Pioneer Quantum Series Mini Split Systems Installation Guide

Pioneer Quantum Series Mini Split Systems Installation Guide

PIONEER-LOGO

Pioneer Quantum Series Mini Split Systems

Pioneer-Quantum-Series-Mini-Split-Systems-PRODUCT-IMAGE

Product Information

The 24 Volt Interface Adapter is an accessory that makes any Pioneer Quantum Series mini split system compatible with 24V analog heat pump thermostats. It is designed to be installed indoors in an area free from drips and moisture. The dimensions of the interface kit are as follows:

  • Length: 283mm (11.1 inches)
  • Width: 220mm (8.7 inches)
  • Height: 63mm (2.5 inches)

It is important to note that the interface kit should not be installed near flammable liquids or gases, as it can create a fire hazard.

Product Usage Instructions

  1. Before starting the installation, ensure that you have all the necessary parts and tools as listed in Tables 1 and 2 respectively.
  2. Select a suitable installation location for the 24 Volt Interface Adapter.
  3. Remove the cover of the interface kit by unscrewing the four screws.
  4. Mount the back plate of the interface kit vertically on the wall using three screws and anchors.
  5. Wire the connections according to the specified wiring diagram (Fig. 3).
  6. Cover the interface kit with the lid and secure it with the locking screw.

Please refer to the product manual for more detailed information on system configuration, application scenarios, and connection wiring specifications.

Read this manual carefully before installing or operating your new air conditioning unit. Make sure to save this manual for future reference.

WARNING

  • Wires must be properly sized according to the NEC/NFPA 70, CEC and all prevailing codes, ordinances and standards.
  • All conductors must be installed with a strain relief eliminating stress on the wire following installation which may result in wire damage and/or overheating with a potential for fire. Installation must be performed in accordance with the  requirement of NEC and CEC by authorized personnel only.
  • All wiring to be rated for the control box amperage rating.
  • All wiring installed to meet general industry standards and practices,
  • Do not install adapter near flammable liquids or gases.
  • Do not operate the unit with wet hands, as this could lead to electrical shock.

CAUTION

  • When connecting with RS 485 communication to the outdoor unit, shielded wire must be used and grounded at one end only.
  • When using shielded wire the cable should be grounded at one end to reduce EMI.
  • T1 sensor cable shall not exceed 23′ (7 m).

Read this manual carefully before installing or operating your new air conditioning unit.Make sure to save this manual for future reference.

Wall-Mounted 24V INTERFACE KIT Installation

Wear appropriate personal protection equipment (PPE) when installing or servicing.

24V INTERFACE KIT DimensionsPioneer-Quantum-Series-Mini-Split-Systems-01

This interface must be installed indoors in an area free from drips and moisture.

Pioneer-Quantum-Series-Mini-Split-Systems-02General installation instructions Location and clearances

Preparation Before Installation

  1. Ensure you have the following parts
    NoNameQuantityRemarks
    1Control box1 
    2Screws3M4*20 (For mounting on the wall)
    3Anchors3For mounting on the wall
    4The connective wires group2For connecting the sensor
    55m connective wires group1 
  2. Prepare the following tools
    No                                Name               Quantity
    1Switch box1
    2Wiring tube (insulating sleeve and tightening screw)1
  3. Select installation location
    DO NOT install the 24V INTERFACE KIT near flammable liquids or gases such as gasoline or hydrogen sulfide. Doing so creates a fire hazard.

Installation Method

  1. Remove the cover of 24V INTERFACE KIT Remove the four screws of 24V INTERFACE KIT with a screwdriver or similar tool. Along the hem rotating separation lifted the lid.Pioneer-Quantum-Series-Mini-Split-Systems-03Minimum free space required around the kit is 7″ (180 mm).
  2. Mount the back plate of the 24V INTERFACE KITPioneer-Quantum-Series-Mini-Split-Systems-04Mount 24V INTERFACE KIT vertically, and folding in on, fasten the back plate to the wall with 3 screws (M4x20) and anchors.
    NOTE:
    Place the unit on a flat surface. Be careful not to distort the back plate of the 24V INTERFACE KIT by over tightening the screws.
    • When installed vertically, the direction of the arrow must be up.
  3. Wiring.
  4. Cover the 24V INTERFACE KIT lid, locking screw.Pioneer-Quantum-Series-Mini-Split-Systems-05

System Configuration
NOTE:
Thermostat should be configured for use with a conventional system.
The remote controller, wiring controller, central controller and WIFI can not be used with this control box at the same time. Only the Swing and LED furcation can be used.

