Lennox Commercial Rooftop Unit User Guide

Lennox Commercial Rooftop Unit User Guide

LENNOX Commercial Rooftop Unit User Guide
LENNOX Commercial Rooftop Unit

Siemens Setup and Configuration Guide

Applies to Lennox Rooftop using a Siemens Climatix ECO Economizer Controller 

Follow the steps below to setup the siemens controller manually.

  1. From the default HMI screen, press and hold Enter + Up. The 5CONFIG STATE screen displays.
  2. Press enter, and then confirm the switch by pressing enter again. Blocks can be changed by pressing and holding Enter + Up or Down. Parameters can be changed by pressing enter and using the arrows to adjust. Confirm the switch by pressing enter again.
  3. Configure I/Os. See below for notable parameters.
    ParameterConfigure AsDescription
    6OCCAlways/T-statOccupancy comes from controller or OC terminal
    6OAT SIGNTC10KConfigures signal type of OAT sensor
    6OAH SIG0-10VConfigures signal type of OAH sensor
    6RAH SIG0-10VConfigures signal type of RAH sensor
    6MAT SIGNTC10KConfigures signal type of MAT or LAT
  4. If configurations are done, press and hold Enter + Up or Down to switch to the 8RUN STATE screen, then press Enter twice to go back to Running State. The 1FREECOOL screen displays.
    AppsApp Store Google Play
    Apps  App Store  Google Play
    Apps  App Store Google Play
    Apps  App Store  Google Play
  5. Verify status parameters. See below for notable parameters.
    ParameterDescription
    1FREECOOLIndicates if the system can use outdoor air for free cooling
    1ECON ENABIndicates if outdoor air is being used for the 1st stage of cooling
    1OCCUPIEDIndicates if the space is occupied- Controller needs to be in the occupied state
    1Y1-INY1-In call from thermostat for Cooling Stage 1
    1Y1-OUTY1-Out signal to compressor for Cooling Stage
  6. Configure basic settings. See below for notable parameters.
    ParameterConfigure AsDescription
    2TEMP OFF55°F (12.8°C)Temperature shutoff setpoint
    2ENTH OFF22 Btu/lbmEnthalpy shutoff setpoint
    2FAN L ACT2.8VMinimum position at low speed
    2FAN H ACT3.6VMinimum position at high speed

    Damper Position – 2V = 0% 6V = 50% 10V = 100%

  7. Configure advanced settings. See below for notable parameters.
    ParameterConfigure AsDescription
    3FREEZE POSCLOAnti-freeze protection damper position
    3MAT SET53°F (11.7°C)Setpoint of MAT or LAT sensor
    3FRZ PROT45°F (7.2°C)Anti-freeze protection setpoint of MAT sensor
    3OAT LOCK32°F (0°C)OAT lockout setpoint for anti-freeze
  8. To enter test functions. See below for notable parameters.
    From the default HMI screen, press and hold Enter + Up. The 5CONFIG STATE screen displays. Press enter, and then confirm the switch by pressing enter again.
ParameterDescription
7DAMPER MIN POSDrives damper to minimum position
7DAMPER CLOSEDrives damper 100% closed
7DAMPER OPENDrives damper 100% open
If configurations are done, press and hold Enter + Up or Down to switch to the 8RUN STATE screen, then press Enter twice to go back to Running State. The 1FREECOOL screen displays.

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals