10X Line Electrified Bored Lock
Product Information
The 10X Line Electrified Bored Lock is an electric lock with an
8-pin connector and a pigtail harness for easy installation. It
comes with fail-safe and fail-secure options that can be configured
using the DIP switch. The lock requires a 12VDC or 24VDC regulated
and filtered power supply and can handle load currents of up to 1A.
The minimum permissible wire size to be used shall not be less than
26 AWG. The product may contain lead which is known to the state of
California to cause cancer and birth defects or other reproductive
harm.
Product Usage Instructions
- Refer to Template 4756 (and also 4753 if BHW trim) for door
preparation. Use door marker provided with lock to verify
dimensions. - Configure the lock for fail-safe or fail-secure using the DIP
switch. Move the switch to the desired position and power cycle
after changing switch position. - Wire the lock by following Figure 2 and the wiring diagram in
Figure 3. Make sure to use the appropriate wire gauge and minimum
permissible wire size. - Install the lock on the door and verify that it is functioning
properly. - Wire the request-to-exit switch by following the wiring diagram
in Figure 4. - Test the lock and request-to-exit switch to ensure proper
functionality.
Installation Instructions
10X Line
Electrified Bored Lock
1 Installation Notes
· Doors manufactured by ASSA ABLOY Group Companies are available pre-wired with ElectroLynx® connectors. · Wire colors are consistent with all ASSA ABLOY products. · Doors without ElectroLynx connectors will have to be hard wired. · For Non ElectroLynx Connector System Door:
» Install available Retrofit Harness and use with ElectroLynx Hinge. » Follow installation instructions for ElectroLynx Connector System. · For Non ElectroLynx Connector System Door and Hinge: » Remove connector on lock. » Use proper crimp splices or wire nuts in accordance with local code for terminating connections. » Lock is polarity sensitive. · The system shall not be installed in fail secure mode unless permitted by the local authority having jurisdiction and shall not interfere with the operation of Listed panic hardware. · Power shall be by UL294 and ULC-60839 Class 2 Power Limited power supplies or Listed Access Control units. · ULC-60839-11-1 – Grade 1 and Environmental class: indoor only. · UL294 access control performance levels (Endurance Level IV, Line Security Level I, Attack Level I, Power Standby Level I). · Wiring methods shall be in accordance with the National Electrical Code (ANSI/NFPA70), CSA 22.1, Canadian Electrical Code (CEC), Part I, Safety Standard for Electrical Installations, local codes and the authorities having jurisdiction.
2
Electrical Specifications
· Operating voltage range: 10.2VDC to 26.4VDC
· Current draw: 10mA continuous. · Peak current draw: 500mA.
Wire Gauge Chart
Total One-Way Length of Wire
Run (ft)
100 150 200 250
12VDC Load Current @ 12VDC
1/2A
1A
18
14
16
12
14
12
14
10
24 VDC Load Current @ 24VDC
1/2A
1A
20
18
18
16
18
14
16
14
Note: The minimum permissible wire size to be used shall not be less than 26 AWG. When calculating voltage drop, use 0.5A as the recommended current draw.
WARNING
This product can expose you to lead which is known to the state of California to cause cancer and birth defects or other reproductive harm. For more information go to www. P65warnings.ca.gov.
WARNING
Attention Installer: Improper installation may result in damage to the product and void the factory warranty.
1-800-727-5477 · www.sargentlock.com
Copyright © 2022-2023, SARGENT Manufacturing Company. All rights reserved. Reproduction in whole or in part without the express written permission of SARGENT Manufacturing Company is prohibited. Patent pending and/or patent www.assaabloydss.com/patents.
A8351 03/23
10X Line
Electrified Bored Lock Installation Instructions
3 Door Preparation
Refer to Template 4756 (and also 4753 if BHW trim) for door preparation. Use door marker provided with lock to verify dimensions.
4
Verify / Configure Lock for Fail Safe or Fail Secure
Locks are configurable for Fail Safe or Fail Secure applications, locate dip switch as shown below. Dip switch can only be accessed prior to lock installation. · Power cycling is required after changing switch position.
DIP Switch for Fail Safe or Fail Secure
Figure 1
FAIL SAFE
FAIL SECURE
MOVE THE DIP SWITCH TO THE POSITION DESIRED. POWER CYCLE AFTER CHANGING SWITCH POSITION.
1-800-727-5477 · www.sargentlock.com
Copyright © 2022-2023, SARGENT Manufacturing Company. All rights reserved. Reproduction in whole or in part
without the express written permission of SARGENT Manufacturing Company is prohibited. Patent pending and/or patent www.assaabloydss.com/patents.
2
A8351 03/23
10X Line
Electrified Bored Lock Installation Instructions
5 Installation
Install lock per instruction sheet A8286 (or A8334 if BHW trim), provided with lock. See Figure 2. 1. Plug the 8-pin connector from the lock into the 8-pin connector for the wiring harness thru the door. 2. Plug the 8-pin connector from the door harness into the 8-pin hinge connector. 3. Connect the hinge connector to the transformer or power supply. Caution: Verify that the correct voltage and polarity is being used. The voltage must not exceed 30VDC. If voltage exceeds this value, the lock may be damaged. Lock is polarity sensitive. 4. Test lock · Fail Secure applying power unlocks · Fail Safe applying power locks
Figure 2
Note: Typical door harness location is shown. Other locations may exist depending on door type.
3
Red (+), 2 Black (-), 1
To transformer or power supply
Pigtail Harness (QC2 shown) 2-wire with 8-pin connector
Yellow Blue Green Red (+) Black (-) White Orange Brown
2
1
Red, 2 Black, 1
Lock with 8-pin connector.
Lock polarity is sensitive.
8- wire QC8 Electric Hinge with 8-pin connector
Door harness with 8- and 4-pin connectors. 4-pin connector is not used.
1-800-727-5477 · www.sargentlock.com
Copyright © 2022-2023, SARGENT Manufacturing Company. All rights reserved. Reproduction in whole or in part
without the express written permission of SARGENT Manufacturing Company is prohibited. Patent pending and/or patent www.assaabloydss.com/patents.
3
A8351 03/23
6 Wiring Diagram
12VDC or 24VDC Regulated and Filtered
Power Supply
Input
L N
120VAC GND 60HZ
120VAC L/N/G
+ – +-
Output 1 Output 2
Normally Closed Fire Alarm Contact
Switch or relay contacts
(if required)
NO
C
NC
Figure 3
Pigtail Harness (QC2 shown) 2-wire with 8-pin connector
Red (+), 2 Black (-), 1
Plug into 8-pin hinge connector at door
7
Request to Exit Switch Wiring Diagram
12/24VDC Input Power
87 65
43 21
PPINPININ53O4WRGAHRNIETGEENE (+) PIN 2 RED
(-) PIN 1 BLACK
NOTE: RX SWITCH MONITORS INSIDE HANDLE
NC
C
RX SWITCH
NO
Figure 4
1-800-727-5477 · www.sargentlock.com
Copyright © 2022-2023, SARGENT Manufacturing Company. All rights reserved. Reproduction in whole or in part without the express written permission of SARGENT Manufacturing Company is prohibited. Patent pending and/or patent www.assaabloydss.com/patents.
A8351 03/23