Milleteknik 350-122 Redundancy Panel 1u Owner's Manual

350-122 Redundancy Panel 1U

Product Information: Redundancy Panel 1U

The Redundancy Panel 1U is a device that provides double sum
alarm in case of loss of voltage from power supply (Power supply
24V 15A 1U) one, two and three (depending on which are connected),
tripped load fuse 1, 2 and 3, (depending on which are connected).
It has a capacity to connect up to four loads and powered by
connected power supplies (Power supply 24V 15A 1U).

Product Usage Instructions:

Step 1: Mount the Redundancy Panel 1U in a 19
rack using the appropriate screw and nut for the rack. Screw and
nut are not included.

Step 2: Connect the Power supply 24V 15A 1U to
the Redundancy Panel 1U.

Step 3: Connect the load to the Redundancy
Panel 1U using quick connectors.

Step 4: If three Power supplies 24V 15A 1U are
to be used with Redundancy panel 1U, remove the jumper on Input 3.
If two Power supply 24V 15A 1U are to be used together with the
Redundancy panel 1U, fit the jumper (red circle) (it is fitted from
the factory). Should three Power supply 24V 15A 1U jumper, (red
circle) should not be mounted. Unscrew the cover and adjust the
bracket.

Note: Read the manual carefully before
installing and using the product. Ensure that all connections are
made properly and follow the safety instructions provided in the
manual.

SV EN
Redundancy Panel 1U
Strömstyrning av Power supply 24V 15A

350-122 Publiceringsdatum 2023-03-09

SV

Innehållsförteckning
1. Om …………………………………………………………………………………………………………………………. 3 2. Komponentöversikt ……………………………………………………………………………………………………… 4 3. Kapsling …………………………………………………………………………………………………………………… 5
3.1. Montering i 19″ rack …………………………………………………………………………………………… 5 3.2. Montering ……………………………………………………………………………………………………….. 5 4. Inkoppling …………………………………………………………………………………………………………………. 5 5. Koppla ihop med Power supply 24BV 15A 1U …………………………………………………………………… 6 5.1. Input 3 ……………………………………………………………………………………………………………. 6 6. Anslut last ………………………………………………………………………………………………………………… 7 6.1. Larmfunktioner …………………………………………………………………………………………………. 7 7. Anslut larm ……………………………………………………………………………………………………………….. 7 8. Driftsättning ………………………………………………………………………………………………………………. 8 9. Panelförklaring …………………………………………………………………………………………………………… 8 10. Regelverk och certifieringar ………………………………………………………………………………………… 8 10.1. Krav som produkten uppfyller …………………………………………………………………………….. 8 11. Tekniska data …………………………………………………………………………………………………………… 8 12. Tekniska data kapsling ……………………………………………………………………………………………….. 9 12.1. Tekniska data 1U …………………………………………………………………………………………….. 9 13. Garanti, support, tillverkningsland och ursprungsland ……………………………………………………….. 9 13.1. Garanti …………………………………………………………………………………………………………. 9 13.2. Tillverkningsland …………………………………………………………………………………………….. 9 13.3. Tillverkare ……………………………………………………………………………………………………… 9 14. Produktens livslängd, miljöpåverkan och återvinning ………………………………………………………. 10 15. Om detta dokument …………………………………………………………………………………………………. 10 16. Adress och kontaktuppgifter ………………………………………………………………………………………. 10
1. OM
Redundancy Panel 1U är en rackmonterad enhet för strömstyrning av Power supply 24V 15A 1UE eller batteribackuper från Milleteknik. Redundancy Panel 1U har tre (3) ingångar vilket innebär att det är möjligt att ansluta upp till tre (3) nätaggregat (Power supply 24V 15A 1U). Om två av tre nätaggregaten (Power supply 24V 15A 1U) / batteribackuper slutar att fungera som strömkälla till systemet täcker det tredje och sista fungerande nätaggregatet. Redundancy Panel 1U larmar för om någon av strömkällorna slutar att fungera eller vid lastsäkringsfel. Användningsområde: Där behov av redundans i 24 V strömförsörjning finns.
3

SV

LÄS DETTA FÖRST!
Om det är möjligt, lämna 100 mm fritt utrymme. Systemet är avsett för bruk i kontrollerad inomhusmiljö. Endast personer med behörighet bör installera och underhålla systemet. Det är installatörens ansvar att systemet är lämpad för avsett bruk. Dokument som medföljer systemet skall förvaras i det eller i dess omedelbara närhet. Ventilation skall ej övertäckas. Nätspänning bör vara bortkopplad under installation. Alla uppgifter med reservation för ändringar. Vid installation av denna produkt erkänner och accepterar installatören denna produkts begränsningar som de är beskrivna i denna manual.
2. KOMPONENTÖVERSIKT
Figur 1. Framsida

Nr 1 2

Förklaring Indikeringsdiod för last och anslutna Power supply 24V 15A 1U Lastsäkringar

Figur 2. Baksida

4

SV

Nr 1
2.1-2.4 3.1-3.3

Förklaring
Dubblerat summalarm, NO/COM/NC+NO/COM/NC. Summalarm: larm vid bortfall av spänning från nätaggregat (Power supply 24V 15A 1U) ett, två och tre (beroende på vilka som är inkopplade), utlöst lastsäkring 1, 2 och 3, (beroende på vilka som är anslutna).
Last in 1-4, — / ++
Inkoppling av Power supply 24V 15A 1U

3. KAPSLING

3.1. Montering i 19″ rack
Enheten skall monteras i 19″ rack. Konsol skruvas fast i rack med M6 skruv och korgmutter, minst en på varje sida. Använd lämplig skruv och mutter för rack. Skruv och mutter ingår ej.

Nr 1

Enhenten skruvas fast i 19″ rack.

3.2. Montering

Förklaring

4. INKOPPLING

Redundancy Panel 1HE drivs av påkopplade nätaggregat (Power supply 24V 15A 1U. Anslut 24 V last på Last 1-4.

5

5. KOPPLA IHOP MED POWER SUPPLY 24BV 15A 1U

SV

Tabell 1. Koppla ihop Redundancy panel 1U med Power supply 24V 15A 1U

Nr 1 2 3

Förklaring Koppla in första Power supply 24V 15A 1U på Input 1. Koppla in andra Power supply 24V 15A 1U på Input 2. Koppla in tredje Power supply 24V 15A 1U på Input 3. Se input 3 [6]I

5.1. Input 3

VIKTIGT
Detta avsnitt gäller endast om tre Power supply 24V 15A 1U skall användas med Redundancy panel 1U.
Skall tre Power supply 24V 15A 1U användas skall bygel på Input 3 avlägsnas. Skall två Power supply 24V 15A 1U användas tillsammans med Redunandcy panel 1U skall jumper, (röd cirkel) vara monterad (sitter monterad från fabrik). Skall tre Power supply 24V 15A 1U skall jumper, (röd cirkel) ej vara monterad. Skruva av locket och justera bygel.
6

SV

Skruva av locket och justera bygel. Tag bort jumper vid användning av tre Power supply 24V 15A 1U.
VARNING
Enheten får ej vara spänningssatt vid bygling.
6. ANSLUT LAST
24 V last ansluts visa snabbkontakt. [4] 6.1. Larmfunktioner
Dubblerat summalarm: Larm vid bortfall av spänning från nätaggregat efter lastsäkring.
7. ANSLUT LARM
Larm ansluts på baksidan. NO/CO/NC. Använd valfri anslutning, larmen är dubblerade. Summalarm: larm vid bortfall av spänning från nätaggregat ett, två och tre (beroende på vilka som är inkopplade), utlöst lastsäkring 1, 2 ,3 och 4, (beroende på vilka som är anslutna).
7

SV

8. DRIFTSÄTTNING

Efter inkoppling skall uppstart ske i följande steg:
1. Koppla till nätaggregat (bör ej vara spänningssatta vid installation) och last. 2. Kontrollera att säkring(ar) på framsida är på ON. 3. Spänningssätt elnät. 4. Enheten fungerar normalt då indikeringsdiod lyser med fast grönt sken.

9. PANELFÖRKLARING

Tabell 2.
LED för Alarm Alarm PSU 1-3 PSU 1-3 Load 1-4 Load 1-4

Status Släckt Rött Grön Släckt Grön Släckt

Förklaring Normaldrift. Larm för PSU Error / fel på eller utlös lastsäkring. Normaldrift- Power supply 24V 15A 1U är inkopplat. Fel på Power supply 24V 15A 1U. Normaldrift. Lastsäkring har löst ut.

10. REGELVERK OCH CERTIFIERINGAR

10.1. Krav som produkten uppfyller

EMC: El:
CE:

EMC Direktivet 2014/30EU Lågspänningsdirektivet: 2014/35/EU
CE direktivet enligt:765/2008

11. TEKNISKA DATA

Tabell 3. Kretskort Redundans 19R2

Info Artikelbenämning Strömförsörjning Lastutgångar Ingångar

Förklaring Kretskort Redundans 19R2 Produkten drivs av påkopplade nätaggregat (Power supply 24V 15A 1U). Fyra stycken, –/++ Tre stycken, — / ++ snabbkontakt.

8

Info Larm
Säkringar (last).

Förklaring
Dubbla summalarm: larm vid bortfall av spänning från nätaggregat ett, två och tre (beroende på vilka som är inkopplade), utlöst lastsäkring 1, 2 och 3, (beroende på vilka som är anslutna).
Automatsäkringar 10 A

12. TEKNISKA DATA KAPSLING

SV

12.1. Tekniska data 1U

Info Namn Kapslingsklass Mått Höjdenheter Montering Omgivningstemperatur Omgivning Material Färg Kabelgenomföringar, antal

Förklaring 1U IP 20 Höjd: 44 mm, bredd: 244 mm, djup: 280 mm. 1 19″ rack +5 °C – +40 °C. För bästa batterilivslängd: +15 °C till +25 °C. Miljöklass 1, inomhus. 20% ~ 90% relativ fuktighet Pulverlackerad plåt Svart 8

13. GARANTI, SUPPORT, TILLVERKNINGSLAND OCH URSPRUNGSLAND

13.1. Garanti
Produkten har två års garanti, från inköpsdatum (om inget annat avtalats). Kostnadsfri support under garantitiden nås på [email protected] eller telefon, 031-34 00 230. Ersättning för res- och eller arbetstid i samband med lokalisering av fel, installerande av reparerad eller utbytt vara ingår ej i garantin. Kontakta Milleteknik för mer information. Milleteknik ger support under produktens livslängd, dock som längst 10 år efter inköpsdatum. Byte till likvärdig produkt kan förekomma om Milleteknik bedömer att reparation inte är möjlig. Kostnader för support tillkommer efter det att garantitiden har gått ut.
13.2. Tillverkningsland
Sverige
13.3. Tillverkare
Designad och producerad av Milleteknik AB
9

SV

14. PRODUKTENS LIVSLÄNGD, MILJÖPÅVERKAN OCH ÅTERVINNING
Produkten är designad och konstruerad för lång livslängd vilket minskar miljöpåverkan. Produktens livslängd (förutom slitagedelar) är beroende på, bland annat miljöfaktorer, främst omgivningstemperatur, oförutsedd belastning på komponenter som blixtnedslag, yttre åverkan, handhavandefel, med flera. Produkter återvinns genom att lämnas till närmaste återvinningsstation eller sändas åter till tillverkare. Kontakta din distributör för mer information. Kostnader som uppkommer i samband med återvinning ersätts ej.
15. OM DETTA DOKUMENT
Dokumentets artikelnummer: 350-122 Detta dokument kan ändras utan föregående meddelande. Alla uppgifter publiceras med reservation för tryckfel.
16. ADRESS OCH KONTAKTUPPGIFTER
Milleteknik AB Ögärdesvägen 8 B 433 30 Partille Sverige 031-340 02 30 [email protected] www.milleteknik.se
10

EN

Table of Contents
1. About …………………………………………………………………………………………………………………….. 11 2. Component overview …………………………………………………………………………………………………. 12 3. Enclosures ……………………………………………………………………………………………………………… 13
3.1. Installation in 19″ rack ………………………………………………………………………………………. 13 3.2. Mounting ………………………………………………………………………………………………………. 13 4. Connection ……………………………………………………………………………………………………………… 13 5. Connect with Power supply 24BV 15A 1U ………………………………………………………………………. 14 5.1. Input 3 ………………………………………………………………………………………………………….. 14 6. Connect load …………………………………………………………………………………………………………… 15 6.1. Alarm functions ………………………………………………………………………………………………. 15 7. Connect alarm …………………………………………………………………………………………………………. 15 8. Commissioning ………………………………………………………………………………………………………… 16 9. Panel explanation ……………………………………………………………………………………………………… 16 10. Regulations and certifications ……………………………………………………………………………………. 16 10.1. Requirements that the product meets ………………………………………………………………… 16 11. Technical data ………………………………………………………………………………………………………… 16 12. Technical data enclosures …………………………………………………………………………………………. 17 12.1. Technical data 1U ………………………………………………………………………………………….. 17 13. Warranty, support, country of manufacture and country of origin ………………………………………… 17 13.1. Warranty ……………………………………………………………………………………………………… 17 13.2. Country of manufacture ………………………………………………………………………………….. 17 13.3. Designed and produced by: Milleteknik AB ………………………………………………………….. 17 14. Product life cycle, environmental impact and recycling …………………………………………………….. 18 15. About this document ………………………………………………………………………………………………… 18 16. Address and contact details ………………………………………………………………………………………. 18
1. ABOUT
Redundancy Panel 1U is a rack-mounted unit for power control of Power supply 24V 15A 1UE or battery backups from Milleteknik. Redundancy Panel 1U has three (3) inputs, which means that it is possible to connect up to three (3) power supplies (Power supply 24V 15A 1U). If two of the three power supplies (Power supply 24V 15A 1U) / battery backups stop working as a power source for the system, the third and last functioning power supply covers. Redundancy Panel 1U alerts if one of the power sources stops working or in the event of a load fuse failure. Area of use: Where there is a need for redundancy in the 24 V power supply.
11

READ THIS FIRST!
If possible, leave 100 mm of free space. The system is intended for use in a controlled indoor environment. Only authorized persons should install and maintain the system. It is the installer’s responsibility to ensure that the system is suitable for its intended use. Documents accompanying the system must be kept in or in its immediate vicinity. Ventilation should not be covered. Mains voltage should be disconnected during installation. All information subject to change. Upon installation of this product, the installer acknowledges and accepts the limitations of this product as described in this manual.
2. COMPONENT OVERVIEW
Figure 1. Front

EN

No 1 2
Figure 2. Back

Explanation LED for load and connected Power supply 24V 15A 1U Load fuses

12

EN

No 1
2.1-2.4 3.1-3.3

Explanation
Double sum alarm, NO/COM/NC+NO/COM/NC. Sum alarm: alarm in case of loss of voltage from power supply (Power supply 24V 15A 1U) one, two and three (depending on which are connected), tripped load fuse 1, 2 and 3, (depending on which are connected).
Load 1-4, — / ++
Connection of Power supply 24V 15A 1U

3. ENCLOSURES

3.1. Installation in 19″ rack
The unit must be mounted in a 19″ rack. Bracket is screwed into rack with M6 screw and basket nut, at least one on each side. Use the appropriate screw and nut for the rack. Screw and nut not included.

No . 1

The unit is screwed into a 19″ rack.

3.2. Mounting

Explanation

4. CONNECTION

Redundancy Panel 1HE is powered by connected power supplies (Power supply 24V 15A 1U. Connect 24 V load to Load 1-4.

13

5. CONNECT WITH POWER SUPPLY 24BV 15A 1U

EN

Table 1. Connect Redundancy panel 1U with Power supply 24V 15A 1U

No 1 2 3

Explanation Connect the first Power supply 24V 15A 1U to Input 1. Connect the other Power supply 24V 15A 1U to Input 2. Connect the third Power supply 24V 15A 1U to Input 3. See input 3 [14]IN

5.1. Input 3

IMPORTANT
This section only applies if three Power supply 24V 15A 1U are to be used with Redundancy panel 1U.
If three Power supplies 24V 15A 1U are to be used, the jumper on Input 3 must be removed. If two Power supply 24V 15A 1U are to be used together with the Redunandcy panel 1U, the jumper (red circle) must be fitted (it is fitted from the factory). Should three Power supply 24V 15A 1U jumper, (red circle) should not be mounted. Unscrew the cover and adjust the bracket.
14

EN

Unscrew the cover and adjust the bracket. Remove jumper when using three Power supply 24V 15A 1U.
WARNING
The unit must not be energized when bridging.
6. CONNECT LOAD
24 V load is connected show quick contact. [12] 6.1. Alarm functions
Double total alarm: Alarm in the event of loss of voltage from the power supply after load protection.
7. CONNECT ALARM
Alarm is connected on the back. NO/CO/NC. Use any connection, the alarms are duplicated. Total alarm: alarm in the event of loss of voltage from power supplies one, two and three (depending on which are connected), tripped load fuse 1, 2, 3 and 4, (depending on which are connected).
15

EN

8. COMMISSIONING

After connection, startup must take place in the following steps:
1. Connect power supply (should not be live during installation) and load. 2. Check that the fuse(s) on the front is ON. 3. Voltage set mains. 4. The device works normally when the indicator diode lights up with a solid green light.
9. PANEL EXPLANATION

Table 2.
Led for Alarm Alarm PSUs 1-3 PSUs 1-3 Loads 1-4 Loads 1-4

Status Turned off RED Green Turned off Green Turned off

Explanation Normal operation. Alarm for PSU Error / fault on or triggered load fuse. Normal operation – Power supply 24V 15A 1U is connected. Error on Power supply 24V 15A 1U. Normal operation. Load fuse has tripped.

10. REGULATIONS AND CERTIFICATIONS

10.1. Requirements that the product meets

EMC: Electricity:
CE:

EMC Directive 2014 / 30EU Low voltage directive: 2014/35 / EU
EN 60950-1 CE directive according to: 765/2008

11. TECHNICAL DATA

Table 3. Circuit board Redundancy 19R2

Info Article name Power supply Load outputs Entrances

Explanation Circuit board Redundancy 19R2 The product is powered by connected power supplies (Power supply 24V 15A 1U). Four pieces, –/++ Three pieces, — / ++ quick connector.

16

Info Alarm
Fuses (load).

Explanation
Double total alarm: alarm in case of loss of voltage from power supplies one, two and three (depending on which are connected), tripped load fuse 1, 2 and 3, (depending on which are connected).
Automatic fuses 10 A

12. TECHNICAL DATA ENCLOSURES

EN

12.1. Technical data 1U

Info Name Enclosure class Measure Height units Mounting Ambient temperature Environment Material Color Cable glands, number

Explanation 1U IP 20 Height: 44 mm, width: 244 mm, depth: 280 mm. 1 19 “rack + 5 ° C – + 40 ° C. For best battery life: + 15 ° C to + 25 ° C. Environmental class 1, indoors. 20% ~ 90% relative humidity Powder coated sheet metal Black 8

13. WARRANTY, SUPPORT, COUNTRY OF MANUFACTURE AND COUNTRY OF ORIGIN

13.1. Warranty
The product has a two-year warranty, from the date of purchase (unless otherwise agreed). Support during the warranty period can be reached at [email protected] or telephone, +46 31-34 00 230. Compensation for travel and / or working hours in connection with locating faults, installing repaired or replaced goods is not included in the warranty. Contact Milleteknik for more information. Milleteknik provides support during the product’s lifetime, however, no later than 10 years after the date of purchase. Switching to an equivalent product may occur if Milleteknik deems that repair is not possible. Support costs may (at Milleteknik’s discretion) occour after the warranty period has expired.
13.2. Country of manufacture
Country of manufacture / country of origin is Sweden. For more information, contact your seller.
13.3. Designed and produced by: Milleteknik AB
Designed and produced by Milleteknik AB
17

EN

14. PRODUCT LIFE CYCLE, ENVIRONMENTAL IMPACT AND RECYCLING
The product is designed and constructed for a long service life, which reduces the environmental impact. The product’s service life depends on, among other things, environmental factors, mainly ambient temperature, unforeseen load on components such as lightning strikes, external damage, handling errors, and more. Products are recycled by being handed over to the nearest recycling station or sent back to the manufacturer. Contact your distributor for more information. Costs that arise in connection with recycling are not reimbursed.
15. ABOUT THIS DOCUMENT
Article number of the document: This document is subject to change without prior notice. All information is published with reservation for printing errors.
16. ADDRESS AND CONTACT DETAILS
Milleteknik AB Ögärdesvägen 8 B S-433 30 Partille Sweden +46 31 340 02 30 [email protected] www.milleteknik.se
18

This page is intentionally left blank.

This page is intentionally left blank.

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals