Daikin R32 Split System Air Conditioners Installation Guide

Daikin R32 Split System Air Conditioners Installation Guide

DAIKIN R32 Split System Air Conditioners - logo

Installation manual
R32 Split system air conditioners

DAIKIN R32 Split System Air Conditioners -Conditio

RXJ20M5V1BRXJ20M5V1B9
RXJ25M5V1BRXJ25M5V1B9
RXJ35M5V1BRXJ35M5V1B9
RXA20A5V1BRXA20A5V1B9
RXA25A5V1BRXA25A5V1B9
RXA35A5V1BRXA35A5V1B9
RXM20R5V1BRXM20R5V1B9
RXM25R5V1BRXM25R5V1B9
RXM35R5V1BRXM35R5V1B9
ARXM25R5V1BARXM25R5V1B9
ARXM35R5V1BARXM35R5V1B9
Contents hide

About the documentation

About this document

Target audience
Authorised installers

warning 2WARNING
Make sure installation, servicing, maintenance, repair and applied materials follow the instructions from Daikin and, in addition, comply with applicable legislation and are performed by qualified persons only. In Europe and areas where IEC standards apply, EN/IEC 60335-2-40 is the applicable standard.

DAIKIN R32 Split System Air Conditioners - NFORMATION INFORMATION
This document only describes installation instructions specific to the outdoor unit. For installation of the indoor unit (mounting the indoor unit, connecting the refrigerant piping to the indoor unit, connecting the electrical wiring to the indoor unit …), see the installation manual of the indoor unit.

Documentation set
This document is part of a documentation set. The complete set consists of:

▪ General safety precautions:
▪ Safety instructions that you MUST read before installing
▪ Format: Paper (in the box of the outdoor unit)
▪ Outdoor unit installation manual:
▪ Installation instructions
▪ Format: Paper (in the box of the outdoor unit)
▪ Installer reference guide:
▪ Preparation of the installation, reference data,…
▪ Format: Digital files on http://www.daikineurope.com/support-and-manuals/product-information/

Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages are translations.
Technical engineering data

  • A subset of the latest technical data is available on the regional Daikin website (publicly accessible).
  • The full set of latest technical data is available on the Daikin Business Portal (authentication required).

Specific installer safety instructions

Always observe the following safety instructions and regulations.
Unit installation (see “4 Unit installation” [4 7])

warning 2WARNING
Installation shall be done by an installer, the choice of materials and installation shall comply with the applicable legislation. In Europe, EN378 is the applicable standard.

Installation site (see “4.1 Preparing the installation site” [4 7])

warning 2CAUTION

  • Check if the installation location can support the unit’s weight. Poor installation is hazardous. It can also cause vibrations or unusual operating noise.
  • Provide sufficient service space.
  • Do NOT install the unit so that it is in contact with a ceiling or a wall, as this may cause vibrations.

warning 2WARNING
The appliance shall be stored in a room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater).
Connecting the refrigerant piping (see “5.2 Connecting the refrigerant piping” [4 9])

warning 2CAUTION

  • No brazing or welding on site for units with R32 refrigerant charge during shipment.
  • During installation of the refrigeration system, joining of parts with at least one part charged shall be performed taking into account the following requirements: inside occupied spaces non permanent joints are not allowed for R32 refrigerant except for site made joints directly connecting the indoor unit to piping. Site made joints directly connecting piping to indoor units shall be of non permanent type.

warning 2CAUTION

  • Use the flare nut fixed to the unit.
  • To prevent gas leakage, apply refrigeration oil only to the inside of the flare. Use refrigeration oil for R32.
  • Do NOT reuse joints.

warning 2CAUTION

  • Do NOT use mineral oil on flared part.
  • Do NOT reuse piping from previous installations.
  • NEVER install a drier to this R32 unit to guarantee its lifetime. The drying material may dissolve and damage the system.

warning 2WARNING
Connect the refrigerant piping securely before running the compressor. If the refrigerant piping is NOT connected and the stop valve is open when the compressor is run, air will be sucked in. This will cause abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury.

warning 2CAUTION

  • Incomplete flaring may cause refrigerant gas leakage.
  • Do NOT re-use flares. Use new flares to prevent refrigerant gas leakage.
  • Use flare nuts that are included with the unit. Using different flare nuts may cause refrigerant gas leakage.

warning 2CAUTION
Do NOT open the valves before flaring is complete. This would cause refrigerant gas leakage.
WARNING ICON DANGER: RISK OF EXPLOSION
Do NOT start the unit if it is vacuumed.

Charging refrigerant (see “6 Charging refrigerant” [4 10])

warning 2WARNING
The refrigerant inside the unit is mildly flammable, but normally does NOT leak. If the refrigerant leaks in the room and comes in contact with fire from a burner, a heater, or a cooker, this may result in fire, or the formation of a harmful gas. Turn off any combustible heating devices, ventilate the room, and contact the dealer where you purchased the unit. Do NOT use the unit until a service person confirms that the part from which the refrigerant leaked has been repaired.

warning 2WARNING

  • Only use R32 as refrigerant. Other substances may cause explosions and accidents.
  • R32 contains fluorinated greenhouse gases. Its global warming potential (GWP) value is 675. Do NOT vent these gases into the atmosphere.
  • When charging refrigerant, ALWAYS use protective gloves and safety glasses.

warning 2CAUTION
To avoid compressor breakdown, do NOT charge more than the specified amount of refrigerant.
warning 2WARNING
NEVER directly touch any accidental leaking refrigerant. This could result in severe wounds caused by frostbite.
Electrical installation (see “7 Electrical installation” [4 11])
warning 2WARNING
Appliance shall be installed in accordance with national wiring regulations.

warning 2WARNING

  • All wiring MUST be performed by an authorised electrician and MUST comply with the applicable legislation.
  • Make electrical connections to the fixed wiring.
  • All components procured on-site and all electrical construction MUST comply with the applicable legislation.

warning 2WARNING

  • If the power supply has a missing or wrong N-phase, equipment might break down.
  • Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber, or telephone earth. Incomplete earthing may cause electrical shock.
  • Install the required fuses or circuit breakers.
  • Secure the electrical wiring with cable ties so that the cables do NOT come in contact with sharp edges or piping, particularly on the high-pressure side.
  • Do NOT use taped wires, stranded conductor wires, extension cords, or connections from a star system. They can cause overheating, electrical shock or fire.
  • Do NOT install a phase advancing capacitor, because this unit is equipped with an inverter. A phase advancing capacitor will reduce performance and may cause accidents.

warning 2WARNING
ALWAYS use multicore cable for power supply cables.
warning 2WARNING
Use an all-pole disconnection type breaker with at least 3  mm between the contact point gaps that provide full disconnection under overvoltage category III.
warning 2WARNING
If the supply cord is damaged, it MUST be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
warning 2WARNING
Do NOT connect the power supply to the indoor unit. This could result in electrical shock or fire.
warning 2WARNING

  • Do NOT use locally purchased electrical parts inside the product.
  • Do NOT branch the power supply for the drain pump, etc. from the terminal block. This could result in electrical shock or fire.

warning 2WARNING
Keep the interconnection wiring away from copper pipes without thermal insulation as such pipes will be very hot.
Electric Warning Icon DANGER: RISK OF ELECTROCUTION
All electrical parts (including thermistors) are powered by the power supply. Do not touch them with bare hands.
Electric Warning IconDANGER: RISK OF ELECTROCUTION
Disconnect the power supply for more than 10  minutes, and measure the voltage at the terminals of main circuit capacitors or electrical components before servicing. The voltage MUST be less than 50 V DC before you can touch electrical components. For the location of the terminals, see the wiring diagram.

Finishing indoor unit installation (see “8 Finishing the outdoor unit installation” [4 12])

Electric Warning Icon DANGER: RISK OF ELECTROCUTION

  • Make sure that the system is earthed properly.
  • Turn off the power supply before servicing.
  • Install the switch box cover before turning on the power supply.

Commissioning (see “10 Commissioning” [4 13])

Electric Warning Icon DANGER: RISK OF ELECTROCUTION
Risk of burns ICONDANGER: RISK OF BURNING/SCALDING
warning 2CAUTION
Do NOT perform the test operation while working on the indoor units.
When performing the test operation, NOT only the outdoor unit, but the connected indoor unit will operate as well.
Working on an indoor unit while performing a test operation is dangerous.
warning 2CAUTION
Do NOT insert fingers, rods or other objects into the air inlet or outlet. Do NOT remove the fan guard. When the fan is rotating at high speed, it will cause injury.

About the box

Outdoor unit
To remove the accessories from the outdoor unit
  1. Lift the outdoor unit.
  2. Remove the accessories at the bottom of the package.
    DAIKIN R32 Split System Air Conditioners - To remove

a. General safety precautions
b. Outdoor unit installation manual
c. Fluorinated greenhouse gases label
d. Multilingual fluorinated greenhouse gases label
e. Drain plug (located on the bottom of the packing case)
f. Energy label

Unit installation

warning 2WARNING
Installation shall be done by an installer, the choice of materials and installation shall comply with the applicable legislation. In Europe, EN378 is the applicable standard.

Preparing the installation site

warning 2WARNING
The appliance shall be stored in a room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater).

Installation site requirements of the outdoor unit

Mind the following spacing guidelines:DAIKIN R32 Split System Air Conditioners -outdoor unit

warningNOTICE
The height of the wall on the outlet side of the outdoor unit MUST be ≤1200 mm.

It is recommended to install a baffle plate when the air outlet is exposed to wind. It is recommended to install the outdoor unit with the air inlet facing the wall and NOT directly exposed to the wind. Do NOT install the unit in sound sensitive areas (e.g. near a bedroom), so that the operation noise will cause no trouble.
Note: If the sound is measured under actual installation conditions, the measured value might be higher than the sound pressure level mentioned in “Sound spectrum” in the data book due to environmental noise and sound reflections.

DAIKIN R32 Split System Air Conditioners - NFORMATIONINFORMATION
The sound pressure level is less than 70 dBA.
The outdoor unit is designed for outdoor installation only and for ambient temperatures specified in the table below (unless otherwise specified in the operation manual of the connected indoor unit).

ModelCoolingHeating
RXM-R, ARXM-R–10~50°C DB–20~24°C DB
RXA-A, RXJ-M–10~46°C DB–15~24°C DB
Additional installation site requirements of the outdoor unit in cold climates

Protect the outdoor unit against direct snowfall and take care that the outdoor unit is NEVER snowed up.DAIKIN R32 Split System Air Conditioners - Snow cover or shed

a. Snow cover or shed
b. Pedestal
c. Prevailing wind direction
d. Air outlet

It is recommended to provide at least 150 mm of free space below the unit (300 mm for heavy snowfall areas). Additionally, make sure the unit is positioned at least 100 mm above the maximum expected level of snow. If necessary, construct a pedestal. See “4.2 Mounting the outdoor unit” [4 8] for more details. In heavy snowfall areas it is very important to select an installation site where the snow will NOT affect the unit. If lateral snowfall is possible, make sure that the heat exchanger coil is NOT affected by the snow. If necessary, install a snow cover or shed and a pedestal.

Mounting the outdoor unit
To provide the installation structure

Use a vibration-proof rubber (field supply) in cases where vibrations may be transmitted to the building.
Prepare 4 sets of M8 or M10 anchor bolts, nuts and washers (field supply).
DAIKIN R32 Split System Air Conditioners - Preparea. 100 mm above expected level of snow

To install the outdoor unit

DAIKIN R32 Split System Air Conditioners -To install the outdoor unit

To provide drainage

warningNOTICE
If the unit is installed in a cold climate, take adequate measures so that the evacuated condensate CANNOT freeze.
warningNOTICE
If the drain holes of the outdoor unit are blocked up by a mounting base or floor surface, place additional foot bases ≤30 mm under the outdoor unit’s feet.
DAIKIN R32 Split System Air Conditioners - NFORMATIONINFORMATION
For information on the available options, contact your dealer.

  1. Use a drain plug for drainage.
  2. Use a Ø16 mm hose (field supply).

DAIKIN R32 Split System Air Conditioners - Drain port

a Drain port
b Bottom frame
c Drain plug
d Hose (field supply)

Piping installation

Preparing refrigerant piping
Refrigerant piping requirements

warning NOTICE
The piping and other pressure-containing parts shall be suitable for refrigerant. Use phosphoric acid deoxidised seamless copper for refrigerant.

▪ Piping material: Phosphoric acid deoxidised seamless copper.
▪ Flare connections: Only use annealed material.
▪ Piping diameter:

Liquid pipingØ6.4 mm (1/4″)
Gas pipingØ9.5 mm (3/8″)

▪ Piping temper grade and thickness:

Outer diameter (Ø)Temper gradeThickness (t) (a)
6.4 mm (1/4″)Annealed (O)≥0.8 mmDAIKIN R32 Split System Air Conditioners - Thickness
9.5 mm (3/8″)Annealed (O)

(a) Depending on the applicable legislation and the maximum working pressure of the unit (see “PS High” on the unit name plate), larger piping thickness might be required.

Refrigerant piping insulation
  • Use polyethylene foam as insulation material:
  • with a heat transfer rate between 0.041 and 0.052 W/mK (0.035 and 0.045 kcal/mh°C)
  • with a heat resistance of at least 120°C
  • Insulation thickness
Pipe outer diameter (Øp)Insulation inner diameter (Øi)Insulation thickness (t)
6.4 mm (1/4″)8~10 mm≥10 mm
9.5 mm (3/8″)12~15 mm

DAIKIN R32 Split System Air Conditioners - temperature

If the temperature is higher than 30°C and the humidity is higher than RH 80%, the thickness of the insulation materials should be at least 20  mm to prevent condensation on the surface of the insulation.

Refrigerant piping length and height difference
What?Distance
Maximum allowable pipe length20 m
What?Distance
Minimum allowable pipe length1.5 m
Maximum allowable height difference15 m
Connecting the refrigerant piping

Risk of burns ICON DANGER: RISK OF BURNING/SCALDING

warning 2CAUTION

  • No brazing or welding on site for units with R32 refrigerant charge during shipment.
  • During installation of the refrigeration system, joining of parts with at least one part charged shall be performed taking into account the following requirements: inside occupied spaces non-permanent joints are not allowed for R32 refrigerant except for site made joints directly connecting the indoor unit to piping. Site made joints directly connecting piping to indoor units shall be of non-permanent type.
To connect the refrigerant piping to the outdoor unit
  • Piping length. Keep field piping as short as possible.
  • Piping protection. Protect the field piping against physical damage.

warning 2WARNING
Connect the refrigerant piping securely before running the compressor. If the refrigerant piping is NOT connected and the stop valve is open when the compressor is run, air will be sucked in. This will cause abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury.
warning 2CAUTION

  • Use the flare nut fixed to the unit.
  • To prevent gas leakage, apply refrigeration oil only to the inside of the flare. Use refrigeration oil for R32.
  • Do NOT reuse joints.
  1. Connect the liquid refrigerant connection from the indoor unit to the liquid stop valve of the outdoor unit.
    DAIKIN R32 Split System Air Conditioners - Liquid stop valvea Liquid stop valve
    b Gas stop valve
    c Service port
  2. Connect the gas refrigerant connection from the indoor unit to the gas stop valve of the outdoor unit.

warningNOTICE
It is recommended that the refrigerant piping between indoor and outdoor unit is installed in a ducting or the refrigerant piping is wrapped with finishing tape.

Checking the refrigerant piping
To check for leaks

warningNOTICE
Do NOT exceed the unit’s maximum working pressure (see “PS High” on the unit name plate).
warningNOTICE
ALWAYS use a recommended bubble test solution from your wholesaler.
NEVER use soap water:

  • Soap water may cause cracking of components, such as flare nuts or stop valve caps.
  • Soap water may contain salt, which absorbs moisture that will freeze when the piping gets cold.
  • Soap water contains ammonia which may lead to corrosion of flared joints (between the brass flare nut and the copper flare).
  1. Charge the system with nitrogen gas up to a gauge pressure of at least 200  kPa (2  bar). It is recommended to pressurize to 3000 kPa (30 bar) in order to detect small leaks.
  2. Check for leaks by applying the bubble test solution to all connections.
  3. Discharge all nitrogen gas.
To perform vacuum drying

WARNING ICON DANGER: RISK OF EXPLOSION
Do NOT start the unit if it is vacuumed.

  1. Vacuum the system until the pressure on the manifold indicates −0.1 MPa (−1 bar).
  2. Leave as is for 4-5 minutes and check the pressure:
    If the pressure…
    Does not change
    Increases
  3. Vacuum the system for at least 2 hours to a manifold pressure of −0.1 MPa (−1 bar).
  4. After turning the pump OFF, check the pressure for at least 1 hour.
  5. If you do NOT reach the target vacuum or CANNOT maintain the vacuum for 1 hour, do the following:
    ▪ Check for leaks again.
    ▪ Perform vacuum drying again.

warning NOTICE
Make sure to open the stop valves after installing the refrigerant piping and performing vacuum drying. Running the system with the stop valves closed may break the compressor.

Charging refrigerant

About the refrigerant

This product contains fluorinated greenhouse gases. Do NOT vent gases into the atmosphere.
Refrigerant type: R32
Global warming potential (GWP) value: 675
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
warning 2WARNING
The appliance shall be stored in a room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater).
warning 2WARNING
▪ Do NOT pierce or burn refrigerant cycle parts.
▪ Do NOT use cleaning materials or means to accelerate the defrosting process other than those recommended by the manufacturer.
▪ Be aware that the refrigerant inside the system is odourless.
warning 2WARNING
The refrigerant inside the unit is mildly flammable, but normally does NOT leak. If the refrigerant leaks in the room and comes in contact with fire from a burner, a heater, or a cooker, this may result in fire, or the formation of a harmful gas.
Turn off any combustible heating devices, ventilate the room, and contact the dealer where you purchased the unit.
Do NOT use the unit until a service person confirms that the part from which the refrigerant leaked has been repaired.
warning 2WARNING
NEVER directly touch any accidental leaking refrigerant.
This could result in severe wounds caused by frostbite.

To determine the additional refrigerant amount
If the total liquid piping length is…Then…
≤10 mDo NOT add additional refrigerant.
>10 mR=(total length (m) of liquid
piping⁠–⁠10 m)×0.020
R=Additional charge (kg) (rounded in units
of 0.01 kg)

DAIKIN R32 Split System Air Conditioners - NFORMATIONINFORMATION
Piping length is the one-way length of liquid piping.

To determine the complete recharge amount

DAIKIN R32 Split System Air Conditioners - NFORMATIONINFORMATION
If a complete recharge is necessary, the total refrigerant charge is: the factory refrigerant charge (see unit name plate) + the determined additional amount.

To charge additional refrigerant

warning 2WARNING

  • Only use R32 as refrigerant. Other substances may cause explosions and accidents.
  • R32 contains fluorinated greenhouse gases. Its global warming potential (GWP) value is 675. Do NOT vent these gases into the atmosphere.
  • When charging refrigerant, ALWAYS use protective gloves and safety glasses.

Prerequisite:
Before charging refrigerant, make sure the refrigerant piping is connected and checked (leak test and vacuum drying).

  1. Connect the refrigerant cylinder to the service port.
  2. Charge the additional refrigerant amount.
  3. Open the gas stop valve.
To fix the fluorinated greenhouse gases label
  1. Fill in the label as follows:
    DAIKIN R32 Split System Air Conditioners - fluorinateda. If a multilingual fluorinated greenhouse gases label is delivered with the unit (see accessories), peel off the applicable language and stick it on top of a.
    b. Factory refrigerant charge: see unit name plate
    c. Additional refrigerant amount charged
    d. Total refrigerant charge
    e. Quantity of fluorinated greenhouse gases of the total refrigerant charge expressed as tonnes CO2 equivalent.
    f. GWP = Global warming potential

warning NOTICE
Applicable legislation on fluorinated greenhouse gases requires that the refrigerant charge of the unit is indicated both in weight and CO2 equivalent.
Formula to calculate the quantity in CO2 equivalent tonnes: GWP value of the refrigerant × total refrigerant charge [in kg] / 1000
Use the GWP value mentioned on the refrigerant charge label.
2 Fix the label on the inside of the outdoor unit near the gas and liquid stop valves.

Electrical installation

Electric Warning IconDANGER: RISK OF ELECTROCUTION
warning 2 WARNING

  • All wiring MUST be performed by an authorised electrician and MUST comply with the applicable legislation.
  • Make electrical connections to the fixed wiring.
  • All components procured on-site and all electrical construction MUST comply with the applicable legislation.

warning 2WARNING
ALWAYS use multicore cable for power supply cables.
warning 2WARNING
Use an all-pole disconnection type breaker with at least 3  mm between the contact point gaps that provide full disconnection under overvoltage category III.
warning 2WARNING
If the supply cord is damaged, it MUST be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
warning 2WARNING
Do NOT connect the power supply to the indoor unit. This could result in electrical shock or fire.
warning 2WARNING

  • Do NOT use locally purchased electrical parts inside the product.
  • Do NOT branch the power supply for the drain pump, etc. from the terminal block. This could result in electrical shock or fire.

warning 2WARNING
Keep the interconnection wiring away from copper pipes without thermal insulation as such pipes will be very hot.
Electric Warning Icon DANGER: RISK OF ELECTROCUTION
All electrical parts (including thermistors) are powered by the power supply. Do not touch them with bare hands.
Electric Warning IconDANGER: RISK OF ELECTROCUTION
Disconnect the power supply for more than 10  minutes, and measure the voltage at the terminals of main circuit capacitors or electrical components before servicing. The voltage MUST be less than 50 V DC before you can touch electrical components. For the location of the terminals, see the wiring diagram.DAIKIN R32 Split System Air Conditioners - Disconnect

a Multimeter (DC voltage range)
b S80 – reversing solenoid valve lead wire
c S70 – fan motor lead wire
d LED
e S90 – thermistor lead wire
f S20 – electronic expansion valve lead wire
g S40 – thermal overload relay lead wire
h DB1 – diode bridge

Specifications of standard wiring components
ComponentClass 20Class 25+35
Power supply cableVoltage220-240 V
Phase1-
Frequency50 Hz
Wire sizes3-core cable
2.5 mm2-4.0 mm2
HO5RN-F (60245 IEC 57)
Interconnection cable (indooroutdoor)4-core cable

1.5 mm2-2.5 mm2 and
applicable for 220-240 V
HO5RN-F (60245 IEC 57)

Recommended circuit breaker10 A13 A
Residual current deviceMUST comply with applicable legislation
To connect the electrical wiring to the outdoor unit
  1. Remove the service cover.
  2. Open the wire clamp.
  3. Connect the interconnection cable and power supply as follows:
    DAIKIN R32 Split System Air Conditioners - Removea. Interconnection cable
    b. Power supply cable
    c. Circuit breaker
    d. Residual current device
    e. Power supply
    f. Earth
    DAIKIN R32 Split System Air Conditioners - Tighten
  4. Tighten the terminal screws securely. We recommend using a Phillips screwdriver.
  5. Install the service cover.

Finishing the outdoor unit installation

To finish the outdoor unit installation

Electric Warning IconDANGER: RISK OF ELECTROCUTION

  • Make sure that the system is earthed properly.
  • Turn off the power supply before servicing.
  • Install the switch box cover before turning on the power supply.
  1. Insulate and fix the refrigerant piping and cables as follows:
    DAIKIN R32 Split System Air Conditioners - Insulatea. Gas pipe
    b. Gas pipe insulation
    c. Interconnection cable
    d. Field wiring (if applicable)
    e. Liquid pipe
    f. Liquid pipe insulation
    g. Finishing tape
  2. Install the service cover.

Configuration

Facility setting

Use this function for cooling at low outdoor temperature. This function is designed for facilities such as equipment of computer rooms. NEVER use in a residence or office where people occupy the space.
Applicable for: RXM-R, ARXM-R, RXJ-M, RXA-A.

To set the facility mode

When cutting jumper J6 on the PCB, the operation range will expand to –15°C. The facility mode will stop if the outdoor temperature drops below –20°C and resume when the temperature rises again.
To cut jumper J6

  1. Remove the top plate of the outdoor unit.
  2. Remove the front plate.
  3. Remove the drip proof cover.
  4. Cut jumper J6 on the outdoor unit PCB.
    DAIKIN R32 Split System Air Conditioners - Cut jumpera. Front plate
    b. Top plate
    c. Drip proof cover
    d. Jumpers

DAIKIN R32 Split System Air Conditioners - NFORMATION INFORMATION

  • The indoor unit may produce Intermittent noise due to the outdoor unit fan turning ON and/or OFF.
  • Do NOT place humidifiers or other items which might raise humidity in rooms when you use the facility mode.
  • Cutting jumper J6 sets the indoor unit fan to the highest speed.
  • Do NOT use this setting in residences or offices with people.
Standby electricity saving function
About the standby electricity saving function

This mode turns OFF the power supply of the outdoor unit and sets the indoor unit into the standby saving mode to reduce the power consumption of the unit.
This mode is only applicable for outdoor units: ARXM25+35R, RXM20~35R and indoor units: FTXM, ATXM, FVXM.
DAIKIN R32 Split System Air Conditioners - NFORMATIONINFORMATION
The standby electricity saving can ONLY be used for the units described above.
warning 2WARNING
Before connecting or disconnecting the connector, make sure the power supply is turned off.
DAIKIN R32 Split System Air Conditioners - NFORMATIONINFORMATION
Selective connector for standby electricity saving is required if other than applicable indoor unit is connected.

To turn on standby electricity saving function

Prerequisite: The main power supply MUST be turned off.

  1. Remove the service cover.
  2. Disconnect the selective standby electricity saving connector.
    DAIKIN R32 Split System Air Conditioners - Prerequisite
  3. Turn on the main power supply.

Commissioning

warningNOTICE
General commissioning checklist. Next to the commissioning instructions in this chapter, a general commissioning checklist is also available on the Daikin Business Portal (authentication required).
The general commissioning checklist is complementary to the instructions in this chapter and can be used as a guideline and reporting template during the commissioning and hand-over to the user.
warningNOTICE
ALWAYS operate the unit with thermistors and/or pressure sensors/switches. If NOT, burning of the compressor might be the result.

Checklist before commissioning

After the installation of the unit, first check the items listed below. Once all checks are fulfilled, the unit must be closed. Power-up the unit after it is closed.

DAIKIN R32 Split System Air Conditioners - PreparekThe indoor unit is properly mounted.
DAIKIN R32 Split System Air Conditioners - PreparekThe outdoor unit is properly mounted.
DAIKIN R32 Split System Air Conditioners - PreparekThe system is properly earthed and the earth terminals are tightened.
DAIKIN R32 Split System Air Conditioners - PreparekThe power supply voltage matches the voltage on the identification label of the unit.
DAIKIN R32 Split System Air Conditioners - PreparekThere are NO loose connections or damaged electrical components in the switch box.
DAIKIN R32 Split System Air Conditioners - PreparekThere are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units.
DAIKIN R32 Split System Air Conditioners - PreparekThere are NO refrigerant leaks.
DAIKIN R32 Split System Air Conditioners - PreparekThe refrigerant pipes (gas and liquid) are thermally insulated.
DAIKIN R32 Split System Air Conditioners - PreparekThe correct pipe size is installed and the pipes are
DAIKIN R32 Split System Air Conditioners - Preparekproperly insulated.
DAIKIN R32 Split System Air Conditioners - PreparekThe stop valves (gas and liquid) on the outdoor unit are fully open.
DAIKIN R32 Split System Air Conditioners - PreparekThe following field wiring has been carried out according to this document and the applicable legislation between the outdoor unit and the indoor unit.
DAIKIN R32 Split System Air Conditioners - PreparekDrainage
Make sure drainage flows smoothly.
Possible consequence: Condensate water might drip.
DAIKIN R32 Split System Air Conditioners - PreparekThe indoor unit receives the signals of the user interface.
DAIKIN R32 Split System Air Conditioners - PreparekThe specified wires are used for the interconnection cable.
DAIKIN R32 Split System Air Conditioners - PreparekThe fuses, circuit breakers, or locally installed protection devices are installed according to this document, and have NOT been bypassed.
Checklist during commissioning
DAIKIN R32 Split System Air Conditioners - PreparekTo perform an air purge.
DAIKIN R32 Split System Air Conditioners - PreparekTo perform a test run.
To perform a test run

Prerequisite: Power supply MUST be in the specified range.
Prerequisite: Test run may be performed in cooling or heating mode.
Prerequisite: Test run should be performed in accordance with the operation manual of the indoor unit to make sure that all functions and parts are working properly.

  1. In cooling mode, select the lowest programmable temperature.
    In heating mode, select the highest programmable temperature.
    Test run can be disabled if necessary.
  2. When the test run is finished, set the temperature to a normal level. In cooling mode: 26~28°C, in heating mode: 20~24°C.
  3. The system stops operating 3  minutes after the unit is turned OFF.

DAIKIN R32 Split System Air Conditioners - NFORMATION INFORMATION

  • Even if the unit is turned OFF, it consumes electricity.
  • When the power turns back on after a power break, the previously selected mode will be resumed.

Troubleshooting

Fault diagnosis using LED on outdoor unit PCB
LED is…Diagnosis
DAIKIN R32 Split System Air Conditioners -flashingflashingNormal.
▪ Check the indoor unit.
DAIKIN R32 Split System Air Conditioners - flashingsON▪ Turn the power OFF and back ON, and check the LED within approximately 3 minutes. If the LED is ON again, the outdoor unit PCB is faulty.
slide barOFF1. Supply voltage (for power saving).
2. Power supply fault.
3. Turn the power OFF and back ON, and check the LED within approximately 3 minutes.
If the LED is OFF again, the outdoor unit PCB is faulty.

Electric Warning Icon DANGER: RISK OF ELECTROCUTION

  • When the unit is not operating, the LEDs on the PCB are turned off in order to save power.
  • Even when the LEDs are off, the terminal block and the PCB may be powered.

Disposal

warningNOTICE
Do NOT try to dismantle the system yourself: dismantling of the system, treatment of the refrigerant, oil and other parts MUST comply with applicable legislation. Units MUST be treated at a specialised treatment facility for reuse, recycling and recovery.

Technical data

  • A subset of the latest technical data is available on the regional Daikin website (publicly accessible).
  • The full set of latest technical data is available on the Daikin Business Portal (authentication required).
Wiring diagram

The wiring diagram is delivered with the unit, located inside of the outdoor unit (bottom side of the top plate).

Unified wiring diagram legend

For applied parts and numbering, refer to the wiring diagram on the unit. Part numbering is by Arabic numbers in ascending order for each part and is represented in the overview below by “*” in the part code.

SymbolMeaningSymbolMeaning
DAIKIN R32 Split System Air Conditioners - iconCircuit breakerDAIKIN R32 Split System Air Conditioners - ProtectiveProtective earth
DAIKIN R32 Split System Air Conditioners - Liquid stop valvekConnectionDAIKIN R32 Split System Air Conditioners - earthProtective earth (screw)
DAIKIN R32 Split System Air Conditioners - Liquid stop valvecConnectorDAIKIN R32 Split System Air Conditioners - RectifierRectifier
DAIKIN R32 Split System Air Conditioners - InsulateeEarthDAIKIN R32 Split System Air Conditioners -RelayRelay connector
DAIKIN R32 Split System Air Conditioners - InsulatekField wiringDAIKIN R32 Split System Air Conditioners -connectorShort-circuit connector
DAIKIN R32 Split System Air Conditioners - InsulateekFuseDAIKIN R32 Split System Air Conditioners - TerminalTerminal
DAIKIN R32 Split System Air Conditioners - indorIndoor unitDAIKIN R32 Split System Air Conditioners -TerminalTerminal strip
DAIKIN R32 Split System Air Conditioners - InsulateekkOutdoor unitDAIKIN R32 Split System Air Conditioners - clampWire clamp
DAIKIN R32 Split System Air Conditioners - InsulateekoResidual current device
SymbolColourSymbolColour
BLKBlackORGOrange
BLUBluePNKPink
BRNBrownPRP, PPLPurple
GRNGreenREDRed
GRYGreyWHTWhite
YLWYellow
SymbolMeaning
A*PPrinted circuit board
BS*Pushbutton ON/OFF, operation switch
BZ, H*OBuzzer
C*Capacitor
AC*, CN*, E*, HA*, HE*, HL*, HN*, HR*, MR*_A, MR*_B, S*, U, V, W, X*A, K*R_*, NEConnection, connector
D*, V*DDiode
DB*Diode bridge
DS*DIP switch
E*HHeater
FU*, F*U, (for characteristics, refer to PCB inside your unit)Fuse
FG*Connector (frame ground)
H*Harness
SymbolMeaning
H*P, LED*, V*LPilot lamp, light emitting diode
HAPLight emitting diode (service monitor green)
HIGH VOLTAGEHigh voltage
IESIntelligent eye sensor
IPM*Intelligent power module
K*R, KCR, KFR, KHuR, K*MMagnetic relay
LLive
L*Coil
L*RReactor
M*Stepper motor
M*CCompressor motor
M*FFan motor
M*PDrain pump motor
M*SSwing motor
MR*, MRCW*, MRM*, MRN*Magnetic relay
NNeutral
n=*, N=*Number of passes through ferrite core
PAMPulse-amplitude modulation
PCB*Printed circuit board
PM*Power module
PSSwitching power supply
PTC*PTC thermistor
Q*Insulated gate bipolar transistor (IGBT)
Q*CCircuit breaker
Q*DI, KLMEarth leak circuit breaker
Q*LOverload protector
Q*MThermo switch
Q*RResidual current device
R*Resistor
R*TThermistor
RCReceiver
S*CLimit switch
S*LFloat switch
S*NGRefrigerant leak detector
S*NPHPressure sensor (high)
S*NPLPressure sensor (low)
S*PH, HPS*Pressure switch (high)
S*PLPressure switch (low)
S*TThermostat
S*RHHumidity sensor
S*W, SW*Operation switch
SA*, F1SSurge arrester
SR*, WLUSignal receiver
SS*Selector switch
SHEET METALTerminal strip fixed plate
T*RTransformer
TC, TRCTransmitter
V*, R*VVaristor
V*RDiode bridge, Insulated-gate bipolar transistor (IGBT) power  module
WRCWireless remote controller

DAIKIN R32 Split System Air Conditioners - QR3P650253-1

DAIKIN R32 Split System Air Conditioners - logo

DAIKIN ISITMA VE SOĞUTMA SİSTEMLERİ SAN.TİC. A.Ş.
Gülsuyu Mahallesi, Fevzi Çakmak Caddesi, Burçak Sokak, No:20, 34848 Maltepe
İSTANBUL / TÜRKİYE
Tel: 0216 453 27 00
Faks: 0216 671 06 00
Çağrı Merkezi: 444 999 0
Web: www.daikin.com.tr

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals