Neptronic At080-30 Actuator Instruction Manual

Neptronic At080-30 Actuator Instruction Manual

neptronic - logo

AT080-30 Actuator
Actuator Specification
Instruction Manual

AT080-30 Actuator

neptronic AT080-30 ActuatorFeature:

• Variable running time.AT000
• Manuel override.AT020
• Maintenance free.AT060
• Fail safe by Enerdrive System (on models 060 & 080).AT080
• Auxiliary switches. (on models 020 & 080).AT000-30
AT020-30
AT060-30
AT080-30
Technical DataAT000AT020AT060AT080AT000-30AT020-30AT060-30AT080-30
Auxiliary switchesNoYes(2)NoYes(2)NoYes(2)NoYes(2)
FeedbackNoNoNoNoNoNoNoNo
Fail safe – EnerdriveNoYesNoYes
Power consumption6 VA20VA Peak, 6VA6 VA20VA Peak, 6VA
Control signal3 wire / 2 position,
3 wire / 3 point floating
2 wire / 2 position.
4 wire / 3 point floating
3 wire / 2 position.
3 wire / 3 point floating
2 wire / 2 position.
4 wire / 3 point floating
Running time60 sec force dependant30 sec force dependant
Force100 lb. [450 N] at rated voltage
Power supply22 to 26 VAC or 28 to 32 VDC
Electrical connection18 AWG [0.8 mm2] minimum
Inlet bushing2 inlet bushing of 5/8 in [15.9 mm] & 7/8 in [22.2 mm]
Maximum Stroke0.5 in [12.7mm]
DirectionReversible. normally open or normally close (factory set with normally close direction)
Ambient temperature0°F to +122°F [-18°C to +50°C]
Storage temperature-22°F to +122°F [-30°C to +50°C]
Relative Humidity5 to 95 % non condensing.
Weight2 lbs. [0.9 kg]
Warning: Do not use automatic screw driver on manual override

Dimensions neptronic AT080-30 Actuator - fig

Dimension InchesMetric (mm) 
A5.93150.6
B4.8121.9
C3.691.4

Caution
We strongly recommend that all neptronic® products be wired to a separate transformer and that transformer shall service only neptronic® products. This precaution will prevent interference with, and/or possible damage to incompatible equipment.
When multiple actuators are wired on a single transformer, polarity must be observed. Long wiring runs create voltage drop which may affect the actuator performance.

AT000/020/060/080
AT000-30/020-30/060-30/080-30

Mechanical installation

Mounting of the actuator on valve

Correct mountingneptronic AT080-30 Actuator - fig 1Non Correct mountingneptronic AT080-30 Actuator - fig 21. Screw completely the valve shaft (C) unto the coupling of the actuator (A).
2. Unscrew the coupling (A) for ½ of turn in order to leave a functional play.
3. Screw the counter nut (B).
Warning: Do not over tight coupling of the actuator on the shaft of the valve.

Mounting of the actuated valve on system

Vertical mounting

neptronic AT080-30 Actuator - fig 3

Horizontal mounting

neptronic AT080-30 Actuator - fig 4

1. Pay attention to system particularity; be sure that the
expansions, contractions of the system and its medium as
well as operating pressures are within the tolerances.
2. When plumbing, the motorized valve should be situated in
an easily accessible place and sufficient space should be
allowed for the removal of the actuator.
3. To prevent moisture from collecting in the motor casing, install the motorized valve such that the actuator is
superior to the valve, at 20-30º / at vertical. Avoid mounting the valve so that the valve stem is below
horizontal.

Wiring Diagrams

Models AT000 & 020
AT000-30 & 020-30
Models AT060 & 080
AT060-30 & 080-30
3 wire / 2 position (ON-OFF)neptronic AT080-30 Actuator - fig 52 wire / 2 position (ON-OFF)neptronic AT080-30 Actuator - fig 8
3 wire / 3 point floatingneptronic AT080-30 Actuator - fig 64 wire / 3 point floatingneptronic AT080-30 Actuator - fig 9
PC Boardneptronic AT080-30 Actuator - fig 7Dip switch settingsneptronic AT080-30 Actuator - fig 10

*On AT model:
When switch #3 is “ON”, the running time will be 60 sec. neptronic AT080-30 Actuator - icon

LISTED TEMPERATURE REGULATING EQUIPMENT 41 X 9
CLASS 2 CIRCUIT

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals