FT-01202 5kW Surge Arrester Cartridge

Technical Data FT-01202

Description

The FUSADEE R5/14 cartridge is a Type 2 Surge Protection Device
designed for low voltage networks. It provides surge protection for
areas with low surge risk or for protection in divisional
boards.

Features

  • Type 2 Surge Protection Device
  • Designed for low voltage networks
  • Provides surge protection for low surge risk areas or
    divisional boards

Installation Requirements

The FT-01202 must be installed downstream of a differential
circuit breaker with a caliber lower than 100A.

Product Usage Instructions

  1. Ensure that the FT-01202 is installed downstream of a
    differential circuit breaker with a caliber lower than 100A.
  2. Connect the FT-01202 to the low voltage network that requires
    surge protection.
  3. Ensure that the FT-01202 is properly grounded.
  4. Test the surge protection device to ensure proper function
    before use.

Note: The FT-01202 is designed for use in low surge risk areas
or divisional boards. If you require surge protection for high
surge risk areas, please consult a qualified electrician or contact
the manufacturer for further assistance.

Technical data FT-01202
FUSADR5/14 ­ Surge protection device FUSADEE Edition 19/11/2008
Description
FUSADEE R5/14 cartridge.
User guide
Surge protection for low voltage network in low surge risk area or for protection in divisional board.
Description
Type 2 Surge protection Device for low voltage network.
Features
· Rated voltage Uc : 400Vac ; · Nominal voltage 230/400Vac · Compatible earthing systems : TT, TN et IT · Residual protection voltage Up : 0,8kV ; · Conformity : IEC 61643-11
Installation requirements
Installation downstream of a differential circuit breaker with a caliber lower than 100A.
description assistance
Type 2 Surge Protection Device for <100A board, nominal voltage 400V, Protection voltage Up 0.8kV, Zener technology, discharge current rating In 0.1kA, number of discharges at In unlimited, disconnector associated recommended: nominal current <100A sensitivity <1A undelayed or S Type. Cylindrical arrester cartridge size 14x51mm.
Spare parts and accessories
Spare : · Cartridge-holder FUSADEE 14×51 : code 10203
Recommended accessories: · Cartridge controler : code 30111
Code 10203