Seneca T201dch50-mu Ac/dc True Rms Or Dc Bipolar Current Transformer User Manual

Seneca T201dch50-mu Ac/dc True Rms Or Dc Bipolar Current Transformer User Manual

SENECA logo

USER MANUAL
T201DCH50-MU, T201DCH100-MU
T201DCH300-MU, T201DCH600-MU
AC/DC TRUE RMS or DC BIPOLAR CURRENT TRANSFORMER
WITH MODBUS RTU PROTOCOL AND ANALOG/DIGITAL OUTPUT

SENECA T201DCH50-MU AC DC True RMS or DC Bipolar Current

CE SYMBOL

SENECA S.r.l.
Via Austria 26 – 35127 – Z.I. – PADOVA (PD) – ITALY
Tel. +39.049.8705355 – 8705355 Fax +39 049.8706287
ORIGINAL INSTRUCTIONS
www.seneca.it

Introduction
Contents of the present documentation refer to products and technologies described in it.
All technical data contained in the document may be modified without prior notice.
Content of this documentation is subject to periodical revision.
To use the product safely and effectively, read carefully the following instructions before use.
The product must be used only for the use for which it was designed and built: any other use must be considered with full responsibility of the user. The installation, programming and set-up is allowed only to authorized operators, physically and intellectually suitable.
Set up shall be performed only after a correct installation and the user shall perform every operation described in the installation manual carefully.
Seneca is not considered liable for failure, breakdown, accident caused because of ignorance or failure to apply the indicated requirements.
Seneca is not considered liable for any unauthorized changes.
Seneca reserves the right to modify the device, for any commercial or construction requirements, without the obligation to promptly update the reference manuals.
No liability for the contents of these documents can be accepted.
Use the concepts, examples and other content at your own risk.
There may be errors and inaccuracies in this document that may of course be damaging to your system.
Proceed with caution, and although this is highly unlikely, the author(s) do not take any responsibility for that.
Technical features are subject to change without notice.

CONTACT US

Technical support[email protected]  
Product information[email protected] 

Document revisions

DATEREVISIONNOTES
20/02/20190First Revision
02/10/20201/2Added T201DCH600-MU model
26/05/20213Modiche a paragrafo Ingressi/Uscite digitali

This document is the property of SENECA srl. Duplication and reproduction are forbidden, if not authorized.

DEVICE DESCRIPTION AND INTENDED USE

WARNING WARNING!
This User Manual extends the information from the Installation Manual about the device configuration.
Use the Installation Manual for more info.

WARNING WARNING!
Under any circumstances, SENECA s.r.l. or its suppliers shall not be responsible for loss of recording data/incomes or for consequential or incidental damage due to neglect or reckless mishandling of the device, even though SENECA is well aware of these possible damages.
SENECA, its subsidiaries, affiliates, companies of the group, its suppliers and retailers shall not guarantee that the functions will satisfy completely customer’s expectations or that device, the firmware and the software shall have no errors or work continuously.

Description

The T201DCH50/100/300/600-MU are isolated contactless loop-powered AC/DC current transducers. The look and device’s function are very similar to those of an active standard Current Transformer, but with the remarkable feature of measuring the DC and AC components. For its electrical endurance, ease of use and compact dimensions, the T201DCH50-MU, T201DCH100-MU and T201DCH300-MU and T201DCH600-MU fit every kind of current measurement: up to 50 Adc/Aac, 100 Adc/Aac and 300 Adc/Aac and 600 Adc/Aac (respectively).
An RS485 port and a USB port with a standard Modus RTU slave protocol are also available. The device can measure a current in 2 different modes (using dip switches or the Easy Setup Software):

  • TRUE RMS AC/DC CURRENT MEASURE
  • DC BIPOLAR CURRENT MEASURE (used also for obtaining the sign +/- of a DC current)
Features
  • Similar usage to a standard alternating current active C.T.
  • No shunt, no wasted power from the measuring circuit
  • High accuracy rating
  • Analog 0/10V dc with configurable start/stop values
  • Digital Output configurable Alarm (Max, Min, Window)
  • Suitable for use with all Seneca modules that allow to power the device with at least 12 Vdc and having a 0 – 10Vdc input
  • Simple configurable with dip switches or with the free Easy Setup software
  • Two ranges, dip-switch selectable
  • Damping filter availability to improve stable reading
  • Modbus RTU protocol by RS485 and USB ports
  • Modbus Address/Baud Rate/Range/Mode configurable also from dip switch
  • Suitable for batteries, battery chargers, solar panels, power units and generic dc and ac loads.
  • Compact size: overall dimensions less than 96,5 x 68 x 26 mm
  • Baud rate for Modbus RTU: from 1200 baud up to 115200 baud
  • Start/Stop Input/Output Alarm Values configurable with Easy Setup software
  • I Max/Min Resettable by Modbus RTU registers
  • Quick installation on DIN 46277 rail

Refer to the installation manual for more information.

CONFIGURING THE DEVICE

The Device can be configured in two ways:

  • A basic configuration from dip switches
  • A full configuration from flash (using Easy Setup Software by the USB port)

WARNING WARNING!
Dip switches configurations are active only after a reboot!
WARNING WARNING!
The Dip Switch setting will overwrite the Flash setting so, if you need to use the flash configuration you MUST set ALL dip switches to “OFF”.

DIP SWITCH CONFIGURATION

Loading configuration from flash

If ALL Dip Switch 1…8 are OFF, the device use the Flash configuration (you must use the Easy software for configure)

Load  ConfigurationDIP1DIP2DIP3DIP4DIP5DIP6DIP7DIP8
FROM FLASHOFFOFFOFFOFFOFFOFFOFFOFF
Setting the RS485 Modbus RTU Station Address

Dip Switch 1..4 are used for configuring the Modbus RTU Station Address:

Modbus RTU
Address
DIP1DIP2DIP3DIP4
1ONOFFOFFOFF
2OFFONOFFOFF
3ONONOFFOFF
4OFFOFFONOFF
5ONOFFONOFF
6OFFONONOFF
7ONONONOFF
8OFFOFFOFFON
9ONOFFOFFON
10OFFONOFFON
11ONONOFFON
12OFFOFFONON
13ONOFFONON
14OFFONONON
15ONONONON
Setting the RS485 Baud rate

Dip Switch 5..6 are used for setting the Baud Rate

Baud RateDIP5DIP6
9600OFFOFF
19200ONOFF
38400OFFON
57600ONON

WARNING WARNING!
The Parity bit can not be configured with the dip switches configuration but only from the Easy Setup software. By setting the dip switches the parity is always set to “None” (8,N,1).

Setting the RMS/Bipolar mode and 50% – 100% full scale

Dip Switch 7: Select from True RMS Measure / Bipolar DC Measure
Dip Switch 8: Select 50% of full scale
The following figure is related to RMS measure (“Bipol” dip switch 7 = OFF):

SENECA T201DCH50-MU AC DC True RMS or DC Bipolar Current- Setting the RMS

MODELDIP7  BIPOLDIP8  50% FSAB
T201DCH50-MUOFFOFF25 A50 A
T201DCH50-MUOFFON12,5 A25 A
T201DCH100-MUOFFOFF50 A100 A
T201DCH100-MUOFFON25 A50 A
T201DCH300-MUOFFOFF150 A300 A
T201DCH300-MUOFFON75 A150 A
T201DCH600-MUOFFOFF300 A600 A
T201DCH600-MUOFFON150 A300 A

The following figure is related to the Bipolar measure (“Bipol” dip switch 7 = ON):

SENECA T201DCH50-MU AC DC True RMS or DC Bipolar Current- Setting the RMS 2

MODELBIPOL DIP7
SWITCH
50%FS DIP8
SWITCH
CD
T201DCH50-MUONOFF-50 A+50 A
T201DCH50-MUONON-25 A+25 A
T201DCH100-MUONOFF-100 A+100 A
T201DCH100-MUONON-50 A+50 A
T201DCH300-MUONOFF-300 A+300 A
T201DCH300-MUONON-150 A+150 A
T201DCH600-MUONOFF-600 A+600 A
T201DCH600-MUONON-300 A+300 A

WARNINGWARNING!
Dip switches configuration is active only after a reboot!
So, for example, using the RMS measure with 0 A input the Output voltage is 0V but using the Bipolar measure with 0 A input the Output voltage is 5V.

MODBUS RTU PROTOCOL

The Modbus protocol supported by the T201DCH50-100-300-600 MU is:

  • Modbus RTU Slave

For more information about these protocols, please refer to the Modbus specification website: http://www.modbus.org/specs.php.

Modbus RTU function code supported

The following Modbus RTU functions are supported:

  • Read Holding Register (function 3) Max 5 Registers
  • Write Single Register (function 6)
  • Write Multiple registers (function 16) Max 2 Registers

WARNING WARNING!
All 32 bits values are stored into 2 consecutive registers
WARNING WARNING!
You can Read a Maximum of 5 Modbus Registers with the Read Holding Register function (function 3)
WARNING WARNING!
You can Write a Maximum of 2 Modbus Registers with the Write Multiple Register function (function 16)
WARNING WARNING!
The USB Modbus configuration is fixed to 38400 baud, 8bit, No parity, 1 stop bit When the USB cable is inserted the RS485 will stop communicating until the USB will be unplugged.

MODBUS REGISTER TABLE

The following abbreviations are used in the register tables:
MS = More significant
LS = Less significant
MSW = 16 most significant bits
LSW = 16 least significant bits
MSW* = 16 most significant or least significant bits depending on the configuration (most significant default)
LSW* = 16 less significant or more significant bits depending on the configuration (less significant default)
MSW = 8 most significant bits
LSW = 8 least significant bits
MSBIT = Most significant bit
MSBIT = Least significant bit
RO = Register in read-only
RW = Read/write register
RW** = Reading and writing register contained in flash memory, writable a maximum of 10000 times.
Unsigned 16 bit = unsigned integer register, can take values from 0 to 65535
Signed 16 bit = signed integer register can take values from -32768 to +32767
Float 32 bits = 32-bit single-precision floating point register (IEEE 754) https://en.wikipedia.org/wiki/IEEE_754
BIT = Boolean registry, can be 0 (false) or 1 (true)

 “0-BASED” OR “1-BASED” MODBUS ADDRESSES

According to the Modbus standard, the Holding Register registers are addressable from 0 to 65535, there are 2 different conventions for numbering the addresses: “0-BASED” and “1-BASED”.
For greater clarity, Seneca shows its register tables in both conventions.

WARNING ATTENTION!
CAREFULLY READ THE DOCUMENTATION OF THE MODBUS MASTER DEVICE IN ORDER TO UNDERSTAND WHICH OF THE TWO CONVENTIONS THE MANUFACTURER HAS DECIDED TO USE

5.1.1. MODBUS ADDRESSES WITH “0-BASED” CONVENTION
The numbering is:

HOLDING REGISTER MODBUS
ADDRESS (OFFSET)
MEANING
0FIRST REGISTER
1SECOND REGISTER
2THIRD REGISTER
3FOURTH REGISTER
4FIFTH REGISTER

Therefore the first register is at address 0.
In the following tables, this convention is indicated with “ADDRESS OFFSET”.
5.1.2. MODBUS ADDRESSES WITH “1 BASED” CONVENTION (STANDARD)
The numbering is that established by the Modbus consortium and is of the type:

HOLDING REGISTER MODBUS
ADDRESS 4x
MEANING
40001FIRST REGISTER
40002SECOND REGISTER
40003THIRD REGISTER
40004FOURTH REGISTER
40005FIFTH REGISTER

In the following tables, this convention is indicated with “ADDRESS 4x” since a 4 is added to the address so that the first Modbus register is 40001.
A further convention is also possible where the number 4 is omitted in front of the registered address:

HOLDING MODBUS ADDRESS
WITHOUT 4x
MEANING
1FIRST REGISTER
2SECOND REGISTER
3THIRD REGISTER
4FOURTH REGISTER
5FIFTH REGISTER
BIT CONVENTION WITHIN A MODBUS HOLDING REGISTER

A Modbus Holding Register consists of 16 bits with the following convention:

BITBITBITBITBITBITBITBITBITBITBITBITBITBITBITBIT
1514131211109876543210

For instance, if the value of the register in decimal is 12300
the value 12300 in hexadecimal is: 0x300C
the hexadecimal 0x300C in binary value is: 11 0000 0000 1100
So, using the above convention, we get:

BITBITBITBITBITBITBITBITBITBITBITBITBITBITBITBIT
1514131211109876543210
0011000000001100
MSB and LSB BYTE CONVENTION WITHIN A MODBUS HOLDING REGISTER

A Modbus Holding Register consists of 16 bits with the following convention:

BITBITBITBITBITBITBITBITBITBITBITBITBITBITBITBIT
1514131211109876543210

LSB Byte (Least Significant Byte) defines the 8 bits ranging from Bit 0 to Bit 7 included, we define MSB Byte (Most Significant Byte) the 8 bits ranging from Bit 8 to Bit 15 inclusive:

BITBITBITBITBITBITBITBITBITBITBITBITBITBITBITBIT
1514131211109876543210
BYTE MSBBYTE LSB
REPRESENTATION OF A 32-BIT VALUE IN TWO CONSECUTIVE MODBUS HOLDING REGISTERS

The representation of a 32-bit value in the Modbus Holding Registers is made using 2 consecutive Holding Registers (a Holding Register is a 16-bit register). To obtain the 32-bit value it is, therefore, necessary to read two consecutive registers:

For example, if register 40064 contains the 16 most significant bits (MSW) while register 40065 contains the least significant 16 bits (LSW), the 32-bit value is obtained by composing the 2 registers:

BITBITBITBITBITBITBITBITBITBITBITBITBITBITBITBIT
1514131211109876543210
40064 MOST SIGNIFICANT WORD

 

BITBITBITBITBITBITBITBITBITBITBITBITBITBITBITBIT
1514131211109876543210
40065 LEAST SIGNIFICANT WORD

32 = + ( ∗ 65536)
In the reading registers it is possible to swap the most significant word with the least significant word, therefore it is possible to obtain 40064 as LSW and 40065 as MSW.

TYPE OF 32-BIT FLOATING POINT DATA (IEEE 754)

The IEEE 754 standard (https://en.wikipedia.org/wiki/IEEE_754) defines the format for representing floating-point numbers.
As already mentioned, since it is a 32-bit data type, its representation occupies two 16-bit holding registers.
To obtain a binary/hexadecimal conversion of a floating-point value it is possible to refer to an online converter at this address: http://www.h-schmidt.net/FloatConverter/IEEE754.html

SENECA T201DCH50-MU AC DC True RMS or DC Bipolar Current- FLOATING POINT

Using the last representation the value 2.54 is represented at 32 bits as: 0x40228F5C
Since we have 16-bit registers available, the value must be divided into MSW and LSW: 0x4022 (16418 decimal) are the 16 most significant bits (MSW) while 0x8F5C (36700 decimal) are the 16 least significant bits (LSW).

T201DCH-MU: MODBUS 4xxxx HOLDING REGISTERS TABLE (FUNCTION CODE 3)
REGISTER
NAME
COMMENTREGISTE
RTYPE
R/WDEFAULT
T VALUE
OR
START
VALUE
ADDRESS
(4xxxx)
OFFSET ADDRESS
S
INTEGER
CURRENT
VALUE
[A X100]
[A X10]
(T201 DC H600
A)
Current Measure Value
in signed integer
[A x100]
For example:
18534 = 185.34 A
-2500 = -25.00 A
[A x10] for 600A model
For example:
60000 = 600.0 A
Signed 16
Bits
R4005150
CURRENT
MIN
[A]
Minimum Current Value
(use register Command
for reset the value)
The value is set to 0 at
startup
Float32R40059 (LSW) 40060 (MSW)58-59
CURRENT
MAX
[A]
Maximum Current Value
(use register Command
for reset the value)
The value is set to 0 at
startup
Float32R40061 (LSW) 40062 (MSW)60-61
OUTPUT
VOLTAGE
r
Output Voltage
M
Float32
40063
R(LSW)
40064
(MSW)
62-63
INVERSE
FLOAT
CURRENT
VALUE
[A]
Current Measure Value
in floating-point MSW-
LSW
[A]
Copy of Float Current
Value
Registers with Inverse
(MSW-LSW) Floating
Point
Float32R40065 (MSW) 40066 (LSW)64-65

 

REGISTER
NAME
COMMENTREGISTE
R TYPE
1DEFAULT
T VALUE
OR
START
VALUE
ADDRESS
(4xxxx)
OFFSET
ADDRESS
INTEGER
CURRENT
VALUE
[A X100]
[A X10]
(7201 DC H600
A)
Current Measure Value
in signed integer
[A x100]
For example:
18534 = 185.34 A
-2500 = -25.00 A
[A x10] for 600A model
For example:
60000 = 600.0 A
Signed 16
Bits
R4005150
CURRENT
MIN
[A]
Minimum Current Value
(use register Command
for reset the value)
The value is set to 0 at
startup
Float32R40059 (LSW) 40060 (MSW)58-59
CURRENT
MAX
[A]
Maximum Current Value
(use register Command
for reset the value)
The value is set to 0 at
startup
Float32R40061 (LSW) 40062 (MSW)60-61
OUTPUT
VOLTAGE
M
Output VoltageFloat32
40063
R(LSW)
40064
(MSW)
62-63
INVERSE
FLOAT
CURRENT
VALUE
[A]
Current Measure Value
in floating-point MSW-
LSW
[A]
Copy of Float Current
Value
Registers with Inverse
(MSW-LSW) Floating
Point
Float32R40065 (MSW) 40066 (LSW)64-65

 

REGISTER
NAME
COMMENTREGISTE
R TYPE
1DEFAULT VALUE
OR
START
VALUE
ADDRESS
(4xxxx)
OFFSET
ADDRESS
ALARM
STATUS
Alarm status flag:
BIT 0 = Max Pre-Alarm BIT 1 = Min Pre-Alarm BIT 2 = Internal Window Pre-Alarm
BIT 3 = External Window Pre-Alarm
Bit 4..Bit 7 = Not Used BIT 8 = Max Alarm
BIT 9 = Min Alarm
BIT 10 = Internal
Window Alarm
BIT 11 = External
Window Alarm
BIT 12..15 = Not Used
Unsigned
16 bits
R04006766
MODBUS
STATION
ADDRESS
Modbus RTU station
address
Unsigned
16 bits
WV’140101100
BAUD RATERS485 Port Baud rate
0 = 4800 baud
1 = 9600 baud
2 =19200 baud
3 = 38400 baud
4 = 57600 baud
5 = 115200 baud
6 = 1200 baud
7 = 2400 baud
Unsigned
16 bits
MN*340102101
PARITYCommunication Parity
Bit
0 = None (8,N,1)
1= Even (8,E,1)
2 = Odd (8,0,1)
Unsigned
16 bits
Rw.040103102
REGISTER
NAME
COMMENTREGISTE
R TYPE
1DEFAULT VALUE
OR
START
VALUE
ADDRESS
(4xxxx)
OFFSET
ADDRESS
OUT MODE
TRUE
RMS/BIPOLAR
MSB (OUT MODE)
Select from Digital or
Analog output:
0 = Select Analog
Output
1 = Select Digital Output
(Alarm)
LSB (TRUE
RMS/BIPOLAR) Select from True RMS or Bipolar DC
measurement mode
0 = True RMS
1 = Bipolar DC
Unsigned
16 bits
RW0, „,103
RESERVEDReservedUnsigned
16 bits
R04005104
FILTERSelect Filter level
0 = LOW
RMS =1400 ms
response Time
BIPOLAR = 78 ms
response Time
1 = HIGH
RMS = 2900 ms
response Time
BIPOLAR = 650 ms
response Time
Unsigned
16 bits
Rw.0:C’ 06105
MODELSelect the model
0 = T201DCH50-MU
1 = T201DCH100-MU
2 = T201DCH300-MU
3 = T201DCH300-MU
HW2
4 = T201DCH600-MU
Unsigned
16 bits
RAccording
to the
model
40107106
REGISTER
NAME
COMMENTREGISTE
R TYPE
RWOR T VALUE
START
VALUE
ADDRESS
(4xxxx)
OFFSET
ADDRESS
ALARM TYPESelect the Alarm linked
to the Digital Output:
0 = NONE
1= MAX (Alarm if the
Current is above the
High Threshold)
2 = MIN (Alarm if the
Current is below the Low
Threshold)
3 = Window INT (Alarm
if the Current > Low
Threshold but < High
Threshold)
4 – Window EXT (Alarm
if the Current is > High
Threshold or < Low
Threshold)
Unsigned
16 bits
Dim.
I’
0.: : ‘ :5
DOUT MODE0 = Digital Output is
normally Low
1 = Digital Output is
normally Hiqh
Unsigned
16 bits
Rw.040109108
ALARM
DELAY
Alarm delay in x 10ms
(for example mite 1000
for obtain 10 seconds of
delay)
unsigned
16 bits
RW ,
R
040110109
START INPUT
SCALE
Select the Start Input
Scale [A]
Float32RW’According
to the
“1”
model
40111 (LSW)
40112 (MSW)
110-111
STOP INPUT
SCALE
Select the Stop Input
Scale [A]
Float32RIN IAccording to tha” model40113 (LSW)
40114 (MSW)
112-113
START
OUTPUT
SCALE
Select the Start output
Scale M
Float32RW’0.0 V40115 (LSW)
40116 (MSW)
114-115
STOP
OUTPUT
SCALE
Select the Stop output
Scale M
Float32RW*10.0 V40117 (LSW)
40118 (MSW))
116-117
ALARM
HYSTERESIS
Select the Hysteresis for
the Alarm in [A]
Float32RW’10.0 A40119 (LSW)
40120 (MSW)
118-119

FULL CONFIGURATION WITH EASY SETUP

For configuring all the device parameters you must use the RS485 Port and the Easy T201DCH-MU software included in the Easy Setup Suite.
You can download the Easy Setup software for free from: www.seneca.it

Easy Setup Menu

SENECA T201DCH50-MU AC DC True RMS or DC Bipolar Current- Easy Setup Menu

Connect: Use the connect icon for connecting the PC to the Device. Note that you need an RS485 to USB converters like Seneca S117P1 or S107USB for connecting the device to a PC.
New: Load the default parameters in the actual project
Open: Open a stored project
Save: Save the actual project
Read: Read the actual configuration from the device (if the dip switches are not ALL of the configuration is read from dip switches)

WARNING WARNING!
If you read a configuration from the device with at least one dip switch to “ON” the software will read the dip switch configuration because of overwriting the flash configuration.
Send: Send the project configuration (if the dip switches are not ALL of the device use the dip switch configuration and NOT the sent configuration)
Test: Start a Registers read, you can also reset the MIN/MAX values and start/stop a Datalogger

Creating a Project Configuration

SENECA T201DCH50-MU AC DC True RMS or DC Bipolar Current- Creating a ProjectWARNING WARNING!
You must set all dip switches to OFF before sending the configuration to the device or the actual configuration will be overwritten from the dip switches configuration!
The parameters in the “Configuration” section that can be configured are:
Model: Select between T201DCH50-MU, T201DCH100-MU, T201DCH300-MU, T201DCH300-MU HW2 or T201DCH600-MU model.
Station Address: Select The Modbus RTU station address
Baud Rate: Select the Baud rate from 1200 to 115200 baud
Parity: Select NONE, ODD or EVEN
Mode: Select the current measure mode: True RMS or DC Bipolar
Filter: Select between LOW or HIGH:

FILTERRMS RESPONSE
TIME
(10%-90% F.S.)
BIPOLAR DC
RESPONSE TIME
(10%-90% F.S.)
LOW1400 ms78 ms
HIGH2900 ms650 ms

The parameters in the “OUTPUT” section that can be configured depends by the Output Type if is selected “Analogic” or “Digital” (Only for T201DCH50/100/300-MU models)
If The Output is configured in “Analogic”:

SENECA T201DCH50-MU AC DC True RMS or DC Bipolar Current- nalogic

Note: The T201DCH600-MU allows the use of both the analog and digital output simultaneously.
Input Start/Stop Scale and Output Start/Stop Scale: Select the Start/Stop input and Output Start/Stop scale see figure:

SENECA T201DCH50-MU AC DC True RMS or DC Bipolar Current- Input Start

For example:
INPUT START = 20 A
INPUT STOP = 80 A
OUTPUT START = 2 V
OUTPUT STOP = 6 V

SENECA T201DCH50-MU AC DC True RMS or DC Bipolar Current- Input Start 2

Note that with an input of 0 A the output is 0 V and over 80 A the output is over 6V (6V and 2V are not a limit).
WARNING WARNING!
The Output Voltage is limited to about 10.8V
If The Output is configured in “Digital”:SENECA T201DCH50-MU AC DC True RMS or DC Bipolar Current- Output

Digital Output Type: Select between Normally Low or Normally High.
Alarm Type: Select Between:
NONE: No Alarm active
MAXIMUM: Alarm if the Current is above the High Threshold
MINIMUM: Alarm if the Current is below the Low Threshold
ACTIVE IF INTO THE WINDOW: (Alarm if the Current > Low Threshold but < High Threshold)
ACTIVE IF OUT THE WINDOW: (Alarm if the Current is > High Threshold or < Low Threshold)
Alarm Delay: Select the Alarm delay in x 10 ms (for example write 100 for 1-second delay)
Hysteresis: Select the Alarm Hysteresis in [A]
High Alarm: Select the High Threshold for the Alarm in [A]
Low Alarm: Select the Low Threshold for the Alarm in [A]

Testing the Device

When the configuration is sent to the device you can test the actual configuration by using the SENECA T201DCH50-MU AC DC True RMS or DC Bipolar Current- Testingicon:

SENECA T201DCH50-MU AC DC True RMS or DC Bipolar Current- Testing the Device

The test configuration will acquire the measure from the Modbus registers, you can also reset the MIN/MAX values.

6.3.1. The datalogger

The datalogger can be used for acquiring data that can be used with external software (for example Microsoft Excel ™). It is possible to set how much time to acquire the samples (minimum 1 second):

SENECA T201DCH50-MU AC DC True RMS or DC Bipolar Current- The datalogger
The datalogger will create a file in a standard .csv format that can be open with external tools:
SENECA T201DCH50-MU AC DC True RMS or DC Bipolar Current- external toolsThe file can also be open with a text editor:

INDEX;TYPE;TIMESTAMP;I;IMAX;IMIN;VOUT
1;LOG;18/07/2017 17:37:16;9,94182968139648;10,0166397094727;0;5,50153207778931
2;LOG;18/07/2017 17:37:17;9,98420906066895;10,0598001480103;0;5,50216913223267
3;LOG;18/07/2017 17:37:18;10,0491199493408;10,0602102279663;0;5,4690899848938
4;LOG;18/07/2017 17:37:19;9,99160003662109;10,0602102279663;0;5,50054502487183
5;LOG;18/07/2017 17:37:20;10,0064001083374;10,0602102279663;0;5,49996995925903
6;LOG;18/07/2017 17:37:21;10,0018796920776;10,0602102279663;0;5,50327777862549
7;LOG;18/07/2017 17:37:22;9,94471645355225;10,0778799057007;0;5,50132608413696
8;LOG;18/07/2017 17:37:23;9,97722816467285;10,0778799057007;0;5,50247716903687
9;LOG;18/07/2017 17:37:24;10,0623197555542;10,0778799057007;0;5,50186014175415
10;LOG;18/07/2017 17:37:25;9,99120616912842;10,0778799057007;0;5,50126504898071
11;LOG;18/07/2017 17:37:26;10,0330896377563;10,0778799057007;0;5,50066900253296
12;LOG;18/07/2017 17:37:27;10,0363702774048;10,0778799057007;0;5,50058698654175
13;LOG;18/07/2017 17:37:29;10,0059795379639;10,0778799057007;0;5,50120306015015
14;LOG;18/07/2017 17:37:30;9,97681522369385;10,0778799057007;0;5,50337982177734
15;LOG;18/07/2017 17:37:31;10,0129499435425;10,0778799057007;0;5,50225019454956
16;LOG;18/07/2017 17:37:32;10,0162401199341;10,0778799057007;0;5,50075101852417
17;LOG;18/07/2017 17:37:33;10,0614995956421;10,0778799057007;0;5,50206613540649

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY
BE REPRODUCED WITHOUT PRIOR PERMISSION.
www.seneca.it

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals