Blue Jay Bj-mcm2403-v Multi Channel Circuit Metering System User Manual

BJ-MCM2403-V Multi Channel Circuit Metering System

Multi-channel Circuit Metering System BJ-MCM2403-V User
Manual

Version 1.4

Tel: +0086-023-67628702

Website: www.cqbluejay.com

Address: 1802, Building 2, No.88, Jianxin East Road, Chongqing,
400020, China

Email: [email protected]

Product Information

The BJ-MCM2403-V Series Multi-Channel Circuit Metering System is
a compact and robust metering solution that provides reliable
monitoring of building electrical loads with a low installation
cost-per-point by combining submetering. The unit performs
real-time metering, measures energy consumption, multi-tariff
time-of-use (TOU), and monitors power quality of 4 channels
circuits for three-phase circuits.

The MCM2403-V Series has advanced communication options,
including Modbus via RS485, I/O communications, providing for
extensive reliable data exchange. Multiple units can be connected
together to meter an unlimited number of circuits. The versatility
of the MCM400 meters is ideal for multi-tenant or departmental
metering applications within office towers, condominiums, apartment
buildings, shopping centers, and other multi-user environments.

Specifications

The BJ-MCM2403-V Series Multi-Channel Circuit Metering System
has the following specifications:

  • Real-time metering of 4 channels circuits for three-phase
    circuits
  • Measures energy consumption and multi-tariff TOU
  • Monitors power quality
  • Advanced communication options including Modbus via RS485, I/O
    communications
  • Multiple units can be connected together to meter an unlimited
    number of circuits

Product Usage Instructions

Before using the BJ-MCM2403-V Series Multi-Channel Circuit
Metering System, carefully read the user manual and fully
understand the implications and correct guidance of operations in
accordance with the user manual. This will help you make better use
of the DC Energy Meter and help to solve various problems at the
scene.

Follow these instructions when using the meter:

  1. Before turning on the power supply, ensure that the power
    supply is within the provisions of the instrument.
  2. During installation, ensure that the current input terminal is
    non-open and voltage input terminals are non-short circuit.
  3. Ensure that the instrument wiring is consistent with the
    internal system settings.
  4. When communicating with the PC, ensure that instrument
    communication parameters are consistent with the PC.

Please read the user manual carefully and save this document for
future reference.

If you have any questions or concerns about the BJ-MCM2403-V
Series Multi-Channel Circuit Metering System, please contact us
at:

Tel: +0086-023-67628702

Website: www.cqbluejay.com

Address: 1802, Building 2, No.88, Jianxin East Road, Chongqing,
400020, China

Email: [email protected]

User Manual
Multi-channel Circuit Metering System BJ-MCM2403-V User Manual
Version1.4

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:[email protected]

Read me

User Manual

When you use BJ-MCM2403-V Series Multi-Channels Circuit Metering system, be sure to carefully read this user manual, and be able to fully understand the implications, the correct guidance of operations in accordance with user manual, which will help you make better use this DC Energy Meter, and help to solve the various problems at the scene.
1. Before the meter turning on the power supply, be sure that the power supply within the provisions of the instrument;
2. When installation, the current input terminal must non-open, voltage input terminals must Nonshort circuit;
3. Be sure the instrument wiring consistent with the internal system settings;
4. When communicating with the PC, instrument communication parameters must be consistent with the PC

Please read this user manual carefully Please save this document

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:[email protected]

Directory

User Manual

CONTENTS

Page

1. – SUMMARIZE………………………………………………………………………………………………………………… – 3 –
2. – SPECIFICATIONS ………………………………………………………………………………………………………… – 4 –
3.- INSTALLATION AND START-UP……………………………………………………………………………………. – 6 3.1.- INSTALLATION ……………………………………………………………………………………………………………. – 6 3.2. – CONNECTION TERMINAL OF MCM400 ……………………………………………………………………………. – 7 –
4. – SETUP PROCEDURE …………………………………………………………………………………………………… – 8 4.1. – KEY OPERATION ………………………………………………………………………………………………………… – 8 4.2. – SHOW ELECTRIC PARAMETERS……………………………………………………………………………………… – 8 4.3.- PARAMETERS SETTING………………………………………………………………………………………………. – 10 4.4. – MENU STRUCTURE…………………………………………………………………………………………………….- 11 –
5. – COMMUNICATION PROTOCOL ………………………………………………………………………………….. – 13 5.1. – CONNECTION FOR THE RS485 BUS ……………………………………………………………………………. – 13 5.2. – MODBUS © PROTOCOL……………………………………………………………………………………………. – 14 5.3. – REGISTER ADDRESS TABLE ……………………………………………………………………………………….. – 15 –
6. – SAFETY CONSIDERATIONS ………………………………………………………………………………………. – 19 –
7. – MAINTENANCE………………………………………………………………………………………………………….. – 19 –

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:[email protected]

1. – SUMMARIZE

User Manual

The MCM2403-V Series provides a compact and robust metering solution, enable reliable monitoring of building electrical loads with a low installation cost-per-point by combining submetering. The unit performs real-time metering, measures energy consumption, multi-tariff time-ofuse (TOU) and monitors power quality of 4 channels circuits for three phase circuits.
Advanced communications options including Modbus via RS485, I/O communications provide for extensive reliable data exchange. Multiple units can be connected together to meter unlimited number of circuits. The versatility of MCM400 meters are ideal for multi-tenant or departmental metering applications within office towers, condominiums, apartment buildings, shopping centers and other multi-user environments.
Measurement Function
Voltage: Line Voltage; Phase Voltage Current: Total Current; Current per channel Power and Power Factor: Total power Reactive Power, Apparent Power, Power Factor and for per channel Frequency: System Frequency
Energy Function
Energy (kWh) measurement meeting international standards, accuracy is Class 1.0. It optional Time of Use feature: 12 Seasons, 4 Tariffs record, max three-month data for each channel.
Over/Under Limit Alarming
Users can select parameters and set their set points. An alarm will be triggered when the set point is reached, user can get the info from MODBUS reading.
Power Quality Analysis
Optional power quality parameters such as voltage and current THD, Odd harmonic distortion (Total Odd HD), even harmonic distortion (Total Even HD), 2 ~ 21 times the harmonic content, Current Kfactor (KF), crest factor (CF), telephone interference factor (THFF), voltage and current unbalance etc.
Communication and Network
Supports RS485 communication open protocol: Modbus RTU;

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:[email protected]

2. – SPECIFICATIONS

User Manual

Reference standard: IEC60688-2012 IEC62053-21:2003 GBT 22264.1-2008 (IEC61557-12)

Accuracy standards

Parameter

Accuracy

A phase

B phase

C phase

Voltage

0.2

Current

0.2

Active Power

0.5

Reactive Power

0.5

Apparent power

0.5

Power Factor

0.5

Active Energy

1

Reactive Energy

2

Frequency

0.1

Va Aa1-12 Wa1-12 vara1-12 VAa1-12 PFa1-12

Vb Ab1-12 Wb1-12 varb1-12 VAb1-12 PFb1-12

Vc Ac1-12 Wc1-12 varc1-12 VAc1-12 PFc1-12

Notes: final metering accuracy depends one sampling CT and PT accuracy

All
W1-12 var1-12 VA1-12 PF1-12 Wh1-12 varh1-12 Hz1-12

Input Voltage: Rated 20~380V (need confirm before order) Current: Rated ../100mA (optional ../0.333V, need confirm before order) Frequency: 40-65Hz

Overload Current: 1.2 times rated continuous; 5 seconds for 10 times the rated Voltage: 1 seconds for 2 times the rated

Dielectric strength Standard IEC 61010-1 2kV AC RMS 1 minute, between input / output / case / power supply

EMC Test
Electrostatic discharge immunity test: Electrical fast transient burst immunity test
Surge (Shock) immunity test

standard
IEC-61000-4-2 level 4 IEC61000-4-4 level 3
IEC61000-4-5 level 3

Test voltage 8Kv
Input 1kV; Power supply 2kV
common mode test voltage 2kV

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:[email protected]

Work environment Temperature: -15C~ +55C Humidity: RH 20%~95% (No condensation)
Storage Conditions Temperature: -30C~+70C Humidity: RH 20%~95%
Working Power AC/DC 85-265V, 45-65Hz Maximum power consumption 3W
Dimensions L × H × D =105X104X61.75mm

User Manual

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:[email protected]

3.- INSTALLATION AND START-UP

User Manual

The manual you hold in your hands contains information and warnings that the user should respect in order to guarantee a proper operation of all the instrument functions and keep its safety conditions. The instrument must not be powered and used until its definitive assembly is on the cabinet’s door.
Whether the instrument is not used as manufacturer’s specifications, the protection of the instrument can be damaged.
When any protection failure is suspected to exist (for example, it presents external visible damages),the instrument must be immediately powered off. In this case contact a qualified service representative.
3.1.- Installation
Mounting
Instrument is to be mounted on 35mm Din-rail. Keep all connections inside the cabinet.
Note that with the instrument powered on, the terminals could be dangerous to touch and cover opening actions or elements removal may allow accessing dangerous parts. Therefore, the instrument must not be used until this is completely installed.

Notes:
Auxiliary power:
MCM2403-V meter with AUX power input, if not for a special statement, we provide the 85265VAC/DC power interface for standard products. Please ensure that the auxiliary power match meter access to prevent damage to the product.

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:[email protected]

3.2. – Connection terminal of MCM400

User Manual

Notes:

Meter use foolproof design, access terminal uses different styles block:

Terminal Current sampling
Voltage sampling
AUX sampling Digital output terminal
RS485 COMM

Size 3.81mm
7.62mm
5.08mm 5.08mm
3.81mm

Style 6pin
4pin
2pin 3pin
3pin

The current input pin need to access the CT, and output signal of CT is 0-100mA or 0~0.333V, CT access have polarity to power direction. Please confirm your ordering meter types and prepare related CT.

Digital output is passive load, inside relay can drive max 250VAC(3A)/30VDC(3A) load, please make sure connected load do not exceed this capacity.

Wiring diagram may be changed due to the special requirements of customers’ order, please refer the label on the rear part.

If you are or sure or signs unclear, please contact:

Blue Jay Technical Support: [email protected]

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:[email protected]

4. – SETUP PROCEDURE

User Manual

4.1. – Key operation

“” or “” Screen switch or value increase/decrease

“SET”

Menu enters or exit

“”

Enter next menu or confirm the change

4.2. – Show electric parameters
When the MCM400 in monitor screen, user can use keypad switch shows the electrical parameters, press “” to switch another screen in this channel, press “” to switch parameter for channel 1-4 press ” ” to switch more details parameter in screen screen roller logic as following:

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:[email protected]

CH1:Voltage Ua 000.0 V Ub 000.0 V Uc 000.0 V

CH1: Amp Ia 0.000 A Ib 0.000 A Ic 0.000 A

CH1:All Power Pz 0000 W Qz 0000 var Pfz 0.000

CH1:Fequency Fr 00.00 Hz

User Manual
CH1:Split Pow Pa 0000 W Pb 0000 W Pc 0000 W

CH1:Voltage Uab 000.0 V Ubc 000.0 V Uca 000.0 V

CH1:Split Pow Pfa 0.000 Pfb 0.000 Pfc 0.000
CH1:Ep C:+ 00000.000kWh
C:- 00000.000 kWh

CH1:Split Pow Sa 0000 VA Sb 0000 VA Sc 0000 VA

CH1:Split Pow Qa 0000 var Qb 0000 var Qc 0000 var

CH1:Ep B:+ 00000.000kWh
B:- 00000.000kWh

CH1:Ep A:+ 00000.000kWh
A:- 00000.000kWh

CH1:Ep Z:+ 00000.000kWh
Z:- 00000.000kWh

CH1:Eq C:+00000.000kvarh
C:-00000.000kvarh

CH1:Eq B:+00000.000kvarh
B:-00000.000kvarh

CH1:Eq A:+00000.000kvarh
A:-00000.000kvarh

CH1:Eq Z:+00000.000kvarh
Z:-00000.000kvarh

CH1:Harm A 000.0% B 000.0%
ITEHD C 000.0%

CH1:Harm A 000.0% B 000.0%
ITOHD C 000.0%

CH1:Harm A 000.0% B 000.0%
ITHD C 000.0%

CH1:Harm A 000.0% B 000.0%
UTEHD C 000.0%

CH1:Harm A 000.0% B 000.0%
UTOHD C 000.0%

CH1:Harm A 000.0% B 000.0%
UTHD C 000.0%

CH1:Harm-U (%)Ua Ub Uc 20 00.0 00.0 00.0 21 00.0 00.0 00.0

CH1:Harm-U (%)Ua Ub Uc 06 00.0 00.0 00.0 07 00.0 00.0 00.0

CH1:Harm-U (%)Ua Ub Uc 04 00.0 00.0 00.0 05 00.0 00.0 00.0

CH1:Harm-U (%)Ua Ub Uc 02 00.0 00.0 00.0 03 00.0 00.0 00.0

CH1:Harm-I (%)Ua Ub Uc 20 00.0 00.0 00.0 21 00.0 00.0 00.0

CH1:Harm-I (%)Ua Ub Uc 06 00.0 00.0 00.0 07 00.0 00.0 00.0

CH1:Harm-I (%)Ua Ub Uc 04 00.0 00.0 00.0 05 00.0 00.0 00.0

CH1:Harm-I (%)Ua Ub Uc 02 00.0 00.0 00.0 03 00.0 00.0 00.0

CH1:DO DO1

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:[email protected]

4.3.- Parameters Setting

User Manual

The SETUP procedure of the MCM2403-V is performed by means of several SETUP options. When into the SETUP, use the keyboard to select different options and enter required variables:

Press the key SET can enter the parameter setting. the screen ask access password (Default is

0001), then press

can enter the menu.

The operation menu logic as following:

Input set Line: 3P4L Voltage 0220V Amp: 0.100A
Input set PT: 0001 CT1: 0050 CT2: 0050
Input set CT3: 0050 CT4: 0050

Menu 01Input set 02Bus set 03Alarm set
Bus set Address 001 Baud rate 9600 Data form n.8.1

Alarm set Alarm-1 Alarm-2 Alarm-3
Alarm set Alarm-4 Alarm-5

Alarm-1 ModeOFF Delay 000.1S Parameter Ua
Alarm-1 Value 5500 Hysteresis 0050 Channel CH1

Menu 04Relay set 05System set

Relay Set Do-1
Do-1 Mode Remote Time 001.0S

System Set Password 0001 Display MAN Blacklight 5 mi
System Set Clear Energy Contrast 5

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:[email protected]

4.4. – Menu Structure

User Manual

level 1
Input Setting
Comm Setting
Alarm Setting
Digital output
System Settings

Level 2 Wiring mode Rated volt Rated amp PT ratio CT of CH1 CT of CH2 CT of CH3 CT of CH4 Address Baud Rate Check format
Alarm_1…5
DO
Password Display Backlight

Level 3 3P4L/3P3L2CT/3P3
L3CT 220V 333mV Last time set value Last time set value Last time set value Last time set value Last time set value 1~247 2400 / 4800 / 9600 / 19200 n.8.1 / o.8.1 / e.8.1
Mode
Delay Parameter
Value
hysteresis Related channel
Mode
Time
0~9999 MAN
Number 1~9 1~5

Level 4
1~9999 1~9999 1~9999 1~9999 1~9999
/ / / OFF / Upper Limit / Lower Limit / Ua/Ub/Uc/Uab/Ubc…
0~9999
0~9999 CH1-4 Remote Alarm_1…5
ON OFF
Default 001.0sec / /
/

Description
input signal network measurement
Default setting, cannot be modified
Default setting, cannot be modified
Default 0001 Default 0050 Default 0050 Default 0050 Default 0050 Default 0001
Default is 9600
Factory default (n.8.1)
Total three mode
Alarm triggered time delay, Default 001.0s
Alarm triggered parameters
Default is 5500,value related to secondary side
parameters, unit: Volte – 0.1V; Amp – 0.001A;
Active power – 0.1W; Reactive power – 0.1VAR;
Power factor – 0.001; Frequency – 0.01HZ;
Default is 0050
Default CH1
Remote for RS485 control Alarm_1…5 related to alarm
setting ON/OFF are forced
act/release In Alarm act for delay time, in remote control mode for
pulse time
Reset user password
Manual switching, or automatic switching in
1~9sec LCD backlight duration, unit
is min, default is 5

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:[email protected]

Clear Contrast

Energy 1~9

User Manual

/

Clear the record in meter

/

LCD display contrast, default is 5

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:[email protected]

5. – COMMUNICATION PROTOCOL
5.1. – Connection for the RS485 BUS

User Manual

The composition of the RS-485 cabling must be carried out with a meshed screen cable (minimum 3 wire), diameter of not less than 0.5mm2, with a maximum distance of 1,200 m between the BJ194… and the master unit. This Bus may connect a maximum of 32 BJ194…

Note: 1. For communication with the master unit, customers can choose the RS-232 to RS-485 converter to use
2. Full range of BJ-… meter RS485 PIN number is 58,59,60
3. Due to product modifications or custom requirements, the interface pin place may be changed. For details, please refer to product label on the rear board

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:[email protected]

5.2. – MODBUS © protocol
Modbus RTU Frame Format:

Address code Function code

1 BYTE 1 BYTE

Data code

4 BYTE

Error Check code

2 BYTE

User Manual
Slave device address 1-247 Indicates the function codes like read coils / inputs Starting address, high byte Starting address, low byte Number of registers, high byte Number of registers, low byte Cyclical Redundancy Check ( CRC )

MODBUS FUNCTIONS

Code:

Meaning:

FUNCTION 03

Reading of n Words

FUNCTION 06

Preset single Registers

Description: This function permits to read all the electrical parameters of the BJ194…series. Write value in to the relevant register

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:[email protected]

5.3. – Register Address Table

User Manual

5.3.1- Basic Power Data–Primary Side (Read only)

Address

Data

Byte mode

Instruction

0

CH1_Ua

2

CH1_Ub

4

CH1_Uc

6

CH1_Uab

8

CH1_Ubc

10

CH1_Uca

12

CH1_Ia

14

CH1_Ib

16

CH1_Ic

18

CH1_Pa

20

CH1_Pb

22

CH1_Pc

24

CH1_P

26

CH1_Qa

28

CH1_Qb

30

CH1_Qc

32

CH1_Q

34

CH1_Sa

36

CH1_Sb

38

CH1_Sc

40

CH1_S

42

CH1_PFa

44

CH1_PFb

46

CH1_PFc

48

CH1_PF

50

CH1_FR

52

CH1_EpZ+

54

CH1_EpZ-

56

CH1_EqZ+

58

CH1_EqZ-

60

CH1_EpA+

float

2

float

2

Channel_1 Phase to Line Voltage, Unit: V

float

2

float

2

float

2

Channel_1 Phase to Phase Voltage, Unit: V

float

2

float

2

float

2

Channel_1 Three phase Current, Unit: A

float

2

float

2 Channel_1 Individual phase active

float

2 power,

float

2 Unit: kW

float

2

Channel_1 Total active power, Unit: kW

float

2

float

2

Channel_1 Individual phase reactive power, Unit: kVar

float

2

float

2

Channel_1 Total reactive power, Unit: kVar

float

2

float

2

Channel_1 Individual apparent power, Unit: kVA

float

2

float

2

Channel_1 Total apparent power, Unit: kVA

float

2

float

2

Channel_1 Individual power factor, 0~1.000

float

2

float

2

Channel_1 Total power factor, 0~1.000

float

2

Channel_1 Frequency, Unit:0.01Hz

float

2

Channel_1 Total positive active energy, Unit: kWh

float

2

Channel_1 Total negative active energy, Unit: kVarh

Channel_1 Total positive reactive

float

2 energy,

Unit: kVarh

Channel_1 Total negative reactive

float

2 energy,

Unit: kWh

Channel_1 A phase positive active

float

2 energy,

Unit: kWh

Status R R R R R R R R R R R R R R R R R R R R R R R R R
R
R
R
R
R
R

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:[email protected]

User Manual

Channel_1 A phase negative active

62

CH1_EpA-

float

2 energy,

R

Unit: kVarh

Channel_1 A phase positive reactive

64

CH1_EqA+

float

2 energy,

R

Unit: kVarh

Channel_1 A phase negative reactive

66

CH1_EqA-

float

2 energy,

R

Unit: kWh

Channel_1 B phase positive active

68

CH1_EpB+

float

2 energy,

R

Unit: kWh

Channel_1 B phase negative active

70

CH1_EpB-

float

2 energy,

R

Unit: kVarh

Channel_1 B phase positive reactive

72

CH1_EqB+

float

2 energy,

R

Unit: kVarh

Channel_1 B phase negative reactive

74

CH1_EqB-

float

2 energy,

R

Unit: kWh

Channel_1 C phase positive active

76

CH1_EpC+

float

2 energy,

R

Unit: kWh

Channel_1 C phase negative active

78

CH1_EpC-

float

2 energy,

R

Unit: kVarh

Channel_1 C phase positive reactive

80

CH1_EqC+

float

2 energy,

R

Unit: kVarh

Channel_1 C phase negative reactive

82

CH1_EqC-

float

2 energy,

R

Unit: kWh

100-182 CH2_parameter float

2

Channel_2 parameter, structure refer to Channel_1

R

200-282 CH3_parameter float

2

Channel_3 parameter, structure refer to Channel_1

R

300-382 CH4_parameter float

2

Channel_4 parameter, structure refer to Channel_1

R

5.3.2- Meter status data

Address

Data

Byte mode

Instruction

Status

1200

Digital output

int

1

0: without act 1: active for trig

R

1202

Alarm

int

1

0: without alarm 1: Alarm trigged Bit 0~4 show Alarm_1~5 status

R

0: Remote control

1: Related to Alarm_1

1203(R/ W)

DO working mode

int

2: Related to Alarm_2 1 3: Related to Alarm_3
4: Related to Alarm_4

R/W

5: Related to Alarm_5

6: trig to closed

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:[email protected]

1204
1240
1241 1242 1243 1244 1245 1246 1247

DO time delay int

Wiring mode

int

Voltage range int

Current range int

PT ratio

int

CT of CH1

int

CT of CH2

int

CT of CH3

int

CT of CH4

int

7: trig to opened

User Manual

In alarm mode: 0.0-999.9sec

1

In remote control mode: 0 for Level output:

R/W

other value for pulse width 0.1-999.9sec

0: 3P4W

1 1: 3P3W-2CT

R

2: 3P3W-3CT

1 Unit: V

R

1 Unit: 333mV

R

1 Range: 1-9999

R

1 Range: 1-9999

R

1 Range: 1-9999

R

1 Range: 1-9999

R

1 Range: 1-9999

R

5.3.3 – Voltage harmonic (max 21th)

Address

Data

Byte mode

1300 1301 1302

THDUa THDUb THDUc

int

1

int

1

int

1

1303

TOHDUa

int

1

1304

TOHDUb

int

1

1305

TOHDUc

int

1

1306

TEHDUa

int

1

1307

TEHDUb

int

1

1308

TEHDUc

int

1

1320-1339 HUa

int

20

1340-1359 HUb

int

20

1360-1379 HUc

int

20

Instruction
A-phase Voltage THD, unit 0.1%
B-phase Voltage THD
C-phase Voltage THD
A-phase Voltage odd harmonic total distortion, unit 0.1% B-phase Voltage odd harmonic total distortion C-phase Voltage odd harmonic total distortion A-phase Voltage even harmonic total distortion, unit 0.1% B-phase Voltage even harmonic total distortion C-phase Voltage even harmonic total distortion A phase voltage harmonic ratio for 2 to 21th, unit 0.1% B phase voltage harmonic ratio for 2 to 21th C phase voltage harmonic ratio for 2 to 21th

Status R R R R
R
R
R
R
R
R
R
R

5.3.4 – Current harmonic (max 21th)

Address

Data

Byte mode

1400

THDIa1

int

1

1401 1402

THDIb1 THDIc1

int

1

int

1

1403

TOHDIa1

int

1

Instruction
Channel_1 A-phase Current THD, unit 0.1% Channel_1 B-phase Current THD
Channel_1 C-phase Current THD Channel_1 A-phase Current odd harmonic total distortion, unit 0.1%

Status
R R R R

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:[email protected]

1404

TOHDIb1

int

1405

TOHDIc1

int

1406

TEHDIa1

int

1407

TEHDIb1

int

1408

TEHDIc1

int

1420-1439 HIa1

int

1440-1459 HIb1

int

1460-1479 Hic1

int

1500-1579 CH2 Harmonic int

1600-1679 CH3 Harmonic int

1700-1779 CH4 Harmonic int

User Manual

1

Channel_1 B-phase Current odd harmonic total distortion

R

1

Channel_1 C-phase Current odd harmonic total distortion

R

1

Channel_1 A-phase Current even harmonic total distortion, unit 0.1%

R

1

Channel_1 B-phase Current even harmonic total distortion

R

1

Channel_1 C-phase Current even harmonic total distortion

R

20

Channel_1 A phase Current harmonic ratio for 2 to 21th, unit 0.1%

R

20

Channel_1 B phase Current harmonic ratio for 2 to 21th

R

20

Channel_1 C phase Current harmonic ratio for 2 to 21th

R

20

Channel_2 harmonic value, structure refer to Channel_1

R

20

Channel_3 harmonic value, structure refer to Channel_1

R

20

Channel_4 harmonic value, structure refer to Channel_1

R

5.3.5 ­ Special operation

Address 3000

Data
Reset energy counter

Byte mode

int

1

Instruction
Send code 0x0A0A (DEC 2570) to clear all the energy counter

Status W

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:[email protected]

6. – SAFETY CONSIDERATIONS

User Manual

All installation specification described at the previous chapters named: INSTALLATION AND STARTUP, INSTALLATION MODES and SPECIFICATIONS.
Note that with the instrument powered on, the terminals could be dangerous to touching and cover opening actions or elements removal may allow accessing dangerous parts. This instrument is factory-shipped at proper operation condition.

7. – MAINTENANCE

The MCM2403-V does not require any special maintenance. No adjustment, maintenance or repairing action should be done when the instrument open and powered on, should those actions are essential, high-qualified operators must perform them.
Before any adjustment, replacement, maintenance or repairing operation is carried out; the instrument must be disconnected from any power supply source.
When any protection failure is suspected to exist, the instrument must be immediately put out of service. The instrument’s design allows a quick replacement in case of any failure.

Tel: +0086-023-67628702 www.cqbluejay.com Add: 1802,Building 2,No.88,Jianxin East Road,Chongqing,400020,China

Email:[email protected]

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals