T201DCH100-OPEN Series Current Transformers
Product Information
| Model Number | T201DCH100-OPEN | T201DCH300-OPEN | T201DCH600-OPEN |
|---|---|---|---|
| Dimensions (LxHxD) | 90 x 85 x 36 mm | 90 x 85 x 36 mm | 90 x 85 x 36 mm |
| Weight | 145 g | 145 g | 145 g |
| Enclosure | PA6, black | PA6, black | PA6, black |
Product Usage Instructions
Installation Regulations
1. Remove the locking pin to allow the instrument to be
opened.
2. When using for the first time, the instrument will not be
blocked by the pin.
3. Position the reading instrument using the DIN rail or the
clamps. The reading direction of the instrument is indicated in the
reference drawing above.
4. Close the instrument using the locking pin. Apply sufficient
pressure to engage the upper half core with the locking lugs.
Caution
Make sure that the direction of the current flowing through the
cable is that shown in the figure (incoming). To increase the
sensitivity of the current measurement, insert the cable several
times into the central hole of the instrument, creating a series of
loops. The sensitivity of the current measurement is proportional
to the number of passages of the conductors in the hole, if the
loops are not homogeneously distributed a reading error could
occur.
Technical Specifications
| Certifications | – |
|---|---|
| Power Supply | – |
| Insulation | An insulation of 3 kVac is guaranteed on bare conductors |
INSTALLATION MANUAL
T201DCH100-OPEN T201DCH300-OPEN T201DCH600-OPEN
PRELIMINARY WARNINGS
The word WARNING preceded by the symbol indicates conditions or actions that put the user’s safety at risk. The word ATTENTION preceded by the symbol indicates conditions or actions that might damage the instrument or the connected equipment. The warranty shall become null and void in the event of improper use or tampering with the module or devices supplied by the manufacturer as necessary for its correct operation, and if the instructions contained in this manual are not followed.
WARNING: The full content of this manual must be read before any operation. The module must only be used by qualified electricians. Specific documentation is available using the QR-CODE shown on page 1.
The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to electrostatic discharges. Take appropriate measures during any operation. Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling). The symbol on the product or its packaging shows the product must be surrendered to a collection centre authorized to recycle electrical and electronic waste.
DOCUMENTATION T201DCH100-OPEN
DOCUMENTATION T201DCH300-OPEN
DOCUMENTATION T201DCH600-OPEN
SENECA s.r.l.; Via Austria, 26 35127 PADOVA ITALY; Tel. +39.049.8705359 – Fax +39.049.8706287
CONTACT INFORMATION
Technical support
Product information
This document is the property of SENECA srl. Copies and reproduction are prohibited unless authorised. The content of this document corresponds to the described products and technologies. Stated data may be modified or supplemented for technical and/or sales purposes.
MI00615-1-EN
INSTALLATION MANUAL
1/4
MODULE LAYOUT
36 m m
85 mm
90 mm
36 mm
Dimensions LxHxD: 90 x 85 x 36 mm; Weight: 145 g; Enclosure: PA6, black
SIGNALS VIA LED ON FRONT PANEL
LED PWR/COM Green PWR/COM Green
D-OUT Yellow
STATUS ON
Flashing ON
LED meaning The device is powered correctly Communication via USB and RS485 port
Digital output activated
INSTALLATION REGULATIONS
Remove the locking pin to allow the instrument to be opened.
When using for the first time, the instrument will not be blocked by the pin.
Position the reading instrument using the DIN rail or the clamps. The reading direction of the instrument is indicated in the reference drawing above.
Close the instrument using the locking pin. Apply sufficient pressure to engage the upper half core with the locking lugs.
CAUTION
Make sure that the direction of the current flowing through the cable is that shown in the figure (incoming). To increase the sensitivity of the current measurement, insert the cable several times into the central hole of the instrument, creating a series of loops. The sensitivity of the current measurement is proportional to the number of passages of the conductors in the hole, if the loops are not homogeneously distributed a reading error could occur.
MI00615-1-EN
INSTALLATION MANUAL
2/4
TECHNICAL SPECIFICATIONS
CERTIFICATIONS
POWER SUPPLY
Voltage: on Vcc and GND terminals, 11.5 28 Vdc; Absorption: Typical: 38 mA (LOAD EXCLUDED)
INSULATION
Using an insulated conductor, its sheath determines the insulation voltage. An insulation of 3 kVac is guaranteed on bare conductors
ENVIRONMENTAL CONDITIONS
Temperature: Humidity: Altitude: Storage temperature: Protection rating:
-25 ÷ + 70°C 10% ÷ 90% non condensing. Up to 2000 m above sea level -40 ÷ + 85°C IP20.
ASSEMBLY CONNECTIONS
DIN rail 35 mm IEC EN60715 or fixing with plastic ties.
