Stiebel Eltron Modbus Tcp/ip Software Extension For Internet Service Gateway User Guide

STIEBEL ELTRON Modbus TCP/IP Software Extension for Internet Service Gateway User Guide

General information

These instructions are intended for qualified contractors.

Note
Read these instructions carefully before using the appliance and retain them for future reference.
Pass on the instructions to a new user if required.

Other symbols in this documentation

Note
General information is identified by the adjacent symbol.

  • Read these texts carefully.

Symbol:  Meaning

Material losses (appliance damage, consequential losses and environmental pollution)

  • This symbol indicates that you have to do something. The action you need to take is described step by step.

Relevant appliances

  • ISG web, part number 229336
  • ISG plus, part number 233493

Brand conformity

Note
This software can only be operated in conjunction with devices and software from the same manufacturer.

  • Never use this software in conjunction with third party software or devices.

Relevant documents

Operating and installation instructions Internet Service Gateway ISG web

Operating and installation instructions for the connected integral ventilation unit or the heat pump

Conditions of use for the ISG web

Contract conditions for the purchase of chargeable software extensions with additional functions for the ISG web

Safety

Intended use

Material losses
Incorrect use can result in damage to the connected integral ventilation unit or heat pump.

Observation of these instructions and of instructions for any accessories used is also  part of the correct use of this appliance.

System requirements

  • ISG web with the Basic service package
  • Compatible device, see “Compatibility overview”
  • Building management system with Modbus TCP/IP Master
  • IP network connection to the ISG and to the building management system

General safety instructions

We guarantee trouble-free function and operational reliability only
if the original accessories intended for the appliance are used.

Instructions, standards and regulations

Note
Observe all applicable national and regional regulations and instructions.

Product description

This product is a software interface for the ISG for building automation. The ISG is a gateway for controlling integral ventilation units and heat pumps. Components required for operating the connected integral ventilation unit or the connected heat pump (e.g. sensors) cannot be replaced by Modbus components.

The following functions are available with the Modbus software:

  • Selecting operating modes
  • Selecting set temperatures
  • Switching fan levels
  • Selecting set DHW temperature
  • Calling up current values and system data

Settings

The ISG uses the following 16-bit register:

“Read input register”

  • Objects are read-only
  • Calling up registers via function code 04 (“Read input registers”)
    Example: To read register 30501, address 501 is brought up with function code 04.

“Read/write holding register”

  • Objects are read-writable
  • Calling up registers via function code 03 (“Read holding registers”)
  • Write via function code 06 (“Write single register”) or function code 16 (“Write multiple registers”)

The substitute value “32768 (0x8000H)” is issued for unavailable objects.

Some status objects are bit-coded (B0 – Bx). The respective corresponding status information is documented under “Coding” (e.g. compressor running yes/no).

A distinction is drawn here between the following types of data:

Data typeValue rangeMultiplier for readingMultiplier for writingSignedStep size 1Step size 5
23276.8 to 3276.70.110Yes0.10.5
60 to 6553511No11
7-327.68 to 327.670.01100Yes0.010.05
80 to 25511515
  • Transferred value x multiplier = data value
  • Example – writing: To write a temperature of 20.3 °C, write value 203 (factor 10) to the register.
  • Example – reading: The value 203 called up means 20.3 °C (203 x 0.1 = 20.3)

IP configuration

Note
Refer to the ISG operating and installation instructions.

You can perform the IP configuration in the SERVICEWELT via the “Profile” tab:

ISG: 192.168.0.126 (standard IP address)
TCP port: 502
Slave ID: 1 (permanent)

Note
The ISG retains its standard IP address when directly connected to your computer. If connected via a router, the DHCP server automatically assigns a different IP address to the ISG.

Compatibility overview

Note
In parameter configuration, first select the appliance type so that the respective corresponding parameters can be configured.

  • Follow the operating and installation instructions for the ISG when connecting the heat pump or the integral ventilation unit to the ISG.

Note
Generally, all listed appliances are supported.

  • Not every object type is available with every appliance.
  • The substitute value “32768 (0x8000H)” is issued for unavailable objects.

You can find an overview of compatible heat pumps / integral ventilation units on our website.

https://www.stiebel-eltron.de/de/home/service/smart-home/kompatibilitaetslisten.html

Incompatibility

  • The ISG must not be operated together with a DCo-active GSM on the same CAN bus. This can result in errors in communication with the WPM.
  • The Modbus TCP/IP software interface cannot be combined with other ISG software interfaces (Exception: Read-only access is possible at the same time as using the EMI energy management software extension).

Troubleshooting

Checking the software version

  • Check whether the Modbus software is installed on the ISG.
  • When a WPM is connected, you will find the corresponding menu in the SERVICEWELT under: DIAGNOSIS → SYSTEM → ISG.
  • When an integral ventilation unit is connected, you will find the corresponding menu in the SERVICEWELT under: DIAGNOSIS → BUS SUBSCRIBER → ISG.
  • If the “Modbus TCP/IP” interface is not listed, you need to update to the latest ISG firmware.
  • Contact STIEBEL ELTRON service department.
  • Visit our homepage for more information.

Checking the data transfer:

  • Using a standard data object (e.g. outside temperature), check the data transfer via Modbus. Compare the transferred value with the value shown in the controller display

Note
ISG addresses are 1 based.
Allowance must be made for an offset of around 1, depending on the configuration.

Acknowledging faults:

  • Faults in the heating system are indicated by the fault status (Modbus addresses: 2504, 2002).
  • For safety reasons, faults can only be acknowledged via the SERVICEWELT user interface.

If you encounter problems with the product and cannot remedy the cause, contact an IT contractor.

Modbus system values for heat pumps with WPM

Note
Generally, all listed appliances are supported.

  • Not every object type is available with every appliance.
  • The substitute value “32768 (0x8000H)” is issued for unavailable objects.
  • ISG addresses are 1 based.

Note
Values in the “Min. value” and “Max. value” columns will vary according to the connected heat pump, and may deviate from the indicated values.

Block 1: System values (Read input register)

Modbus addressObject designationWPMsys- temWPM 3WPM 3iCommentsMin. valueMax. valueData typeUnitWrite/ read (w/r)
501ACTUAL TEMPERATURE FE7xxx2°Cr
502SET TEMPERATURE FE7xxx2°Cr
503ACTUAL TEMPERATURE FEKxx2°Cr
504SET TEMPERATURE FEKxx2°Cr
505RELATIVE HUMIDITYxx2%r
506DEW POINT TEMPERATURExx-40302°Cr
507OUTSIDE TEMPERATURExxx-60802°Cr
508ACTUAL TEMPERATURE HK 1xxx0402°Cr
509SET TEMPERATURE HK 1x0652°Cr
510SET TEMPERATURE HK 1xx0402°Cr
511ACTUAL TEMPERATURE HK 2xxx0902°Cr
512SET TEMPERATURE HK 2xxx0652°Cr
513ACTUAL FLOW TEMPERATURE WPxxxMFG, if available2°Cr
514ACTUAL FLOW TEMPERATURE NHZxxxMFG, if available2°Cr
515ACTUAL FLOW TEMPERATURExxx2°Cr
516ACTUAL RETURN TEMPERATURExxx0902°Cr
517SET FIXED TEMPERATURExxx20502°Cr
518ACTUAL BUFFER  TEMPERATURExxx0902°Cr
519SET BUFFER TEMPERATURExxx2°Cr
520HEATING PRESSURExxxMFG, if available7barr
521FLOW RATExxxMFG, if available2l/minr
522ACTUAL TEMPERATURExxxDHW10652°Cr
523SET TEMPERATURExxxDHW10652°Cr
524ACTUAL TEMPERATURE  FANxxxCooling2Kr
525SET TEMPERATURE FANxxxCooling7252Kr
526ACTUAL TEMPERATURE AREAxxxCooling2Kr
527SET TEMPERATURE AREAxxxCooling2Kr
528COLLECTOR TEMPERATURExSolar thermal0902°Cr
529CYLINDER TEMPERATURExSolar thermal0902°Cr
530RUNTIMExSolar thermal6hr
531ACTUAL TEMPERATURExxExternal heat source10902°Cr
532SET TEMPERATURExxExternal heat source2Kr
533APPLICATION LIMIT HZGxxxLower heating limit-40402°Cr
534APPLICATION LIMIT WWxxxLower DHW limit-40402°Cr
535RUNTIMExxExternal heat source6hr
536SOURCE TEMPERATURExxx2°Cr
537MIN SOURCE TEMPERATURExxx-10102°Cr
538SOURCE PRESSURExxx7barr
539HOT GAS TEMPERATUREx2°Cr
540HIGH PRESSUREx2barr
541LOW PRESSUREx2barr
542RETURN TEMPERATURExxHeat pump 12°Cr
543FLOW TEMPERATURExxHeat pump 12°Cr
544HOT GAS TEMPERATURExxHeat pump 12°Cr
545LOW PRESSURExxHeat pump 17barr
546MEAN PRESSURExxHeat pump 17barr
547HIGH PRESSURExxHeat pump 17barr
548WP WATER FLOW RATExxHeat pump 12l/minr
549RETURN TEMPERATURExxHeat pump 22°Cr
550FLOW TEMPERATURExxHeat pump 22°Cr
551HOT GAS TEMPERATURExxHeat pump 22°Cr
552LOW PRESSURExxHeat pump 27barr
553MEAN PRESSURExxHeat pump 27barr
554HIGH PRESSURExxHeat pump 27barr
555WP WATER FLOW RATExxHeat pump 22l/minr
556RETURN TEMPERATURExxHeat pump 32°Cr
557FLOW TEMPERATURExxHeat pump 32°Cr
558HOT GAS TEMPERATURExxHeat pump 32°Cr
559LOW PRESSURExxHeat pump 37barr
560MEAN PRESSURExxHeat pump 37barr
561HIGH PRESSURExxHeat pump 37barr
562WP WATER FLOW RATExxHeat pump 32l/minr
563RETURN TEMPERATURExxHeat pump 42°Cr
564FLOW TEMPERATURExxHeat pump 42°Cr
565HOT GAS TEMPERATURExxHeat pump 42°Cr
566LOW PRESSURExxHeat pump 47barr
567MEAN PRESSURExxHeat pump 47barr
568HIGH PRESSURExxHeat pump 47barr
569WP WATER FLOW RATExxHeat pump 42l/minr
570RETURN TEMPERATURExxHeat pump 52°Cr
571FLOW TEMPERATURExxHeat pump 52°Cr
572HOT GAS TEMPERATURExxHeat pump 52°Cr
573LOW PRESSURExxHeat pump 57barr
574MEAN PRESSURExxHeat pump 57barr
575HIGH PRESSURExxHeat pump 57barr
576WP WATER FLOW RATExxHeat pump 52l/minr
577RETURN TEMPERATURExxHeat pump 62°Cr
578FLOW TEMPERATURExxHeat pump 62°Cr
579HOT GAS TEMPERATURExxHeat pump 62°Cr
580LOW PRESSURExxHeat pump 67barr
581MEAN PRESSURExxHeat pump 67barr
582HIGH PRESSURExxHeat pump 67barr
583WP WATER FLOW RATExxHeat pump 62l/minr
584              ACTUAL TEMPERATURExRoom temperature, heating circuit 1 2°Cr
 585             SET TEMPERATURExRoom temperature, heating circuit 1 2°Cr
586             RELATIVE HUMIDITYxHeating circuit 12%r
587             DEW POINT TEMPERATURExHeating circuit 12°Cr
 588             ACTUAL TEMPERATURExRoom temperature, heating circuit 22°Cr
 589             SET TEMPERATURExRoom temperature, heating circuit 2 2°Cr
590             RELATIVE HUMIDITYxHeating circuit 22%r
591             DEW POINT TEMPERATURExHeating circuit 22°Cr
 592             ACTUAL TEMPERATURExRoom temperature, heating circuit 3 2 °C r
 593SET TEMPERATURExRoom temperature, heating circuit 3 2 °C r
594RELATIVE HUMIDITYxHeating circuit 32%r
595DEW POINT TEMPERATURExHeating circuit 32°Cr
 596ACTUAL TEMPERATURExRoom temperature, heating circuit 42°Cr
 597             SET TEMPERATURE xRoom temperature, heating circuit 4 2 °C r
598             RELATIVE HUMIDITYxHeating circuit 42%r
599             DEW POINT TEMPERATURExHeating circuit 42°Cr
 600             ACTUAL TEMPERATURE xRoom temperature, heating circuit 5 2 °C r
 601             SET TEMPERATURE xRoom temperature, heating circuit 5 2 °C r
602             RELATIVE HUMIDITYxHeating circuit 52%r
603             DEW POINT TEMPERATURExHeating circuit 52°Cr
 604             SET TEMPERATURE xRoom temperature, cooling circuit 1 2 °C r
 605             SET TEMPERATURE xRoom temperature, cooling circuit 2 2 °C r
 606             SET TEMPERATURE xRoom temperature, cooling circuit 3 2 °C r
 607             SET TEMPERATURE xemperature, cooling circuit4 2 °C r
 608 SET TEMPERATURE xoom temperature, cooling circuit 5 2 °Cr

 

 