Frico Fcr-230 Room Controller Instructions

Frico Fcr-230 Room Controller Instructions

FRICO FCR-230 Room Controller Instructions
FRICO FCR-230 Room Controller

Note Icon Instruction for products with software version 1.2. Read this instruction before installation and wiring of the product. This product is BTL listed from software version 1.2-1-00 (BACnet stack 3.0.4).

Warning Icon Consult documentation in all cases where this symbol is used, in order to find out the nature of the potential hazards and any actions to be taken.

Room controller for controlling fan-coil units

FCR-230 is a room controller intended for controlling fan-coil heaters/ coolers and thermal actuators or 3-point actuators. Installation is directly on the wall or on an electrical connection box. The fan can be set to one of three speeds.
FCR-230 has change-over function and can be used for 2-pipe or 4-pipe systems.

For integration into a system, FCR-230 has communication via RS485 (Modbus, BACnet or EXOline). The device can be configured using the application Regio tool (version 1.3-1-05 or later), which can be downloaded from the Regin web site (www.regin.se).

Technical data

  • Supply voltage: 230 V AC ±10 %, 50/60 Hz
  • Power consumption: < 3 W
  • Ambient temperature: 0…50°C
  • Ambient humidity: Max 90 % RH
  • Storage temperature: -20…+70°C
  • Built-in temperature sensor: NTC type, range 0…50°C
  • Inputs: Refer to connection illustrations and table below
  • Outputs: Relays for fan control, 230 V AC, 3 A DO4, DO5 for actuators, Triac, 230 V AC, max. 300 mA
  • Communication RS485: Modbus, EXOline (using automatic detection/switching) or BACnet
  • Modbus: 8 bits, 1 or 2 stop bits. Odd, even (FI) or no parity
  • Communication speed: 9600, 19200, 38400 bps (EXOline, Modbus and BACnet) or 76800 bps (BACnet only)
  • Terminal blocks: Lift type for a maximum cable area 2.1 mm2
  • Protection class: IP20
  • Pollution degree: 2
  • Overvoltage category: 3
  • Material casing: Polycarbonate, PC
  • Dimensions: 102 x 120 x 29 mm

Installation

Place the controller in a location that has a temperature representative for the room. A suitable location is approx. 1.6 m above floor level in a place with unobstructed air circulation.
Depress the locking tab in the upper edge of the controller with a screwdriver. Carefully turn the screwdriver until the bottom plate and the electronics unit are slightly separated (see figure 1). Then use the cutout that becomes visible in the edge of the bottom plate to open the upper edge completely (see figure 2). Do the same thing in the lower edge of the controller.
Installation

Lift the electronics unit up from the bottom plate. The bottom plate with terminals has a number of hole combinations. Select suitable holes and fasten the bottom plate on the wall or connection box, so that the arrows on the bottom plate point upwards. Do not tighten the screws too hard!

Note: FCR-230 does not indicate fan breakdown or overheating of the heating coil. Therefore, all connections must be made externally. An overheating protection or similar can be used to disconnect the supply voltage.

Disconnection

FCR-230 should be connected to a switch or circuit breaker in the building installation. This switch should be in close proximity to the controller and within easy reach of the operator, and should be marked as the disconnecting device for the equipment.
Always use the circuit breaker to disconnect the controller from the mains supply during maintenance of the fan-coil and actuators.

Settings

Control modes

FCR-230 can control heating and cooling in sequence or be set to seasonal switching between heating and cooling (change-over, see below).

Change-over function

FCR-230 has an input for change-over that automatically resets the output DO4 to operate with heating or cooling function. When the controller is used together with a 3-position actuator, output DO5 is also affected by the change-over function in accordance with the above. A sensor of type PT1000 can be connected to the input and be mounted so that it senses the temperature on the supply pipe to the coil. When the temperature exceeds 28°C, the output function is set to heating and when the temperature drops below 16°C, the output is set to cooling. As an alternative, a potential-free contact can be used.
The input function can be set to NO/NC.
To ensure satisfactory functioning when using a sensor, the system must have continuous primary circuit circulation. When the changeover function is not used, the input must be left disconnected.
When using an electric heater and the change-over function is set to heating, the sequence of operation for FCR-230 will be heating/heating and DO5 will be activated first.
If a change-over sensor is not connected, the sequence will be heating/heating. If cooling is to be used in the sequence, parameter 2 (change-over mode) must be changed manually.

Operating mode

There are four different operating modes. Switching between these modes is performed locally.

Comfort: Icon is shown in the display. Heating and cooling have a smaller neutral zone NZC. An occupancy detector can be connected to the DI in order to select between Comfort and Economy. Switching between Comfort/Economy and Off can also be done via the On/Off button. Comfort/Economy is selected via the parameter list.

Economy (Standby): “Standby” is shown in the display. The heating and cooling setpoints are freely adjustable. Factory settings: heating=15°C, cooling=30°C.

Off: The controller does not heat or cool and the fan stops (unless mould protection has been selected or the cool-down function for the electric heater is running, in which case the fan will still run).

Window: Icon is shown in the display, the controller is off and the fan stops (unless mould protection has been selected or the cool-down function for the electric heater is running, in which case the fan will still run). The window contact is connected to the DI and must be configured.

Occupancy detection
Parameter 3 determines if the DI is window contact input or occupancy detection input. An occupancy detector can be connected to the DI in order to switch between Comfort and Economy mode.

Setpoint
The setpoint is set using the INCREASE and DECREASE buttons. Parameter 24 determines what is shown in the display. Refer to the parameter list for details.

Setpoint limitation
In parameters 34 and 35, it is possible to set the maximum allowed setpoint increase and decrease respectively.
Example: If P35=5 and P34=3, the setpoint can be changed between 17°C and 25°C (see the picture below).
The basic setpoint can be changed in parameter 64 (factory setting=22°C).
Setpoint limitation
Figure 3: Example of setpoint limitation

Fan control

The fan can be controlled via FCR-230 with the following modes: Low speed, Medium speed, High speed, Auto. The current fan speed in the Auto mode depends on the heating or cooling demand and the settings for each speed.
When using automatic control, ”AUTO” is shown in the display. The number of fan speed steps can be selected via parameter 30.
If the parameter is set to 1, the first fan speed step will be used for fan control.

Via parameter 31, it is possible to set the fan to the lowest speed level when Auto mode is selected. If this parameter is set to 1, the fan will run in all operating modes except Off and Window (unless mould protection is active or the cool-down function for the electric heater is running, in which case the fan will run in these modes as well).

Manual control of the fan speed
By pressing the fan button, you change the fan speed according to the sequence I→II→III→AUTO. When using manual control, ”MAN” is shown in the display.
If the fan has been configured not to be affected by the heating or cooling demand, ”AUTO” will not be shown when pressing the fan button.

Indications

The display has the following indications:

  • HEAT: Heating control
  • COOL: Cooling control
  • Icon:The open window symbol is shown if this function has been configured and a window is open.
  • OFF: The controller does not heat or cool

On/Off button
By pressing the On/Off button, FCR-230 will switch between Off mode and Comfort/Economy mode.

Parameter list

When the controller is in Comfort mode or Window mode, different parameter values can be set in a parameter list.
Hold the INCREASE and DECREASE buttons depressed simultaneously for about 5 seconds until the Service symbol is displayed and then  press the INCREASE button twice.
First the display will show parameter 1. Use the INCREASE and DECREASE buttons to scroll between the parameters and press the On/Off button to select the desired parameter. The parameter number will then be replaced by the parameter value. The value can be changed using the INCREASE and DECREASE buttons. If a button is held depressed the value will start scrolling, first slowly and then with increasing speed. To exit the parameter list and go back to the basic display, press the INCREASE button until “EXIT” is shown (one step before parameter 1) and press the On/Off button. You can also exit the parameter list by pressing down the INCREASE and DECREASE buttons simultaneously.

The following parameters can be changed in the parameter list.
Nº = parameter number
FS = factory setting
NO = normally open
NC = normally closed

Description

FS

1Control mode:
2=2-pipe system 3=4-pipe system
4=(Electric heater) N/A
3
2Change-over mode:
0=Heating control, 1=Cooling control, 2=Automatic change-over depending on analogue temperature sensor or digital input
0
3Operating mode when activating digital input 1, terminal 40/41:
0=Economy mode (occupancy detector)
1=Off mode (window contact)
0
4Mould protection: 0=Not active
1=Active (fan never stops)
0
5Neutral zone at Comfort mode (NZC). If the neu- tral zone is 2 K, the heating setpoint is equal to the setpoint minus 1 and the cooling setpoint is equal to the setpoint plus 1.0 K
6Heating setpoint when unoccupied15°C
7Cooling setpoint when unoccupied30°C
8P-band for the room controller10 K
9I-time for the room controller300 s
10Not used for this model
11Switch off timer for Comfort mode0 min
12Switch on delay for Comfort mode0 min
13Sensor connected to AI1, terminal 42/43: 0=Internal sensor, 1=External room sensor0
14Sensor connected to UI1, terminal 43/44: 0=None, 1=Change-over digital, 2=Change-over analogue0
15Type of digital actuator: 0=Thermal, 1=3-point0
16-

17

Not used for this model
18Period time for heating actuator with thermal actuator60 s
19Period time for cooling actuator with thermal actuator60 s
20Runtime for heating actuator with increase/decrease actuator120 s
21Runtime for cooling actuator with increase/decrease actuator120 s
22Time in hours between exercise of heating actuator23
23Time in hours between exercise of cooling actuator23
24Setpoint or actual value shown in the display: 0=Actual, setpoint when changing the setpoint, 1=Actual, setpoint adjustment when changing the setpoint, 2=Setpoint, 3=Only the setpoint adjustment0
25Configuration of fan control:
0=No control, 1=The fan is controlled by heating requirement, 2=The fan is controlled by cooling requirement, 3=The fan is controlled by heating and cooling requirement. When using an electric heater, this parameter should only be set to 1 or 3, or the heater may be overheated.
3
26Start signal in % of the controller output, heating or cooling, for fan speed 120 (5 when using an electric heater)
27Start signal in % of the controller output, heating or cooling, for fan speed 260
28Start signal in % of the controller output, heating or cooling, for fan speed 3100
29Hysteresis for start/stop of fans in % of the controller output. (N/A)5
30Number of fan speeds (N/A)3
31Fan speed in the Auto mode:
0=The fan speed follows the cooling/heating output, 1=The fan speed is minimum limited to the lowest speed
0
32Temperature compensation on AI10 K
33Temperature compensation for the internal room sensor0 K
34Highest permitted setpoint offset upwards. Set- table value=0…13 K. Starting point=22°C.13 K
35Highest permitted setpoint offset downwards. Set- table value=0…17 K. Starting point=22°C.17 K
36NO/NC digital input 1: 0=NO, 1=NC0
37NO/NC universal input 1: 0=NO, 1=NC0
38NO/NC digital output 4: 0=NO, 1=NC1
39NO/NC digital output 5: 0=NO, 1=NC1
40Manual/Auto heating output signal:
0=Off, 1=Manual, 2=Auto
2
41Manual/Auto cooling output signal:
0=Off, 1=Manual, 2=Auto
2
42Heating output signal in manual mode0
43Cooling output signal in manual mode0
44Model
45Version Major
46Version Minor
47Released or beta version
48Revision
49Display backlight low0
50Display backlight high30
51EXOline PLA address
52EXOline ELA address
53Modbus address254
54Modbus communication parity bit:
0=No parity, 1=Odd parity, 2=Even parity
2
55Modbus timeout for character (t1.5) in ms. Should be 1.5 times a character, i.e. at least 2 ms.2 ms
56Modbus answer delay (t3.5) in ms. Should be 3.5 times a character, i.e. at least 5 ms.5 ms
57Communication protocol: 0=EXOline/Modbus, 1=BACnet MS/TP0
58BACnet MS/TP MAC address
0-127=master address, 128-254=slave address
59The 4 low numbers in the BACnet device ID, 0-9999
60The 3 high numbers in the BACnet device ID
61BACnet MS/TP Max. master127
62Communication protocol speed:
0=9600 bps, 1=19200 bps, 2=38400 bps,
3=76800 bps (alternative 3 only applies to BAC- net)
0
63Resets communication parameters (not address- es) to their factory settings:
1=Factory settings (EXOline/Modbus@9600)
0
64Basic setpoint. Settable value=5…50°C.22°C

Recommended settings for Frico convectors:

TKW heatTKW coolTKW change over
20 (FS)1

2

14

0 (FS)0 (FS)2
310 (FS)0 (FS)

0 (FS)

SL/SLS R heatSL/SLS R coolSL/SLS R change over
20 (FS)1

2

14

0 (FS)0 (FS)2
3111

1

Wiring

Wiring Instruction
Figure 4: Bottom plate connections
Wiring Instruction
Figure 5: Connection diagram with water heater
Wiring Instruction
Figure 6: internal placement
Wiring Instruction
Figure 8: External placement

Connection of different actuators

When connecting thermal actuators, DO4 is used for heating actuators and DO5 for cooling actuators. If the installation is a 2-pipe installation and the change-over function is used, the actuator should be connected to DO4.

When connecting 3-point actuators, DO4 is used for increase signal and DO5 for decrease signal, even when the change-over function is used.

10L230 V AC LinePower supply
11Not connected
12N230 V AC NeutralPower supply (internally con-
nected to terminal 13)
13NFan-coil common /Common fan-coil connec-
230 V AC Neutraltor (internally connected to
terminal 12)
20DO1Fan-coil output 1Relay, 230 V AC*, 3 A
for fan control
21DO2Fan-coil output 2Relay, 230 V AC*, 3 A
for fan control
22DO3Fan-coil output 3Relay, 230 V AC*, 3 A
for fan control
30Not connected
31DO4Digital output 4 forDigital output. 230 V AC, max
heating/cooling300 mA. Max 2 A during 20
or opening withms.
3-point actuator
32CDO45Common DO4 & 5Common connection for
digital outputs 4 and 5
33DO5Digital output 5 forDigital output. 230 V AC, max
cooling or closing300 mA. Max 2 A during
with 3-point actua-20 ms.
tor.
40DIDigital inputPotential-free window contact
or occupancy contact. Con-
figurable for NO/NC.
41AgndAnalogue ground
42AIAnalogue inputExternal PT1000 instead of
the internal NTC
43UIUniversal inputChange-over input. Potential-
free switch (configurable for
NO/NC) or PT1000.
44AgndAnalogue ground
50AgndAnalogue ground
51Analogue out A0I EC fan
52Not connected
53ARS485 communication A
54BRS485 communication B

*The sum of the current through DO1-DO3 is protected by a fuse

Low Voltage Directive (LVD) standards / EMC emissions & immunity standards

This product conforms to the EMC and LVD requirements in the European harmonised standards EN 60730-1:2000 and EN 60730-2- 9:2002 and carries the CE mark.

RoHS

This product conforms to the Directive 2011/65/EU of the European Parliament and of the Council.
CE Icon

Contact

Frico AB, Industrivägen 41, 433 61 Sävedalen, Sweden
Tel: +46 31 336 86 00,
Fax: +46 31 26 28 60
www.frico.net,
[email protected]

Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH

Get In Touch
Icon Call: 0845 6880112
Icon Email: [email protected]

Logo

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals