CDT Outdoor Duct Temperature Sensor
CDT – Outdoor Duct Temperature Sensor
The CDT temperature sensor is designed to be mounted directly
onto the fresh air intake of the ventilation duct. It is used to
measure the outdoor air temperature accurately and relay the
information to the PCB board.
Installation Instructions
Follow the instructions below to install the CDT temperature
sensor correctly:
- Locate the temperature sensor near the fresh air intake for
accurate measurement. - Open the housing by removing the screw securing it
together. - Push the probe through the center hole and tighten the two
mounting screws. - Drill a 3/8 (8mm) hole in the duct and insert the probe into
the airstream. - Secure the sensor to the duct using two sheet-metal
screws. - Connect the signal wires to the sensor terminal strip.
- Connect the plug from the temperature probe to the PCB
board. - Close the cover and secure using the screw removed in step
2.
For wiring schematic, download the Condair Sensor Connect App.
The sensing probe is made of thermistor material, and its range is
from -40 to 40 degrees Celsius. The accuracy of the temperature
measurement is determined by the ambient temperature and humidity.
The setpoint limit for relative humidity ranges from 10% to 40% at
outdoor temperatures ranging from -40 to 0 degrees Celsius. The
outdoor duct temperature sensor has two wiring diagrams, one for
On/Off wall humidistat, and another for 0-10V wall humidistat.
CDT – Outdoor Duct Temperature Sensor
Outdoor Duct Temperature Sensor Installation Instructions
This document covers the operation and installation instructions for the following Condair outdoor duct temperature sensor: Kit No. Description 2520263 Outdoor Duct Temperature Sensor The Condair CDT temperature sensor can be used together with the following Condair Digital Humidity Controllers: Part No. Description 2597928 0-10V Digital Wall Humidistat 2520259 On/Off Digital Wall Humidistat 2597929 0-10V Digital Duct Humidistat pkg. 2520273 On/Off Digital Duct Humidistat pkg. 2597934 Digital Wall ON/OFF Humidistat pkg. 2597935 Digital Duct ON/OFF Humidistat pkg. The humidity controller used together with CDT temperature sensor reads the duct air temperature measured by the CDT temperature sensor and reduces the humidity control set point during cold weather operation to prevent condensation on windows and building structures:
1 Installation Instructions
Location: The Condair CDT temperature sensor is mounted directly onto the fresh air intake of the ventilation duct. Installation: Refer to installation overview in section 2. 1. Locate the temperature sensor near the fresh air intake. This will ensure accurate representation of the out-
door air temperature. 2. Open the housing by removing the screw securing the housing together. 3. Push the probe through the center hole and tighten the two mounting screws. 4. Drill a 3/8″ (8 mm) hole in the duct and insert the probe into the air steam. 5. Secure the sensor to the duct using two sheet-metal screws. 6. Connect the signal wires to the sensor terminal strip. Connect the plug from the temperature probe to the
PCB board. 7. Close the cover and secure using the screw removed in step 2.
Page 1
2605766-A EN 2304
2 Installation overview
A mm (inch)
Ø6 x 120/200 (Ø0.24 x 4.7/7.9)
36 (1.4)
B
64 (2.5)
CDT 2520263
64 (2.5)
(0.87 )
22
i AMC-1 AMC-2 C
2a
2b
D
1234
J2
54 (2.1)
60 (2.4)
35 (1.4)
2 3
6 (0.02)
40 (1.6) 45 (1.8)
6.5 (0.26)
4.2 (0.2)
© Condair Group AG, Switzerland
For Wiring Schematic: Get the Condair
Sensor Connect App
70-000252/20201208
Page 2
3 Product Specification
Sensing Probe
Environment Housing Material
Thermistor Type Range Accuracy Ambient Temperature Humidity Cover Mounting Plate Sensor Probe
Setpoint Versus Outdoor Temperature
10k NTC, Curve 24 -40° to 212° F (-40° to 100°C) ± 0.4 K AT 32°F (0°C) 40° to 212° F (-40° to 100°C) 95 %rH not condensing Fireproof ABS plastic Fireproof ABS plastic Stainless Steel
Setpoint Limit (rh)
40 30 20 10
-40 -35 -30 -25 -20 -15 -10 -5 0
5 °C
-40 -31 -22 -13 -4 5 14 23 32 41 °F Outdoor Temperature
Page 3
4 Wiring Diagrams
Wiring diagram CDT-CHR-NA CHR-NA
On/Off Wall Humidistat 2548731
1 234 567 8
Wiring diagram CDT-RCC-NA RCC-NA
0-10V Wall Humidistat 1510142
1 234 567 8
GND / 0V 24V N/A N/A N/A AO 0-10V N/A Temp. Reset
0V / GND 24V AC/DC DO1 DO1 DO2 DO2 RT RT
CDT
Outdoor Duct Temperature Sensor 2520263
1234
CDT
Outdoor Duct Temperature Sensor 2520263
1234