Removable 5-way screw terminals, 5 mm pitch for cables up to 2.5 mm2 micro USB (FOR CONFIGURATION ONLY)
COMMUNICATION PORT
RS485 serial port on terminals A+ and B-; or on USB port
INPUT (on 36 mm through
hole)
Type of measurement: Crest factor: Pass-band: Overload:
AC/DC TRMS or DC Bipolar 2 1 kHz 2000 A impulsive, 3 x IN continuing
CAPACITY
AC/DC True RMS (DIP7=OFF)
DC Bipolar (DIP7=ON)
T201DCH100-OPEN
50A or 100A
±50A or ±100A
T201DCH300-OPEN
150A or 300A
±150A or ±300A
T201DCH600-OPEN
300A or 600A
±300A or ±600A
ANALOGUE OUTPUT on Vout and GND terminals
Type: 0 ÷ 10 Vdc, minimum load RLOAD =2 k. Protection: Reverse polarity protection and over voltage protection Resolution: 13 bit (10000 points)
EMI error: < 0.5% Temperature coefficient: < 200 ppm/°C Hysteresis on measurement: 0.2% of full scale Response speed: With “Fast” filter 800 ms. With “Slow” filter 2000 ms. The type of output can be selected via software
DIGITAL OUTPUT
Type: active, 0- Vcc, maximum load 50 mA The type of output can be selected via software
ACCURACY
below 2% of full scale
above 2% of full scale
T201DCH100-OPEN
1% of full scale at 50/60 Hz, 23°C
0.5% of full scale at 50/60 Hz, 23°C
T201DCH300-OPEN T201DCH600-OPEN
2% of full scale at 50/60 Hz, 23°C
1% of full scale at 50/60 Hz, 23°C
OVERVOLTAGE CATEGORIES
Bare conductor: CAT. III 300 V Insulated conductor: CAT. III 600 V
MI00615-1-EN
INSTALLATION MANUAL
3/4
USB PORT
The module is designed to exchange data according to the modes defined by the MODBUS protocol. It has a micro USB connector and can be configured using applications and/or software programs. The USB communication has priority over the RS485 communication. The USB serial port uses the following communication parameters: 38400,8,N,1 The USB communication port responds exactly like the RS485 port with the exception of the communication parameters. During the use of the USB port, the 485 bus will be inactive; it will reactivate automatically a few seconds after the release of the USB port. EASY SETUP is the software to use for the configuration. For further information go to the website on the cover.
SETTING THE DIP-SWITCHES
The position of the DIP-switches defines the Modbus communication parameters of the module: Address and Baud Rate. The following table shows the Baud Rate and Address values according to the DIP- SWITCH setting:
DIP-Switch status
DIP
DIP
ADDRESS
1 2 3 4
5 6
BAUD RATE
DIP
7
TYPE OF MEASUREMENT
DIP
8
MEASURING SCALES
#1
9600
AC/DC true RMS
Full scale
#2
19200
DC Bipolar
Half scale
#3 #…
38400 57600
DIP-switches must be set while the module is not powered on in order to avoid damaging it.
KEY
#14 The instrument is supplied configured for 100A (DCH100), 300A (DCH300) and 600A
#15
(DCH600), with 800 ms filter inserted and TRMS mode selected.
ON OFF
Note: When DIP switches 3 to 8 are OFF, the communication settings are taken from programming (EEPROM).
ELECTRICAL CONNECTIONS
ANALOGUE OUTPUT
DIGITAL OUTPUT
RS485 SERIAL PORT
Vcc
6 Vcc Vcc
6 Vcc Vcc
6 Vcc
5 GND
5 GND
5 GND
4 A+
4 A+
4 A+
3 B-
3 B-
3 B-
V
2 DO
LOAD
2 DO
2 DO
1 Vout
1 Vout
1 Vout
ANALOGUE OUTPUT BEHAVIOUR
AC/DC TRUE RMS
MODEL T201DCH100-OPEN T201DCH300-OPEN T201DCH600-OPEN
DIP7 DIP8 A
B
OFF OFF 50A 100A
OFF ON 25A 50A
OFF OFF 150A 300A
OFF ON 75A 150A
OFF OFF 300A 600A
OFF ON 150A 300A
DC BIPOLAR MODEL
T201DCH100-OPEN
T201DCH300-OPEN
T201DCH600-OPEN
DIP7 DIP8 C
D
ON OFF -100A +100A
ON ON -50A +50A
ON OFF -300A +300A
ON ON -150A +150A
ON OFF -600A +600A
ON ON -300A +300A
10
10
5
5
OUustciptuat ((VV)) OUustciptuat ((VV))
0
A
B
IngInrpeusst o(A(A) T) RTRMMSS
C
0
D
IngInrpeusst o(A(A) D) DCCBiBpioploalrar
MI00615-1-EN
INSTALLATION MANUAL
4/4