IL01203004Z
NZMB Thermal Magnetic Circuit Breaker
Instruction Manual
NZMB(C)(N)(S)(H)1(-4)-A(M)(S)…
NZMB(N)1-A(AF)…-NA
NZMB(N)1-S…-CNA
(P)N1-… NS1-…-NA
NZMB Thermal Magnetic Circuit Breaker
Electric current! Danger to life!
Installation, commissioning and maintenance work must be carried out by qualified personnel only.
Minimum clearance/direction of blow-out

Terminals

| 1 x 10 – 70 mm² | 1 x 10 – 16mm² | ≧ 2 x 9 x 0.8 mm (≧ 2 x 0.35“ x 0.03“) |
| 2 x 6 – 25 mm² | 2 x 6 – 16 mm² | |
| 1 x AWG 4 – AWG 2/0 | 1 x AWG 12 – AWG 6 | |
| 2 x AWG 10 – AWG 4 | 2 x AWG 10 – AWG 6 |
UL/CSA = Cu only, Ampacity per 75° C Table.
Wiring terminations circuit breaker type NZM…1…-NA (CNA)
Wiring terminations molded case switch type N(S)1…-NA
| Connector type | Wire size | Wire 75° C | Max. A-Rating | Tightening-Torque |
| 1)NZM1-XKC | 1 x AWG 2/0 – 12 2xAWG 4 -10 | Cu only | 125 | 9 Nm (80 lb-in) 6 Nm (53 lb-in) (AWG 8 – 12) |
| NZM1-XKA | 1 x AWG 3/0 – 6 | Cu only | 125 | 15 Nm (133 lb-in) |
| NZM1-XKS | 1 x AWG 2/0 – 12 2xAWG 4 -10 | Cu only | 125 | 9 Nm (80 lb-in) |
| 2)Integrated Auxiliary Terminal | 1 x AWG 12 – 18 | Cu only | 1.2 Nm (11 lb-in) |
- Connector Type NZM1-XKC supplied standard on all NZM1 circuit breakers and switches.
- Integrated Auxiliary Terminal on Connector Type NZM1-XKA only.

Settings

Note: On certain models with UL/CSA labeling the thermal trip setting is fixed and only the magnetic trip (instantaneous) setting is adjustable.
Accessories

Notes on mounting and wiring Auxiliary Switches for UL/CSA labeled models:
- M22-K(10)(01) have screw terminals. M22-CK(10)(01)(20)(02)(11) have clamp terminals.
- Switch modules are snapped into place at the locations shown in the diagrams that follow.
- Switches will function as either “standard” or “trip/alarm” contacts depending on their mounting location.
- Location “HIN” refers to standard operation. Location “HIA” refers to “trip/alarm” operation.
- Follow the numbering and wiring scheme provided above depending on the contact location and function. (N.O. or N.C.)
- Permissible contact configuration: 1 HIA and/or 2 HIN.
Note:
After mounting of the M22… switch is complete, check off the appropriate box on the auxiliary switch label provided on the side of the breaker or switch.
-NA -CNA (UL/CSA)
| Ith = Ie | |
| Ue (V) | Ie (A) |
| 600 AC | 5 A |
| 250 DC | 1 A |
Pilot Duty Ratings: B 600, Q 300 Above 300 V AC Same polarity


Test



Eaton Electric Ltd., P.O. Box 554, Abbey Park, Southampton Road, Titchfield, PO14 4QA, United Kingdom
USA:
Eaton.com/eatoncare
+1 877-386-2273
Eaton.com/aftersales
07/22 IL01203004Z
Eaton.com/recycling
© 2002 Eaton Industries GmbH

















