RDC-NA Dehumidification 0-10V Digital Wall Humidistat
RDC-NA – Dehumidification, 0-10V Digital Wall Humidistat
Dehumidification, 0-10V Digital Wall Humidistat Installation Instructions
This document covers the operation and installation instructions for the following Condair digital humidistat: Kit No. Description 2602797 0-10 V Digital Wall Humidistat
1 Mounting and Installation
Location: Mount the humidity controller Condair RDC-NA in a protected and easy accessible place at least 1.5 m above the floor to the wall (mounting on flush-mounting or surface-mounting box). Observe the following placement notes: Do not place Condair RDC-NA in niches, behind, curtains, etc. Do not place the Condair RDC-NA near heat sources, within the area with direct air draft or direct sunlight. Installation: Refer to installation overview in section 2. 1. Open the screw of the housing and remove mounting plate with the connecting unit. 2. Connect wires of the connection cable to the terminals according to the wiring diagram. 3. At the place of location fix mounting plate (plastic screw facing downwards) with two screws to the flush-mount-
ing or wall-mounting box (see dimensional drawing). 4. Carefully snap housing onto the mounting plate and fix it with the screw (do not tighten screw too much). Note: We recommend using 18-gauge wire, and maximum <100 ft distance from the unit.
Page 1
2605771-A EN 2304
2 Installation overview
A mm (inch)
16(0.6) 32 (1.2)
B
73 (2.9)
RDC-NA 2602797
113 (4.5)
C 58 (2.3)
D
50 (2.0)
2
58 (2.3)
15 (0.6) 83 (3.25) +/- 5 (0.2)
1 2 34 5678
E
1 2 34 5678
6 (0.02)
0V / GND 24V N/A N/A N/A AO 0-10V N/A Temp. Reset
1
12345678
1: 0V / GND 2: 24 V AC/DC ±10% 3: Do not connect 4: Do not connect 5: Do not connect 6: 0…10VDC 7: Do not connect 8: Temp. Reset
© Condair Group AG, Switzerland
For Wiring Schematic:
Get the Condair Sensor Connect App
70-000248/20201214
Page 2
3 Wall Humidistat LCD Display
Actual humidity in %rH
Set humidity setpoint in %rH
°C/°F
%
Output active Control buttons
Buttons /
Operation press long
press briefly press long press briefly press briefly press long
Function
Switching On and Off
Switching between °C and °F Adjusting set point value Shows %rH value Offset settings
Fig. 1: Wall Humidistat LCD Display and function of control buttons
4 Configuration
Using keypad, set specified humidity. For general health and comfort, a humidity setting of 50% is recommended.
5 Error Messages
Err 1:
Sensor element in the device is not properly inserted or defective. Insert the sensor element correctly or replace it.
Err2, 3 & 4: Hardware or memory problem. Replace device.
6 Sensor Calibration
Sensor inputs can be calibrated if needed
Press > 2 sec. UI and its value is displayed.
Press Press
: Calibration value and tool symbol is displayed, UP/DOWN to calibrate,
: Save calibration, tool symbol disappears.
Press UP key again to step through the next active input Note: disable inputs will not be shown
75% UI 1
0.0% ..UI 1
Page 3
7 Setting Parameters to Configure the Controller
The control operation is defined by parameters set using the standard operation terminal. There are two levels: User/display parameters (password 0009) Control parameters (password 00241)
How to change the parameters: 1. Press < >/< > button simultaneously for three seconds. The display will show firmware version and revision
number.
2. Press the < > button to start login. The small digits show “CODE”. 3. Select correct code (password) using < > and < > buttons.
Note: Code to access user parameters is “0009”. The access codes are fixed and cannot be changed. 4. Press the < > button after selecting the correct code. 5. Once logged in with “0009”, the user/display parameters are displayed immediately. 6. Select the parameters with the < > or < > button. Change a parameter by pressing the < > button. The
symbol is displayed to indicate that the parameter may be modified. Use < > or < > button to adjust the value.
7. After you are done, press < > button to save the new value and return to the selection level (symbol disappears after selection is saved). Pressing < > button without pressing < > button will discard the value and return without saving.
8. Press the < > button to leave the menu. The unit will return to normal operation if no button is pressed for more than 5 minutes.
User Parameters (Password 0009)
Table 1: User Parameters
Parameter UP 00 UP 01 UP 02
UP 03 UP 04
Description Enable change of operation modes
Enable change of setpoints
State after power failure: 0 = Switched OFF, 1 = Switched ON, 2 = state before power failure Celsius or Fahrenheit: ON = Fahrenheit, OFF = Celsius
Select type of content for large digits (00= OFF): 01 = Input 02 = Setpoint 03 = Humidity Sensor 04 = External Temperature Sensor
Range ON, OFF ON, OFF
0, 1, 2
ON, OFF 00…04
Default ON (Enabled) ON (Enabled)
2
OFF (Celsius) 01
Control Parameters (Password 0241) Note: Only experts should change these settings! See user parameter for login procedure! Table 2: Output Configuration
Parameter CP 00 CP 01 CP 02
CP 03
Description Minimum setpoint limit in humidification mode Maximum setpoint limit in humidification mode Start delay for fans (Time the fan runs before control output starts) Stop delay for fan (Time the fan keeps running after control output stops)
Range 0..100% 0..100% 0…255 s
0…255 s
Default 10% 90% 10 s
90 s
Page 4
Table 3: Temperature Setback Configuration *For humidity control only
Parameter Description
CP 04
Enable temperature setback OFF = Temperature set back is disabled ON =Temperature setback is enabled
CP 05
Setpoint limit at full setback
CP 06
Lower temperature limit: Outside temperature with maximum setback The setback will be equal to the minimum setpoint limit
CP 07
Upper temperature limit: Outside temperature at begin of setback
CP 08
Number of seconds taken into account to calculate the average input signal Low value = fast response High value = slow response
Range ON, OFF
0..100 % -40…60°C -40…160°F
-40…60°C 40…160°F
0…100
Default OFF
20 % -30 °C (-22°F)
0 °C (32°F) 30
8 Product Specification
Power Supply
Operating Voltage Power Consumption Terminal Connections
Sensor Probe (Humidity Sensor)
Measuring element Range Accuracy Hysteresis Repeatability Stability
Signal Outputs Environment General
Analog Outputs Analog Signal Resolution Maximum Load
Operation Temperature Humidity
Housing Materials Mounting Plate Weight (including packaging)
24 V AC 50/60 Hz ± 10 %, 24 VDC ± 10 % Max. 3 VA For wires 0.34…2.5 mm2 (AWG 24…12)
Capacitive measuring element 0…100 % RH ± 3.0 % at 25 °C ± 1% ± 0.1% < 0.5% / Year
AO1 0…10 VDC or 0…20mA 39 mV or 0.0078 mA 10 mA (at 0…10 VDC) 20 mA (at 0…20mA)
IEC 721-3-3 0…50°C 32…122°F) 95 %rH not condensing
ABS Galvanized Steel 260 g (9.2oz)
Page 5
Page 6
On/Off Humidity Controller Input
GND Humidity Transducer Signal RH (0-10V)
GND Humidity Controller Signal 0-10V
+24V
Remote Fault Indication (24 V, 1 Amp max.)
RA Fan Modulation Control
RA Fan Input Variable Speed J5 Constant Speed
1 234 567 8 Factory Jumper
DA 1 2 3 4 5 6 7 8 9 10 11 12
GND / 0V 24V N/A N/A N/A AO 0-10V N/A Temp. Reset
RDC-NA
0-10V Wall Humidistat 2602797
9 Wiring Diagrams
Wiring diagram RDC-NA for DA