Connection wiring specification

Connection wiringOutdoor 1,2,3Indoor 1,2,3 

R,C

Y/W/G/G1/G2/ G3/Dry
 

Size

Refer to outdoor connecting wires sizeRefer to indoor connecting wires size 

18AWG

(minimum)

 

24AWG

(minimum)

Application
* This system is designed for operation with standard 24 vac HVAC thermostats.
* Wifi standard configuration HVAC thermostats may be used such as NEST, Ecobee, Honeywell, etc.

SYSTEM CONFIGURATION SCENARIOS
Four application scenarios°

Scenario No. 1:
Current loop (L1/L2/S or 1/2/3) communication inverter outdoor unit match with other conventional brand 24V indoor unit;

Match with following outdoor units :

  • Wall Mounted (Sizes 9K~36K) Cassette (Sizes 9K~24K)
  • Ducted (Sizes 9K~24K)
  • Console (Sizes 9K~12K)
  • Floor ceiling (Sizes 18K-24K)

Pioneer-Quantum-Series-Mini-Split-Systems-06

NOTE:

  • T1(Room temperature) sensor should be located in the air inlet side.
  • Must remove the TXV or other metering device from the indoor unit.

Pioneer-Quantum-Series-Mini-Split-Systems-07

NOTE:

  • T1(Room temperature) sensor should be located in the air inlet side.
  • Must remove the TXV or other metering device from the indoor unit.
  • If the indoor unit already with a 24V transformer , removing away the transformer from the interface or disconnect the transformer of the interface.

Scenario No. 2:
485 (P Q)or( S1 S2) communication inverter outdoor unit match with conventional other brand 24V indoor unit;

Match with following outdoor units :

  • Cassette (Sizes 36K~48K) Ducted (Sizes 36K~60K) Floor ceiling (Sizes 36K-60K)

Pioneer-Quantum-Series-Mini-Split-Systems-08

NOTE:

  •  T1(Room temperature) sensor should be located in the air inlet side.
    Must remove the TXV or other throttl-ing device from the indoor.

Pioneer-Quantum-Series-Mini-Split-Systems-09

NOTE:

  •  T1(Room temperature) sensor should be located in the air inlet side.
  • Must remove the TXV or other throttl-ing device from the indoor.
  • If the indoor unit already has a 24V transformer, removing the transformer from the interface or disconnect the transformer of the interface.

Scenario No. 3:
Current loop (L1 L2 S or 1 2 3) inverter outdoor unit match with current loop inverter indoor unit;

Match the following indoor units with the corresponding compatible SINGLE ZONE and multi zone outdoor units:

  • Wall Mounted (Sizes 9K~36K)
  • Cassette (Sizes 9K~24K)
  • Ducted (Sizes 9K~24K)
  • Console (Sizes 9K~12K)
  • Floor ceiling (Sizes 18K-24K)
  • Multi system (2 zone, 3 zone, 4 zone, 5 zone)

Pioneer-Quantum-Series-Mini-Split-Systems-10

NOTE:

  • Please connect thermostat G to 24V interface G as default.
  • Make sure the power supply is correct.
  • For Wall Mounted unit ,the up-down swing louver and the display on/off funcation is available by the wireless remote controller.
  • Remove 24V control box T1 sensor when match with indoor unit,which has T1 sensor.

Scenario No. 4:
485 (P Q)or( S1 S2)inverter outdoor unit match with 485 inverter indoor unit ;

Match the following indoor units with the corresponding compatible SINGLE ZONE outdoor units:

  • Cassette (Sizes 36K~48K)
  • Ducted (Sizes 36K~60K)
  • Floor ceiling (Sizes 36K-60K)

Pioneer-Quantum-Series-Mini-Split-Systems-11NOTE:

  • Please connect thermostat G to 24V interface G as default.
  • Make sure the power supply is correct.
  • Remove 24V control box T1 sensor when match with indoor unit, which has T1 sensor.

Key Considerations

  • The following steps should be taken when using this device with a conventional central air conditioning unit:
  • Indoor coil metering device must be removed. 24V transformer in the interface module must be disconnected.
  • Refrigerant charge amount may need to be adjusted, depending on the pipe size and length, see outdoor recharge instruction. The maximum air flow should not exceed 400 CFM/Ton.
  • When the indoor air handler or furnace has its own 24 vac transformer, you must disconnect all four wires of the kit transformer.

Pioneer-Quantum-Series-Mini-Split-Systems-12 Suction and liquid refrigerant lines must be properly insulated to prevent condensation and energy loss.

  •  You must remove the expansion device from an indoor evaporator coil as the refrigerant is controlled by a metering device in the outdoor unit.
  • The following steps should be taken when using this device with a Hi wall (9K-36K Btu/hr) Cassette, Console, Duct, Floor Ceiling (9K – 24K Btu/hr).
  • Power switch on new board is changed. Indoor unit power switch setting, ENC-1 must be changed to the proper motor wattage: Eg. 36K = 8 48K = 9

Control Logic
Connector

ConnectorPurpose
YCooling
WHeating
GFan- Auto speed
AUX/DRYAux-Heat/Dry

Mode setting

YWGAux/DrySetting mode
X**Cooling
X*XHeating (without aux-heater)
X*Heating (with aux-heater)
XXXFan only
**OFF
XXXXOFF
XX*√ (Dry)Dry
XX*√(AUX)Emergency heating

Fan speed setting

Unit ON/OFF             G                   Setting fan speed
XAuto fan speed
Auto fan speed
XXFan OFF

 

ON
XOFF
*ON or OFF

DIP Switch Definitions
DIP SWITCHES CONFIGURATION
The 24V INTERFACE KIT must be configured to operate properly with the system components with which it is installed. To successfully configure the system move the Dip Switches to match the components and functions used.

Pioneer-Quantum-Series-Mini-Split-Systems-13

Dip Switch 1-1
Used to turn ON or OFF the diagnostic code display LED on the control board of the 24V Interface Kit.

SW1-1ResultNote
ONDisplay on 
OFFDisplay offDefault

Pioneer-Quantum-Series-Mini-Split-Systems-14

Dip Switch 1-2
Used for selection of the indoor unit type.

SW1-2ResultNote
ONSets – Both Ductless Indoor and Outdoor Units 
OFFOutdoor only
—– Compatible with other fix speed 24V control indoor (Wall Hung/ Pancake etc.).

Note:

  1. Need to remove the indoor unit throttle (piston/ TXV/ orifice);
  2. Indoor fan may not stop during the defrost.
 

 

 

Default

NOTE: If this control box is matched with other brand indoor unit, you must set OFF.

Dip Switch 2-1
Used for selection of the system: Cooling Only or Heat Pump.

SW2-1ResultNote
ONCooling only 
OFFHeat pumpDefault

Dip Switch 2-2
Used for freeze protection of the indoor coil.

SW2-2ResultNote
ONFan do not stop 
OFFFan will stop if the indoor coil temperature is lowDefault

NOTE : Applicable only to Ductless Style Indoor (scenario 3 and 4) Heat Pump units in Heating Mode.

Dip Switch 3-1
Dry is used for thermostats with a Dry Function output. An auxiliary heater is used on the Ducted Style Indoor Units (scenario 3 and 4) to control a secondary Heat Source.

SW3-1ResultNote
ONDry 
OFFAux-heaterDefault

Dip Switch 3-2
Used to increase the compressor frequency in case the set point has not been reached after 1 hour or 30min of operation.

SW3-2ResultNote
ON1h 
OFF30minDefault

Dip Switch 4-1

SW4-1Note
OFFDefault

For factory test only.

Dip Switch 4-2

SW4-2Note
OFFDefault

For factory test only.

Error Codes

Display               Malfunction & protection indication
E0Indoor EEPROM error
E2Cross-zero detection error
E3Indoor fan speed malfunction
E4Indoor room temperature sen sor error
E5Evaporator coil temperature sensor error
ECRefrigerant leak detection system malfunction
F0Current overload protection
F1Outdoor ambient temperature sensor (T4 ) malfunction
F2Condenser coil temperature sensor (T3) malfunction
F3Condenser coil temperature sensor (T5) malfunction
F4Outdoor unit EEPROM parameter error
F5Outdoor fan speed has been out of control
F6T2b sensor error
P0Inverter module (IPM) malfunction
P1Over-voltage or under-voltage protection
P2Compressor top high temperature protection (OLP)
P3Low ambient temperature cut off in heating
P4Compressor drive malfunction
P6Compressor low-pressure protection
00Module boot mode and indoor running mode for power off
INModule and indoor unit communication malfunction
OUModule and outdoor unit communication malfunction

Wiring Diagram

Pioneer-Quantum-Series-Mini-Split-Systems-15

The design and specifications are subject to change without prior notice for product improvement. Consult with the sales agency or manufacturer for details.

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals