Condair Rdc-na Dehumidification 0-10v Digital Wall Humidistat Instruction Manual

RDC-NA Dehumidification 0-10V Digital Wall Humidistat

RDC-NA – Dehumidification, 0-10V Digital Wall Humidistat
Dehumidification, 0-10V Digital Wall Humidistat Installation Instructions
This document covers the operation and installation instructions for the following Condair digital humidistat: Kit No. Description 2602797 0-10 V Digital Wall Humidistat
1 ­ Mounting and Installation
Location: Mount the humidity controller Condair RDC-NA in a protected and easy accessible place at least 1.5 m above the floor to the wall (mounting on flush-mounting or surface-mounting box). Observe the following placement notes: ­ Do not place Condair RDC-NA in niches, behind, curtains, etc. ­ Do not place the Condair RDC-NA near heat sources, within the area with direct air draft or direct sunlight. Installation: Refer to installation overview in section 2. 1. Open the screw of the housing and remove mounting plate with the connecting unit. 2. Connect wires of the connection cable to the terminals according to the wiring diagram. 3. At the place of location fix mounting plate (plastic screw facing downwards) with two screws to the flush-mount-
ing or wall-mounting box (see dimensional drawing). 4. Carefully snap housing onto the mounting plate and fix it with the screw (do not tighten screw too much). Note: We recommend using 18-gauge wire, and maximum <100 ft distance from the unit.
Page 1

2605771-A EN 2304

2 ­ Installation overview

A mm (inch)
16(0.6) 32 (1.2)

B
73 (2.9)

RDC-NA 2602797

113 (4.5)

C 58 (2.3)

D
50 (2.0)

2

58 (2.3)

15 (0.6) 83 (3.25) +/- 5 (0.2)

1 2 34 5678

E
1 2 34 5678
6 (0.02)

0V / GND 24V N/A N/A N/A AO 0-10V N/A Temp. Reset

1

12345678

1: 0V / GND 2: 24 V AC/DC ±10% 3: Do not connect 4: Do not connect 5: Do not connect 6: 0…10VDC 7: Do not connect 8: Temp. Reset

© Condair Group AG, Switzerland

For Wiring Schematic:
Get the Condair Sensor Connect App

70-000248/20201214

Page 2

3 ­ Wall Humidistat LCD Display
Actual humidity in %rH
Set humidity setpoint in %rH

°C/°F

%

Output active Control buttons

Buttons /

Operation press long
press briefly press long press briefly press briefly press long

Function
Switching On and Off ­­­
Switching between °C and °F Adjusting set point value Shows %rH value Offset settings

Fig. 1: Wall Humidistat LCD Display and function of control buttons

4 ­ Configuration
Using keypad, set specified humidity. For general health and comfort, a humidity setting of 50% is recommended.

5 ­ Error Messages

Err 1:

Sensor element in the device is not properly inserted or defective. Insert the sensor element correctly or replace it.

Err2, 3 & 4: Hardware or memory problem. Replace device.

6 ­ Sensor Calibration
Sensor inputs can be calibrated if needed

Press > 2 sec. UI and its value is displayed.

Press Press

: Calibration value and tool symbol is displayed, UP/DOWN to calibrate,
: Save calibration, tool symbol disappears.

Press UP key again to step through the next active input Note: disable inputs will not be shown

75% UI 1
0.0% ..UI 1

Page 3

7 ­ Setting Parameters to Configure the Controller
The control operation is defined by parameters set using the standard operation terminal. There are two levels: ­ User/display parameters (password 0009) ­ Control parameters (password 00241)
How to change the parameters: 1. Press < >/< > button simultaneously for three seconds. The display will show firmware version and revision
number.
2. Press the < > button to start login. The small digits show “CODE”. 3. Select correct code (password) using < > and < > buttons.
Note: Code to access user parameters is “0009”. The access codes are fixed and cannot be changed. 4. Press the < > button after selecting the correct code. 5. Once logged in with “0009”, the user/display parameters are displayed immediately. 6. Select the parameters with the < > or < > button. Change a parameter by pressing the < > button. The
symbol is displayed to indicate that the parameter may be modified. Use < > or < > button to adjust the value.
7. After you are done, press < > button to save the new value and return to the selection level (symbol disappears after selection is saved). Pressing < > button without pressing < > button will discard the value and return without saving.
8. Press the < > button to leave the menu. The unit will return to normal operation if no button is pressed for more than 5 minutes.

User Parameters (Password 0009)

Table 1: User Parameters

Parameter UP 00 UP 01 UP 02
UP 03 UP 04

Description Enable change of operation modes
Enable change of setpoints
State after power failure: 0 = Switched OFF, 1 = Switched ON, 2 = state before power failure Celsius or Fahrenheit: ON = Fahrenheit, OFF = Celsius
Select type of content for large digits (00= OFF): 01 = Input 02 = Setpoint 03 = Humidity Sensor 04 = External Temperature Sensor

Range ON, OFF ON, OFF
0, 1, 2
ON, OFF 00…04

Default ON (Enabled) ON (Enabled)
2
OFF (Celsius) 01

Control Parameters (Password 0241) Note: Only experts should change these settings! See user parameter for login procedure! Table 2: Output Configuration

Parameter CP 00 CP 01 CP 02
CP 03

Description Minimum setpoint limit in humidification mode Maximum setpoint limit in humidification mode Start delay for fans (Time the fan runs before control output starts) Stop delay for fan (Time the fan keeps running after control output stops)

Range 0..100% 0..100% 0…255 s
0…255 s

Default 10% 90% 10 s
90 s

Page 4

Table 3: Temperature Setback Configuration ­ *For humidity control only

Parameter Description

CP 04

Enable temperature setback OFF = Temperature set back is disabled ON =Temperature setback is enabled

CP 05

Setpoint limit at full setback

CP 06

Lower temperature limit: Outside temperature with maximum setback The setback will be equal to the minimum setpoint limit

CP 07

Upper temperature limit: Outside temperature at begin of setback

CP 08

Number of seconds taken into account to calculate the average input signal Low value = fast response High value = slow response

Range ON, OFF
0..100 % -40…60°C -40…160°F
-40…60°C 40…160°F
0…100

Default OFF
20 % -30 °C (-22°F)
0 °C (32°F) 30

8 ­ Product Specification

Power Supply

Operating Voltage Power Consumption Terminal Connections

Sensor Probe (Humidity Sensor)

Measuring element Range Accuracy Hysteresis Repeatability Stability

Signal Outputs Environment General

Analog Outputs Analog Signal Resolution Maximum Load
Operation Temperature Humidity
Housing Materials Mounting Plate Weight (including packaging)

24 V AC 50/60 Hz ± 10 %, 24 VDC ± 10 % Max. 3 VA For wires 0.34…2.5 mm2 (AWG 24…12)
Capacitive measuring element 0…100 % RH ± 3.0 % at 25 °C ± 1% ± 0.1% < 0.5% / Year
AO1 0…10 VDC or 0…20mA 39 mV or 0.0078 mA 10 mA (at 0…10 VDC) 20 mA (at 0…20mA)
IEC 721-3-3 0…50°C 32…122°F) 95 %rH not condensing
ABS Galvanized Steel 260 g (9.2oz)

Page 5

Page 6

On/Off Humidity Controller Input
GND Humidity Transducer Signal RH (0-10V)
GND Humidity Controller Signal 0-10V
+24V
Remote Fault Indication (24 V, 1 Amp max.)

RA Fan Modulation Control

RA Fan Input Variable Speed J5 Constant Speed

1 234 567 8 Factory Jumper
DA 1 2 3 4 5 6 7 8 9 10 11 12

GND / 0V 24V N/A N/A N/A AO 0-10V N/A Temp. Reset

RDC-NA
0-10V Wall Humidistat 2602797

9 ­ Wiring Diagrams
Wiring diagram RDC-NA for DA