accessories, packaging or literature (manual) indicates that the product contains electronic parts and they must be properly disposed of by following the instructions at https://intesis.com/weee-regulation

Doc.r.1.0
© HMS Industrial Networks S.L.U – All rights reserved
This information is subject to change without notice
Intesis - logoURL https://www.intesis.com

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals