Danfoss Ak-pc 782b Pack Controller Installation Guide

AK-PC 782B Pack Controller

Product Information

The product is the Pack Controller, type AK-PC 782B with USB-B.
It is manufactured by Danfoss and has the model number 080R9351
AN412826307589en-000201. The controller has AI x 11 (analog input)
and DO x 8 (digital output) capabilities. It operates on a supply
voltage of 24 V AC/DC and has a transformer Class II.

The controller has various terminals and connections, including
LAN* (not used), IO Extension, SPDT (Single-Pole Double-Throw)
relay, and AKV coil 110/230 V. It also supports different signal
types such as P (pressure), U (voltage), and Pt 1000.

It is important to note that the 24 V input should not be shared
by other controllers or units, and it must not have an earth
connection. Additionally, low and high voltage must not be
connected to the same output group to ensure safety.

Product Usage Instructions

  1. Before adding or removing modules, ensure that the power is
    disconnected.
  2. Connect the controller to a suitable power source with a supply
    voltage of 24 V AC/DC.
  3. Make sure that the 24 V input does not have an earth
    connection.
  4. Connect any required analog input devices to the corresponding
    terminals based on the signal type and active state mentioned in
    the manual.
  5. Connect any required digital output devices to the
    corresponding terminals based on the signal type and active state
    mentioned in the manual.
  6. If using the LAN feature, use a shielded twisted pair CAT5
    cable for connection.
  7. For any external switches or devices that need to be connected,
    follow the specified active state (e.g., Closed/Open, ON/OFF).
  8. Dispose of the product and any electrical components according
    to local and currently valid legislation. Do not dispose of them
    with domestic waste; they should be separately collected as
    electrical and electronic waste.

Please refer to the user manual for additional information and
specific usage instructions.

Installation Guide
Pack Controller, type AK-PC 782B with USB-B

080R9351 AN412826307589en-000201

Danfoss 80Z942

080Z0202

-20 °C < tamb < 55 °C -0 °F < tamb < 130 °F 0 ­ 95% RH, non condensing IP10 / VBG4 UL: E31024

Warning
Ensure power is disconnected before adding or removing modules.

AI x 11 DO x 8
Supply voltage:
Transformer Class II

Danfoss 80Z941

AI A,B,C,D 24 V AC/DC

12 V 5 V

AI 5 V
Max. 10 V

The 24 V must not be shared by other controllers or units
The 24 V input must not have earth connection
24 V
OK
24 V

Max. 230 V

LAN* Not used IO Extension
*Shielded twisted pair CAT5

For the LAN with IP communication, the address must be set between 011 ­ 199. Factory setting: 011

ON/OFF

ON/OFF

Keep the safety distance. Low and high voltage must not be connected to the same output group.

SPDT

Umin : 48 V AC I max.: 0.5 A

SPDT: AC-1: 4A (ohmic) AC-15: 3A (Inductive)

Danfoss 80Z206

© Danfoss | Climate Solutions | 2023.03

AN412826307589en-000201 | 1

Point

Terminal 15: 12 V Terminal 16: 5 V Terminal 27: 12 V Terminal 28: 5 V Terminal 17, 18, 29, 30:

Danfoss 80Z14
Danfoss 80Z968

Relay or AKV coil 110/230 V

S (sensor) Pt 1000 ohm/0°C
P (pressure)

Signal

Signal type

S1 S2… Saux1 SIG Saux2 SSA SdA GND

Pt 1000

AKS 32R AKS 32

AKS 32R

P0A P0B PcA

AKS 2050 MBS 8250 -1 – xx bar

PcB

AKS 32

-1 – zz bar

U (voltage) On/Off DO

AKV

0 – 5 V

0 – 10 V

Ext. Main switch Day/ Night Door Comp 1 Comp 2 Fan 1 Alarm

Active at: Closed / Open
Active at: ON / OFF

AO

AO

0-10 V

The Product contains electrical components And may not be disposed together with domestic waste. Equipment must be separate collected with Electrical and Electronic waste. According to Local and currently valid legislation.

2 | AN412826307589en-000201

Address

Factory setting: 011

011 ­ 199

Signal

(Controller)

Signal type / Active at

Module Point Terminals

1 (AI 1)

1 – 2

2 (AI 2)

3 – 4

3 (AI 3)

5 – 6

4 (AI 4)

7 – 8

5 (AI 5)

9 – 10

6 (AI 6) 11 – 12

7 (AI 7) 13 – 14

8 (AI 8) 19 – 20

9 (AI 9) 21 – 22

10 (AI 10) 23 – 24

1

11 (AI 11) 25 – 26

12 (DO 1) 31 – 32

13 (DO 2) 33 – 34

14 (DO 3) 35 – 36

15 (DO 4) 37 – 38

16 (DO 5) 39 – 41

17 (DO6) 42 – 44

18 (DO7) 45 – 47

19 (DO8) 24 (AO1) 25 (AO2)

48 – 50 –

© Danfoss | Climate Solutions | 2023.03