Condair Cot Outdoor Mount Temperature Sensor Instruction Manual

COT Outdoor Mount Temperature Sensor

Product Information: COT Outdoor Mount Temperature Sensor

The COT Outdoor Mount Temperature Sensor is a device used to
measure the outdoor air temperature. It is designed to work with a
humidity controller to reduce the humidity control set point during
cold weather operation, preventing condensation on windows and
building structures. The sensor conforms to EMC Standard 89/336/EEC
EMEI Standard 73/23/EEC EN 61 000-6-1/EN 61 000-6-3 and has a
degree of protection of IP 65 to EN 60 529. It has a safety class
of III (IEC 60536) and is made of fireproof PC + ABS plastic. The
device weighs 80g (2.8oz), and its dimensions are 33 x 60 x 50 mm
(1.3 x 2.4 x 2 in).

Product Usage Instructions: COT Outdoor Mount Temperature
Sensor Installation

  1. Choose an appropriate location for the sensor
    installation.
  2. Attach the base plate to the wall using screws or adhesive
    tape.
  3. Connect the sensing probe wires to the terminal connectors
    according to the wiring diagram provided in the manual.
  4. Insert the sensing probe into the cover until it snaps into
    place.
  5. Place the cover over the base plate and align the screw
    holes.
  6. Insert the cable through the cable gland and connect it to the
    circuit in the cover.
  7. Tighten the cable gland to secure the cable in place.
  8. Assemble the cover with the base plate, making sure that the
    seal in the seal groove of the cover is not damaged and in
    place.
  9. Tighten the four screws of the cover with moderate torque to
    complete the installation.

Note: For wiring schematic, get the Condair Sensor Connect
App.

COT – Outdoor Mount Temperature Sensor
Outdoor Mount Temperature Sensor Installation Instructions
This document covers the operation and installation instructions for the following Condair outdoor mount temperature sensor: Kit No. Description 2553858 Outdoor Mount Temperature Sensor The Condair COT temperature sensor can be used together with the following Condair Digital Humidity Controllers: Part No. Description 2597928 0-10V Digital Wall Humidistat 2520259 On/Off Digital Wall Humidistat 2597929 0-10V Digital Duct Humidistat pkg. 2520273 On/Off Digital Duct Humidistat pkg. 2597934 Digital Wall ON/OFF Humidistat pkg. 2597935 Digital Duct ON/OFF Humidistat pkg.
The humidity controller used together with COT temperature sensor reads the outdoor air temperature measured by the COT temperature sensor and reduces the humidity control set point during cold weather operation to prevent condensation on windows and building structures.
1 ­ Installation Instructions
Location: The COT temperature sensor must be installed on a flat vertical surface protected from direct sunlight and rain. Installation: Refer to the installation overview in section 2. 1. The cable gland must face downwards. 2. To install the sensor, remove cover. 3. Place seal and washer below the long mounting screw. Securely fix it to wall. 4. Thread wires through cable gland or conduit connector 5. Connect the wires, normally 18 ga unshielded twisted pair, according to the wiring diagram to the measuring
circuit in the cover 6. Tighten cable gland. 7. Assemble the cover with the base plate. Make sure the seal in the seal grove of the cover is not damaged
and in place. 8. Tighten the four screws of the cover with moderate torque to complete the installation.
Page 1

2605768-A EN 2304

2 ­ Installation overview

A mm (inch)

B

36 (1.4)

64 (2.5)

COT 2553858

64 (2.5)

22 (0.87)

C
3

2a 2b

40 (1.6)

54 (2.1) 54 (2.1)

40 (1.6)

i AMC-1 6 (0.02)
© Condair Group AG, Switzerland

D
SOD-Tn

1234 J2
2 3

For Wiring Schematic: Get the Condair
Sensor Connect App
70-000178/20201214
Page 2

3 ­ Product Specification

Sensing Probe Connection Standards
Environment General

Thermistor: Accuracy: -40…0°C (-40…32°F): 0…50°C (32…122°F): 50…100°C (122…212°F):

NTC 0.5C 0.2C 0.5C

Terminal Connectors

For wire AWG 24…12

Conforms according to EMC Standard 89/336/EEC EMEI Standard 73/23/EEC

EN 61 000-6-1/EN 61 000-6-3

Product Standards Automatic electrical controls for household and EN 60 730 ­ 1 similar use Special requirements on temperature dependent EN 60 730 ­ 2- 9 controls

Degree of protection

IP 65 to EN 60 529

Safety Class

III (IEC 60536)

Operation Temperature Humidity

IEC 721-3-3 -40…100°C (-40…212°F) 95 %rH not condensing

Materials Dimensions Cover: (HxWxD) Weight (including package)

Fire proof PC + ABS plastic 33 X 60 X 50 mm (1.3 x 2.4 x 2 in) 80 g (2.8 oz)

Setpoint Versus Outdoor Temperature

Setpoint Limit (rh)

40 30 20 10
-40 -35 -30 -25 -20 -15 -10 -5 0

5 °C

-40 -31 -22 -13 -4 5 14 23 32 41 °F Outdoor Temperature

4 – Wiring Diagrams
Wiring diagram COT-CHR-NA
CHR-NA
On/Off Wall Humidistat 2548731

COT
Outdoor Mount Temperature Sensor 2553858

0V / GND 24V AC/DC DO1 DO1 DO2 DO2 RT RT

1 234 567 8

1234

Page 3

Wiring diagram COT-RCC-NA RCC-NA
0-10V Wall Humidistat 1510142
1 234 567 8

GND / 0V 24V N/A N/A N/A AO 0-10V N/A Temp. Reset

COT
Outdoor Mount Temperature Sensor 2553858
1234

Page 4