And Ad-8552eip Ethernet Ipconverter Instruction Manual

And Ad-8552eip Ethernet Ipconverter Instruction Manual

AND LOGOAD-8552EIP Ethernet/IP Converter
Instruction Manual

AD-8552EIP Ethernet IP Converter

This manual and Marks
All safety messages are identified by the following, “WARNING” or “CAUTION”, of ANSI Z535.4 (American National Standard Institute: Product Safety Signs and Labels). The meanings are as follows:

warning 2 WARNINGA potentially hazardous situation which, if not avoided, could result in death or serious injury.
warning 2 CAUTIONA potentially hazardous situation which, if not avoided, may result in minor or moderate injury.

warning 2This is a hazard alert mark.

  • This manual is subject to change without notice, at any time, to improve the product.
  • The contents of the product specifications and this manual are subject to change without any obligation on the part of the manufacturer.
  • Under the copyright laws, the software (program) described in this manual is copyrighted, with all rights reserved.
    The software may be installed into one computer and may not be installed into other computers without the prior written consent of A&D Company, Limited. Copying includes translation into another language, reproduction, conversion, photocopy and offer or loan to another person.

Introduction

Thank you for purchasing the AD-8552EIP Ether Net/IP converter.
Please read this manual completely before using the AD-8552EIP.

1-1 Features
The AD-8552EIP converts the RS-232C communications of the weighing device into Ether Net/IP.

  • The measurement value can be reset to zero (re-zero) by operation from the host (PLC or PC).
  • hen connected to an AD-4212C and AD-4212D, etc., it is possible to change the response speed, perform calibration with an external weight, and supply power from the weighing device.
  • The hooks on the back of the AD-8552EIP allow one-touch mounting on a DIN rail.

AND AD 8552EIP EtherNet IPConverter - FIGURE 1

1-2 Cautions
Before use, confirm the following articles for safe operation.

  • Grounding The Converter
    Be sure to ground this converter.
    Separate this earth ground line from others, like ground line of a motor, inverter or a power source. Unless the converter is grounded, it may result in receiving an electric shock, cause operation error or catch fire.
  • Proper Power Source And Power Cable
    Confirm the AC voltage, frequency and power tolerance of the power cable (refer to “4. Power Terminal”). If the voltage range of the cable is lower than the power line voltage, it may cause leakage or catching fire. Use pole compression terminals to connect the power cable to the terminals.
  • Splashing Water
    The module is not water-resistant type.
  • Flammable Gas
    Do not install the converter where flammable gas is present.
  • Heat Radiation Of The Module
    Space out instruments to radiate heat sufficiently.
    Do not use in an environment where the ambient temperature exceeds the operating temperature range [-10℃ to +50℃, 85% RH or less (no condensation)].
    This unit is covered with a transparent plastic protective cover at the time of shipment.
    After installing and connecting, be sure to remove the protective cover before turning on the power.
    If it is used without removing the protective cover, this unit will overheat.
    The protective cover is for preventing the entry of wire scraps and the like during installation and connecting.
    Do not remove it until installation and connecting are complete.

AND AD 8552EIP EtherNet IPConverter - FIGURE 2

Composition and Names

2-1 AD-8552EIP

AND AD 8552EIP EtherNet IPConverter - FIGURE 3

2-2 Accessories

  • Simplified instruction manual

Specifications

Voltage requirement24 VDC external power supply [+ 10%, -15%]
Power requirement9W Max (When power is supplied to 4 units such as AD-4212C)
Communication interface: Ether Net/IP interface CT18 compliant (For connection with external devices)
Refer to “5-1 Ether Net/IP specifications”
:RS-232C interface (For connection to weighing device)
Refer to “6-1 RS-232C specifications”
Communication connectorRJ-45 modular connector (For Ether Net/IP interface)
D-Sub 9 pin (male) (For RS-232C interface)
Operating condition0℃ to + 50℃, Max 85% RH (no condensation)
External dimensions105 (W) x 112 (H) x 103 (D) mm
MassApproximately 440g

3-1 Dimensions

AND AD 8552EIP EtherNet IPConverter - FIGURE 4

3-2 Applicable models
■ Functions available for each model, accessories needed for connection to AD-8552EIP .

AND AD 8552EIP EtherNet IPConverter - FIGURE 5

⋆1.If the weighing device does not have an auto power-on function or auto-start function, it is necessary to turn on the display or each weighing device by key operation after turning on the power.
⋆2.The AD4212D has two types of RS-232C connectors. Connect the display connector and the RS-232C connector of AD-8552EIP . (Do not use the PLC connector.)
⋆3.Some functions (calibration error flag) cannot be used.

Power Terminal

4-1 Power-supply voltage
Connect a constant voltage of external power supply (+ 10% -15%) within the range of 24 VDC to the DC power input terminal of the AD-8552EIP.
Caution

  • Do not use at a voltage exceeding the rated voltage range (24 VDC +10%-15%)
    • Doing so may cause failure or heat generation.
    • This unit may not operate normally.
  • Ground the FG terminal of the switching power supply used for the power supply of this unit.

● The power line of this unit should be dedicated for this unit, and be separate from other drive devices.
・If strong noise is generated from the power line of another device, this unit may be damaged.
・This unit may not start normally due to the inrush current of other drive devices.
・Depending on the circuit configuration of this unit, other drive devices may not operate normally.
● Select a switching power supply capacity of approximately 9W per unit for the dedicated power supply line for this unit.
・If the power capacity is insufficient, this unit may not operate normally.
■Connector: DC power input terminal

AND AD 8552EIP EtherNet IPConverter - FIGURE 6

Signal nameDescription
DC+Power supply 24V input
0VPower supply 0V input
FGFunctional Ground

4-2 Connecting example
To insert or remove the wire, press the button part of the connector with a screwdriver or the like.
Modifying the tip of the wire with a bar-type crimp terminal or the like recommended.

AND AD 8552EIP EtherNet IPConverter - FIGURE 7

Connection conductor specifications

Clamping range (rating)0.20 mm2 to 1.5 mm2
Applicable wireAWGAWG24   to AWG16
Solder plated wire0.2 mm2 to 1.5mm2
Stranded wire0.2 mm2 to 1.5mm2
Bar crimp terminal DIN46228 Part10.25 mm2 to 1.5mm2
Bar crimp terminal (With color) DIN46228 Part40.25 mm2 to 0.75 mm2
Length8mm

Ether Net/IP Interface

5-1 Ether Net/IP specifications
■ Connector(RJ-45 modular connector)

AND AD 8552EIP EtherNet IPConverter - FIGURE 8

Pin No.MDI⋆1MDI-X⋆1
1TD+RD+
2TD-RD-
3RD+TD+
4
5
6RD-TD-
7
8
Housing

RD:Receive data(Input)
TD:Send data(Output)
⋆1.AD-8552EIP is compatible with Auto MDI-X / MDI. The LAN cable can be used either straight or cross.
■ Communication specifications

Communication standardEtherNet/IP (CT18 compliant)
Vender ID188:A&D Company Limited
Device type43 (0x2B):Generic Device
Communication functionCyclic communication (Implicit message)
Message communication (Explicit message)
IP address setting methodDIP switch, WEB interface
Transmission speed10/100Mbps ( Autonegotiation)
Communication methodFull duplex / half duplex ( Autonegotiation)
Connection formStar connection, daisy chain connection
Connection cableShielded twisted pair cable (STP)
Straight / Cross, category 5e and above

5-2 Connections

AND AD 8552EIP EtherNet IPConverter - FIGURE 9

⋆1.LAN cable is not included. Please use a commercially available product.

RS-232C Interface

6-1 RS-232C specifications
■ Connector (D-Sub9 pin, male)

AND AD 8552EIP EtherNet IPConverter - FIGURE 10

Pin No.SignalDirectionDescription
1(Vs)OutputOutput of power supply 0V ⋆1
2RXDInputInput data
3TXDOutputOutput data
4N.C.
5SGSignal ground
6N.C.
7N.C.
8N.C.
9(Va)OutputOutput of power supply 12V ⋆1
ShellShield

⋆1.When connected to specific weighing device such as AD-4212C / AD-4212D, Weighing device can be operated by supplying power from the AD-8552 EIP.(Refer to “3-2 Applicable models”)
■ Communication specifications

ItemSetting
Baud rate [SW-3, 4  No.1 to 4]2400*, 9600, 19200, 38400bps
Data bit7 bit (fixed)
ParityEVEN (fixed)
Stop bit1 bit (fixed)
Terminator<CR><LF> (fixed)
CodeASCII

6-2 Connecting cable
Connect with a cable applicable to the individual weighing device. Refer to “3-2. Applicable models”.
■ Connection diagram(When connected to a weighing device.)

AND AD 8552EIP EtherNet IPConverter - FIGURE 11

*1. Depending on the weighing device, RXD and TXD may be shown on the opposite side (weighing device output: RXD, weighing device input: TXD)
*2.May vary depending on the weighing device.

Switch

  • Set the parameters required for communication using the AD-8552EIP switches (SW-1 to 5).

Caution

  • f the setting is changed, be sure to turn on the power off and on again of AD-8552EIP.
    When the power is turned on, the switch status is read and applied to operations.

7-1 How to operate the switch 

AND AD 8552EIP EtherNet IPConverter - FIGURE 12

7-2 Factory setting
The switch status and settings at the factory setting are as follows. Refer to “7-3. Ether Net/IP switching settings”
“7-4. RS-232C function settings” for the settings that need to be changed.

AND AD 8552EIP EtherNet IPConverter - FIGURE 13

ItemFactory setting valueSwitch status at factory setting
IP address (4th octet)2SW-1:0SW-2:2
RS-232C(CH1) baud rate2400SW-3 No1:0SW-3 No2:0
RS-232C(CH2) baud rate2400SW-3 No3:0SW-3 No4:0
RS-232C(CH3) baud rate2400SW-4 No1:0SW-4 No2:0
RS-232C(CH4) baud rate2400SW-4 No3:0SW-4 No4:0
No FunctionSW-5 No1:0
Fixed decimal point functionAUTOSW-5 No2:1SW-5 No3:1SW-5 No4:1

7-3 EtherNet/IP switching settings

■IP address setting
The IP address allocation can be set within the following range by using the switch (SW-1, 2).
[ 192.168.0.1 ] to [ 192.168.0.254 ], [ 192.168.1.10 ]
(To set an IP address other than the above, refer to “10-4 Network setting screen”.)

SW-1SW-2IP address
00Becomes the address set on WEB interface, “10-4. Network setting screen”.
01[ 192.168.0.1 ]
02[ 192.168.0.2 ]
n1n2[ 192.168.0. ( n1×16 + n2×1 ) ]
FE[ 192.168.0.254 ]
FF[ 192.168.1.10 ]

<Setting example>

AND AD 8552EIP EtherNet IPConverter - FIGURE 14

Caution

  • Please consult with your network administrator before connecting to a network.
  • Set the IP address so that it does not overlap with other devices.

7-4 RS-232C function settings

■ Communication setting
SW-3

CH1: RS-232C Baud RateSetting stateSetting stateCH2: RS-232C Baud rate
2400 bpsAND AD 8552EIP EtherNet IPConverter - ICON 1AND AD 8552EIP EtherNet IPConverter - ICON 12400 bps
9600 bpsAND AD 8552EIP EtherNet IPConverter - ICON 2AND AD 8552EIP EtherNet IPConverter - ICON 29600 bps
19200 bpsAND AD 8552EIP EtherNet IPConverter - ICON 3AND AD 8552EIP EtherNet IPConverter - ICON 319200 bps
38400 bpsAND AD 8552EIP EtherNet IPConverter - ICON 4AND AD 8552EIP EtherNet IPConverter - ICON 438400 bps

AND AD 8552EIP EtherNet IPConverter - FIGURE 15

SW-4

CH3: RS-232C Baud RateSetting stateSetting stateCH4: RS-232C Baud Rate
2400 bpsAND AD 8552EIP EtherNet IPConverter - ICON 1AND AD 8552EIP EtherNet IPConverter - ICON 12400 bps
 9600 bpsAND AD 8552EIP EtherNet IPConverter - ICON 2AND AD 8552EIP EtherNet IPConverter - ICON 29600 bps
 19200 bpsAND AD 8552EIP EtherNet IPConverter - ICON 3AND AD 8552EIP EtherNet IPConverter - ICON 319200 bps
38400 bpsAND AD 8552EIP EtherNet IPConverter - ICON 4AND AD 8552EIP EtherNet IPConverter - ICON 438400 bps

AND AD 8552EIP EtherNet IPConverter - FIGURE 16

7-5 Fixed decimal point function

  • The digits (decimal point position) of the weight value data of EtherNet/IP can be fixed.
  • If the connected weighing device has a smart range function, the number of digits after the decimal point is automatically changed.
    If you want to fix the number of digits, use the fixed decimal point function.

Example of storage format with fixed decimal point function(Example of CH1)

Weighing device output value (CH1)Setting of decimal point positionAD-8552EIP internal data
Weighing value
Instance100:byte 0 to 3
[ CH1 Weighing value ]
Decimal point position
Instance100:byte 6 to 7
[ CH1 Decimal point position ]
123.456g2123452
31234563
AUTO※11234563
123.45g2123452
31234503
AUTO※1123452

SW-5 No.2 to No.4

AND AD 8552EIP EtherNet IPConverter - FIGURE 17

⋆1 Depending on the output of the weighing device, the number of digits stored in the weighing value
(Instance100:byte 0 to 3, 18 to 21, 36 to 39, 54 to 57) and the decimal point position (lnstance100:byte 6 to 7, 24 to 25, 42 to 43, 60 to 61) are automatically switched.

LED (status, error display)

POWER ◯ ◯ ERR
MS ◯ ◯ NS

DisplayFunctionColorStatus
POWERPower onGreen litThe AD-8552EIP is powered on.
ERRErrorRed litThere is something wrong with the AD-8552EIP.
MSModule StatusOffThe AD-8552EIP is not powered on.
Green litIt is working normally.
Green blinkNot initialized.
Red litAn unrecoverable failure has occurred.
Red blinkA recoverable failure has occurred.
NSNetwork StatusOffThe AD-8552EIP is not powered on.
Green litThe Ether Net/IP connection is established.
Green blinkThe Ether Net/IP connection is not established.
Red blinkOne or more connections have timed out.

Communication in Ether Net/IP

  • When an Ether Net/IP connection is established between the AD-8552EIP and the PLC, data is periodically communicated by cyclic data. Cyclic data consists of “9-2 Output data” and “9-3 Input data”.
  • Weighing values can be read and zero reset (rezero) is possible.
  • If you are using the following models, you can calibrate (Sensitivity adjustment) via Ether Net/IP.
    When calibrating with a weighing device other than the following models, operate with the keys of the weighing device while looking at the display of the measuring instrument.
Applicable modelSensitivity adjustment  methodOutline of procedure
AD-4212CExternal weight ⋆1While monitoring the balance status with the Input data(Instance100), it is necessary to instruct data acquisition by Output data(Instance150) and to load and unload the weight on the weighing instrument.
AD-4212DExternal weight ⋆1
Built-in weightAfter instruction by Output data(Instance150), the Input data (Instance100) monitors until calibration is completed.

⋆1.When changing the weight value to be used, refer to the instruction manual of the individual weighing device.

9-1 Preparing for communication
1. Set the following setting items so that the RS-232C of the weighing instrument and AD-8552EIP are the same.
Reference: AD-4212C/AD-4212D factory setting

Setting itemWeighing deviceAD-8552EIP
Baud rate2400*, 9600, 19200, 38400 bps
Data bit7 bit*
ParityEVEN*
Stop bit1 bit*
Terminator<CR><LF>*
Data output formatA&D standard format*
Data output modeSettings for continuous output of weighing values.(stream mode*)

*AD-8552EIP factory setting(normally, the factory setting of AD-4212C / AD-4212D is the same.)
2. Set the following setting items so that the host (PLC, PC, etc.) and AD-8552EIP are the same.
<Setting example>

Setting itemHost(PLC, PC, etc.)AD-8552EIP
IP address*[192.168.0.1][192.168.0.2]

* Make sure that IP addresses do not overlap in the connected network.
3. Refer to ”4-2 Connecting example”, “5-2 Connections”, “6-2 Connecting cable” for connecting.
・Normally, when using the AD-4212C/AD-4212D, power can be supplied from the RS-232C terminal, so connecting to the power terminal of the AD-4212C/AD-4212D is not required.
・ When connecting to the AD-4212D, connect to the AD-8552EIP using the AD-4212D display connector.
4. Turn on the device power.

9-2 Output data (Instance150)
The data transferred from PLC etc. to the AD-8552EIP is called Output data.
Output data is used when outputting a command to the measuring instrument.
■ Output data layout (O->T) [ PLC etc. -> AD8552EIP -> Weighing device(CH1 to 4) ]

Assembly InstanceAttributeByteNameData typeContents
15030,1CH1 CommandUInt16Command outpu(t  Weighing device CH1)
2,3CH2 CommandUInt16Command outpu(t  Weighing device CH2)
4,5CH3 CommandUInt16Command outpu(t  Weighing device CH3)
6,7CH4 CommandUInt16Command outpu(t  Weighing device CH4)

■ Details of the Output data
・Command output [CH1~4 Command] (CH1:byte 0,1、CH2:byte 2,3、CH3: byte 4,5、CH4: byte 6,7)
The following command is output to the weighing device connected to CH1-4.

BitContents※1Remarks
0“EXC” command outputUsed for calibration (sensitivity adjustment)
1“CAL” command output
2“PRT” command output
3“R” command outputPerforming zero reset (rezero) of the weighing device
4“SMP” command outputChange the readability of the weighing device
5“U” command output 2Change response characteristics or switch units
6“RZ” command outputPerforming zero reset (rezero) of the weighing device
7“Z” command output
8“T” command outputPerforming tare
9-15No function

※1.The AD-8552EIP outputs each command to the connected instrument when a “1” is written.
※2.The operation differs depending on the weighing device. For individual operation commands, refer to “3-2 Applicable model” or the instruction manual of the relevant weighing device.

9-3 Input data (Instance100)
The data transferred from AD-8552EIP to PLC, etc. is called Input data.
Input data is used when acquiring data from the weighing device.
■ Input data layout (T->O) [ Weighing device (CH1 to 4) -> AD8552EIP -> PLC, etc. ]

Assembly InstanceAttributeByteNameData typeContents
10030~3CH1 Weighing valueInt32Weighing valueWeighing device CH1
4,5CH1 Status informationUInt16Status information1
6,7CH1 Decimal point positionUInt16Decimal point position
8,9CH1 Weighing unitUInt16Weighing unit
10,11CH1 Response characteristicsUInt16Response characteristics
12,13CH1 Adjustment statusUInt16Adjustment status
14~17CH1 Adjustment weight valueInt32Adjustment weight  value2
18~21CH2 Weighing valueInt32Weighing valueWeighing device CH2
22,23CH2 Status informationUInt16Status information1
24,25CH2 Decimal point positionUInt16Decimal point position
26,27CH2 Weighing unitUInt16Weighing unit
28,29CH2 Response characteristicsUInt16Response  characteristics
30,31CH2 Adjustment statusUInt16Adjustment status
32~35CH2 Adjustment weight valueInt32Adjustment weight value2
36~39CH3 Weighing valueInt32Weighing valueWeighing device CH3
40,41CH3 Status informationUInt16Status information1
42,43CH3 Decimal point positionUInt16Decimal point position
44,45CH3 Weighing unitUInt16weighing unit
46,47CH3 Response characteristicsUInt16Response characteristics
48,49CH3 Adjustment statusUInt16Adjustment status
50~53CH3 Adjustment weight valueInt32Adjustment weight  value2
54~57CH4 Weighing valueInt32Weighing valueWeighing device CH4
58,59CH4 Status informationUInt16Status information1
60,61CH4 Decimal point positionUInt16Decimal point position
62,63CH4 Weighing unitUInt16Weighing unit
64,65CH4 Response characteristicsUInt16Response characteristics
66,67CH4 Adjustment statusUInt16Adjustment status
68~71CH4 Adjustment weight valueInt32Adjustment weight value2

※1.If you connect to anything other than the AD-4212C / D, the functions will be limited.
※2.This function can be used only when connected to the AD-4212C / D.

9-4 Detailed information of the Input data1
■Weighing value [CH1 to 4 Weighing value] (CH1:byte 0 to 3, CH2:byte 18 to 21, CH3:byte 36 to 39、CH4:byte 54 to 57), Decimal point position [CH1 to 4 Decimal point position] (CH1: byte 6,7 CH2: byte 24,25, CH3: byte 42,43, CH4: byte 60,61)
Example of weighing value and decimal point value by output of Weighing device (CH1)(When the decimal point position setting by SW-5 is AUTO)

Weighing value of the weighing device (CH1)ByteNameContentsDataRemarks
123.456g0 to 3CH1 Weighing valueWeighing value0x0001E240⇒ 123456
6,7CH1 Decimal point positionDecimal point position0x0003⇒ 3
123.456g0 to 3CH1 Weighing valueWeighing value0x00003039⇒ 12345
6,7CH1 Decimal point positionDecimal point position0x0002⇒ 2

■ Status information of the weighing device [CH1 to 4 Status information] (CH1:byte 4,5, CH2:byte 22,23, CH3:byte 40,41, CH4:byte 58,59)

ByteStatusRemarks
0Stable / unstable status of weighing value0:Unstable 1:Stable
1Weighing range over flag1:When the weighing value exceeds the maximum display
2Non-weighing status flag0:When receiving the current weighing value from the weighing device 1:When weighing value is interrupted for 2 seconds or more, and rezero or calibration is in progress.
3Rezeroing flag1:Rezero processing in progress※1
4No function
5Adjustment in progress flag1:Adjustment in progress※1
6Adjustment error flag※21 : When calibrating If the value of the weighing calibration weight is not appropriate. (This flag returns to 0 when shifting to the weighing mode.)
7No function
8 to 15

※1.The flag does not change when operated with the keys of the weighing device.
※2.This flag can be used only when connected to the AD-4212C / D.
Caution: Be sure to read “Weighing value” and “Weighing value status information” at the same time. If they are read separately, the correspondence between the “weighing value” and the “weighing value status information” may differ depending on the update timing, so the weighing value status cannot be determined accurately.
■ Weighing unit [CH1~4 Weighing unit] (CH1:byte 8,9, CH2:byte 26,27, CH3:byte 44,45, CH4:byte 62,63)
Relationship between value and unit

ValueUnit (mode)ValueUnit (mode)ValueUnit (mode)
0x0000g (gram)0x0006Mom (Momme)0x000CTL (Tael)
0x0001mg (milligram)0x0007OZ (Ounce)0x000DTol (Tola)
0x0002kg (kilogram)0x0008Lb (Pound)0x000EMES (Messghal)
0x0003PCS (pieces)0x0009OZt (Troy Ounce)0x000FN (Newton)
0x0004% (percent)0x000Adwt (pennyweight)0x0010MLT (Programmable unit)
0x0005ct (carat)0x000BGN (Grain)0xFFFFIndistinguishable

9-5 Detailed information of the Input data2(Only for AD-4212C/AD4212D)
The following items change only when connected to the AD-4212C / AD-4212D.
When connected to other weighing devices, it will be the initial value.
■ Response characteristics [CH1 ~ 4 Response characteristics] (CH1:byte 10,11, CH2:byte 28,29, CH3:46,47, CH4:byte 64,65)

ValueStatus of the response characteristics※1
0x0000Initial value
0x0001FAST
0x0002MID
0x0003SLOW
0x0004User setting※2

※1.You can switch between FAST / MID / SLOW with the “U” command.(Refer to “9-2. Output data”)
※2.With AD-4212C, the response characteristics are set in detail.
(Refer to the WinCT-AD4212C additional instruction manual for the setting method)
■ Adjustment status [CH1 to 4 Adjustment status] (CH1:byte 12,13, CH2:byte 30,31, CH3:byte 48,49, CH4:byte 66,67)

ValueStatus
0x0000Initial value
0x0001Waiting for zero point weighing
0x0002Weighing the zero point
0x0003Waiting for adjustment weight to be weighed
0x0004Weighing adjustment weight
0x0005Sensitivity adjustment completed
0x0006Sensitivity adjustment error

■ Adjustment weight value [CH1 to 4 Adjustment weight value]
(CH1:byte 14 to 17, CH2:byte 32 to 35, CH3:byte 50 to 53, CH4:byte 68 to 71)
You can check the value of the calibration weight to be used when performing calibration (sensitivity adjustment) with your own weight.
‐The unit is grams and the decimal point is a value without a decimal point.
‐The value of the calibration weight to be used is used only when “Waiting for calibration weight to be weighed”.
The initial value is “0xFFFFFFFF”. When you return to the weighing mode, it will return to the initial value.
Example of Adjustment weighing value for weighing device (CH1)

Weight valueByteNameContentsDataRemarks
100g14 to 17CH1 Adjustment weight valueAdjustment weight value0x00000064⇒ 100

9-6 Operating example(When connected to the AD-4212C/AD-4212D)
This is the procedure for performing basic operations on the weighing device via EtherNet/IP communication.
(Describes the case where a weighing device is connected to CH1. When using CH2, 3, 4, make the data layout correspond to the relevant CH (channel).)
■ How to read the weighing value (Weighing device CH1))

StepsItemsContentsInput data layout (Instance150, Attribute3)Output data layout (Instance100 ,Attribute3)Status confirmation contents
AD-4212CAD-4212D
1Confirmation of decimal point positionRefer to the corresponding data layout.Byte 6,7

[CH1 Decimal point position]

Confirm the decimal point position
eg) 0x0003 →   Decimal point 3 digits
2Confirmation of weighing unitRefer to the corresponding data layout.Byte 8,9
[CH1 Weighing unit]
Confirm the corresponding unit of weighing value
eg) 0x0000  →   Unit:g
3Confirmation of weighing valueRefer to the corresponding data layout.Byte 0-3
[CH1 Weighing value]
Confirm the weighing value

eg) 0x00BC614E →   12345678

Byte 4,5
[CH1 Status information]
Confirm the status information
eg) 0x0000 →   Stable weighing value
4Determines the measured value by steps 1 to 3eg) 12345.678 g (stable)
5Repeat steps 3 to 4.2

※1.Be sure to read “Weighing value” and “Weighing value status information” at the same time. If they are read separately, the correspondence between the “weighing value” and the “weighing value status information” may differ depending on the update timing, so the weighing value status cannot be determined accurately.
※2.If you change the decimal point position or unit, or if you want to use the smart range function, perform steps 1 and 2 as necessary.
■ Execution example of rezero (zero reset) (Weighing device CH1)

StepsItemsContentsInput data layout (Instance150, Attribute3)Output data layout (Instance100 ,Attribute3)Status confirmation contents
AD-4212CAD-4212D
1Instructs to start rezeroSets “1” to the corresponding data layoutByte 0,1 [CH1 Command] Bit 3 (“R” command)
2Confirms to start of rezeroRefer to the corresponding data layout.Byte 4,5
[CH1 Status information] bit3
Waits until bit3 changes from 0 to 1※3
3Confirms during rezeroRefer to the corresponding data layout.Byte 4,5
[CH1 Status information] bit3
Waits until bit3 changes from 1 to 0
4Confirms the completion of rezeroRefer to the corresponding data layout.Byte 0 to 3
[CH1 Weighing value]
Confirms to become 0x00000000※4
5Command clearSets “0” to the corresponding data layoutByte 0,1 [CH1 Command] Bit 3 (“R” command)

※ 3.Normally, changes immediately after setting “1” to the corresponding data layout in the previous step.
When the weighing value is stable, rezeroing is completed instantly and bit3 returns to “0”, so the “1” state may not be read depending on the reading timing.
※ 4.If weighing value is unstable, re-zero cannot be executed. Be sure to confirm completion of re-zero by confirming that the weighing value is “0x00000000”.
■Example of calibration (sensitivity adjustment) with external weight(Possible only with AD-4212C/AD-4212D)

StepsItemsContentsInput data layout (Instance150 ,Attribute3)Output data layout (Instance100 ,Attribute3)Status confirmation contents
AD-4212CAD-4212D
1Instructs to start the sensitivity adjustment modeSets “1” to the corresponding data layoutByte 0,1 [CH1 Command]
bit 1‟CAL”bit 0 ‟EXC”
2Confirms the sensitivity adjustment modeRefer to the corresponding data layout.Byte12,13 [CH1 Adjustment status]Wait until 0x0001※1
3Instructs to start weighing at zero pointSets “1” to the corresponding data layoutByte 0,1 [CH1 Command] bit 2 ‟PRT”
4Confirms to start weighing at zero pointRefer to the corresponding data layout.Byte12,13 [CH1 Adjustment status]Wait until 0x0002※1
5Confirms during weighing at the zero pointRefer to the corresponding data layout.Byte12,13 [CH1 Adjustment status]Wait until 0x0003※2
6Command clearSets “0” to the corresponding data formaByte0,1 [CH1 Command] bit 2 ‟PRT”
7Confirms the value of the sensitivity weight to be used※4Refer to the corresponding data layout.Byte14-17
[CH1 Adjustment weight value]
Weight value to use(eg) 0x000000C8 ⇒200g
8Places the weight
9Instructs to start weighing the weightSets “1” to the corresponding data layoutByte0,1 [CH1 Command]  bit 2「PRT」
10Confirms to start weighing weightRefer to the corresponding data layout.Byte12,13 [CH1 Adjustment status]Wait until 0x0004※1
11Confirms during weighing weightRefer to the corresponding data layout.Byte12,13 [CH1 Adjustment status]Wait until 0x0005※2※3
12Replaces the weight
13Confirms the transition to the weighing stateRefer to the corresponding data layout.Byte 0-3 [CH1 Weighing value]Wait until 0x00000000
14Command clearSets “0” to the corresponding data layout0,1 [CH1 Command] bit 2 ‟PRT”
bit 1 ‟CAL”bit 0 ‟EXC”

※1.Normally, it changes immediately after setting “1” to the bit of the previous step.
※2.If the weighing device is unstable, the sensitivity adjustment will not be executed and the weighing state will automatically shift to the weighing state (0x00000000).
※3.If the value of the weighed sensitivity adjustment weight is not appropriate, a sensitivity adjustment error (0x0006) will occur. After that, it automatically shifts to the weighing state (0x00000000).
※4.If you want to change the value of the sensitivity adjustment weight to be used, please check the instruction manual of the relevant weighing device.
■ Calibration (sensitivity adjustment) execution example using the built-in weight(Only with the AD-4212D)

StepsItemsContentsInput data layout (Instance150 ,Attribute3)Output data layout (Instance100 ,Attribute3)Status confirmation contents
AD-4212D
1Calibration (sensitivity adjustment) execution example using the built-in weightSets “1” to the corresponding data layoutByte0,1 [CH1 Command] bit 1 ‟CAL”
2Confirms to start the sensitivity adjustmentRefer to the corresponding data layout.Byte 4,5 [CH1 Status information]Wait until bit 5 becomes 1※1
3Confirms the completionRefer to the corresponding data layout.Byte 4,5 [CH1 Status information]Wait until bit 5 becomes 0※1
Byte 12,13 [CH1 Adjustment status]Confirms becomes 0x0005※5
4Command clearSets “0” to the corresponding data layoutByte0,1 [CH1 Command] bit 1 ‟CAL”

※5.Normally, changes immediately after setting “1” to bit in the previous step.
※6.If the weighing value is unstable, Sensitivity adjustment completed (0x0005) is not entered, and it switches automatically to weighing mode. Also, if the weighing value is not appropriate, Sensitivity adjustment error (0x0006) will occur. After that, it automatically shifts to weighing status (0x0000).

WEB Interface

  • The WEB interface is a function that allows to confirm the operation of the weighing device from a PC browser. The WEB interface can be used to check the operation when starting up the production line or when troubleshooting.

Caution 

  • Establishing communication between the WEB interface and Ether Net/IP at the same time is not recommended.
    (It may conflict with Ether Net/IP communication.)
  • Communication may become unstable depending on the environment, so using for continuous connection and monitoring are recommended.
  • The browsers that have been confirmed to work are Microsoft Edge, Google Chrome, Mozilla Firefox, and Safari.

10-1 Preparing for communication

  1. Prepare in the same way as “9-1. Preparation for communication” (9. Ether Net/IP).
  2. Enter the IP address of the AD-8552EIP in the address bar of your browser.
  3. Press “Connect”.
  4. Enter “and” in the “Password” field and press “send Password”.

10-2 HOME display

AND AD 8552EIP EtherNet IPConverter - FIGURE 18

No.NameDescription
Weighing displayDisplays the “weighing value” of the weighing device connected to CH.1 to 4.
Data layoutDisplays the data layout of EtherNet/IP communication
Weighing device display switching buttonThe “10-3. Weighing device operation screen” connected to each channel is displayed.
PropertyDisplays the “Network Settings” and “MAC Address” of the AD-8552EIP.
Network setting buttonThe AD-8552EIP “10-4. Network Setting Screen” is displayed.

10-3 Weighing Device Operation Screen

  • The weighing device operation screen has a mode (CH1 to 4) that displays one channel on one screen and a mode (ALL) that displays four channels.

■ 1 channel display (CH1 to 4)

AND AD 8552EIP EtherNet IPConverter - FIGURE 19

No.NameDescription
Weighing displayDisplays the “weighing value” of the weighing device connected to the channel display.
Channel displayDisplays channels
Weighing device display switching button“10-3. Weighing Device Operation Screen” connected to each channel is displayed.
HOME button“10-2. HOME display” is displayed.
Key switchOperates the weighing device※1

※1.The key switches that can be operated differ depending on the measuring instrument to be connected. The contents are in table of “3-2. Compatible models” and each measuring instrument.
Please refer to the instruction manual.

■ 4 channel display (ALL) ※2

AND AD 8552EIP EtherNet IPConverter - FIGURE 20

※2.”4 channel display (ALL)” only displays the weighing values of 4 weighing devices.
(When operating the weighing device from the WEB interface, use the channel to which the weighing device to be operated is connected. Please go from “1 channel display”.)
10-4 Network Setting Screen

  • On the network setting screen, you can set the IP address, subnet mask, and default gateway.

AND AD 8552EIP EtherNet IPConverter - FIGURE 21

Note

  • Please consult with your network administrator before connecting to the network.
  • Set the IP address so that it does not overlap with other devices.

■ Network setting screen

AND AD 8552EIP EtherNet IPConverter - FIGURE 22

NameSetting value(setting range)Description
IP address0.0.0.0 to 255.255.255.255
Please consult your network administrator for the setting values.
Displays the IP address of this device.
Sub-net maskDisplays the subnet mask of this unit.
Default gatewayDisplays the default gateway of this device.
OK buttonThe display returns to “10-2. HOME display”.

Troubleshooting

PhenomenonConfirmation and countermeasures
POWER LED does not illuminateMake sure that power is properly supplied to the power supply terminal of the AD- 8552EIP.
・Is the voltage correct?(DC 24V)
・Is the cable connected correctly?
NS LED does not turn greenThe connection with the scanner (PLC) has not been established.
・Is the IP address set so that it does not overlap?
・Is the signal output from the scanner?
NS LED is flashingThe connection with the scanner (PLC) has timed out.
・Is the Ether Net/IP communication cable broken?
・Is the scanner turned on?
IP address cannot be changedTurn the power of the AD-8552EIP off and then on again. When the power is turned on, the changes made to the switch and WEB interface are read and reflected in the operation.
Non-weighing status flag is “1”.Check the setting of the weighing device.
・Check the RS-232C communication settings of the corresponding channel.
・Is the output format of the weighing device set to the A&D standard format?
AD-8552EIP settings cannot be changed.Turn the AD-8552EIP off and then on again. When the power is turned on, the switch status is read and reflected in the operation.

© 2022 All rights reserved.
No part of this publication may be reproduced, transmitted, transcribed, or translated into any language in any form by any means without the written permission of A&D Company, Limited.

AND LOGOA&D Company, Ltd.

A&D Company, Limited
3-23-14 Higashi-Ikebukuro, Toshima-ku, Tokyo 170-0013, JAPAN
Telephone: [81] (3) 5391-6132
Fax: [81] (3) 5391-1566
A&D ENGINEERING, INC.
47747 Warm Springs Blvd, Fremont, California 94539, U.S.A.
Tel: [1] (800) 726-3364 Weighing Support:[1] (888) 726-5931
Inspection Support:[1] (855) 332-8815
A&D INSTRUMENTS LIMITED
Unit 24/26 Blacklands Way, Abingdon Business Park, Abingdon, Oxfordshire OX14 1DY United Kingdom
Telephone: [44] (1235) 550420
Fax: [44] (1235) 550485
A&D AUSTRALASIA PTY LTD
32 Dew Street, Thebarton, South Australia 5031, AUSTRALIA
Telephone: [61] (8) 8301-8100
Fax: [61] (8) 8352-7409

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals