Danfoss 089 0879 Intelligent Purging System Ammonia User Guide

Danfoss 089 0879 Intelligent Purging System Ammonia User Guide

Danfoss-logo

Danfoss 089 0879 Intelligent Purging System Ammonia

Danfoss-089-0879-Intelligent-Purging-System-Ammonia-product

Legal notice

This product information is a part of the documentation for the Danfoss scope of delivery and serves as product presentation and customer advisory service. It contains important information and technical data regarding the product. This product information should be supplemented with the information about the industrial safety and health related regulations at the site of installation of the product. The regulations vary from place to place as a result of the statutory regulations applicable at the site of installation and are therefore not considered in this product information. In addition to this product information and the accident prevention regulations applicable for the respective country and area where the product is used, the technical regulations for safe and professional work must also be observed. This product information has been written in good faith. However, Danfoss cannot be held responsible for any errors that this document may contain or for their consequences. Danfoss reserves the right to make technical changes during the course of further development of the equipment covered by this product information. Illustrations and drawings in this product information are simplified representations. As a result of the improvements and changes, it is possible that the illustrations do not exactly match the current development status. The technical data and dimensions are subject to change. No claims will be accepted on the basis of them.

EU DECLARATION OF CONFORMITY

Danfoss A/S Refrigeration & Air Conditioning Controls

declares under our sole responsibility that the

Product category: Intelligent Purger System (Air Purger)

Type designation(s): IPS 8 Covered by this declaration is in conformity with the following directive(s), standard(s) or other normative document(s), provided that the product is used in accordance with our instructions.

Machine Directive 2006/42/EC
EN 378-2:2016 Refrigerating systems and heat pumps – Safety and environmental requirements – Part 2: Design, construction, testing, marking and documentation IEC 60204-1:2018 Safety requirements for electrical equipment for measurement, control and laboratory use – Part 1: General requirements

Pressure Equipment Directive 2014/68/EU (PED)
EN 378-2:2016 Refrigerating systems and heat pumps – Safety and environmental requirements – Part 2: Design, construction, testing, marking and documentation Ammonia side (R717): Category A4P3. Fluid group: 1. PS = 40 bar. TS: -40 ˜C to 60 ˜C R452A side: Category 1. Fluid group: 2. PS = 28 bar. TS: -40 ˜C to 60 ˜C Ambient temperature: -10 ˜C to 43 ˜C

Electromagnetic Compatibility Directive 2014/30/EU (EMC)

  • IEC 61000-6-2 Electromagnetic compatibility (EMC) – Part 6-2: Generic standards – Immunity standard for industrial environments (IEC77/488/CDV:2015)
  • EN 61000-6-4 Electromagnetic compatibiliy (EMC) – Part 6-4: Generic standards – Emission standard for industrial environments

Note: EMC test performed with cable length < 30m.

Danfoss-089-0879-Intelligent-Purging-System-Ammonia-fig-2

Danfoss only vouches for the correctness of the English version of this declaration. In the event of the declaration being translated into any other language, the translator concerned shall be liable for the correctness of the translation

  • ID No: 084R9456
  • Revision No: AA

Technical data

Supply voltage for: IPS 8 Field1) connected solenoid coils230 V +/-10% AC, 1ph, 60Hz
Current5.7 A (max. 6.5 A)
Power consumptionmax. 1.3 kW
Short-circuit current ratingIcc 10kA
Temperature range ambient-10 °C to +43 °C (14 °F to 109 °F)
Temperature range transport/storage-30 °C to +60 °C (-22 °F to 140 °F)
EnclosureIP55
Weightmax. 100 kg (221 lbs)
Dimensions (LxWxH)1051 x 441 x 703 mm (41.4 x 17.4 x 27.7 inches)
Purger refrigerantR452A 900 gram (31.7 oz)
Max. operating pressure (PS) R452A28 bar (406 psi)
System refrigerantR717
Max. operating pressure R71740 bar (580 psi)
Operating temperature R717-40 °C to +60 °C (-40 °F to 140 °F)

Description Field connected valves

  • Digital Output, DO6 YV ICFD – Valve on ICF (Optional)
  • Digital Output, DO7 Y1 Valve – Purge Point 1
  • Digital Output, DO8 Y2 Valve – Purge Point 2
  • Digital Output, DO9 Y3 Valve – Purge Point 3
  • Digital Output, DO10 Y4 Valve – Purge Point 4
  • Digital Output, DO11 Y5 Valve – Purge Point 5
  • Digital Output, DO12 Y6 Valve – Purge Point 6
  • Digital Output, DO13 Y7 Valve – Purge Point 7
  • Digital Output, DO14 Y8 Valve – Purge Point 8
  • Digital Output, DO15 Y9 Valve – Bubbler (Optional) / General Alarm (Optional)

Ordering

UnitCode number
Danfoss Intelligent Purging System IPS 8 unit084H5002
 

Accessories/Spare parts

Accessory (Not included with IPS)Spare parts for service

(Built-into IPS)

 

Code

Flange blind blank incl Bolts, nuts and Gaskets*x084H5053
SV3 Float Valvex027B2023
ICF 15-4 solenoid, DIN Butt weld 15mm ½ inchx027L4543
ICF 15-4 solenoid, ANSI Socket weld 15mm ½ inchx027L4538
ICF 15-4 solenoid, ANSI Butt weld 15mm ½ inchx027L4602
Welding Flange incl Bolts, nuts and Gasketsx084H5061
Repair kit for Main Purge Valve (Armature, tube, Sealing, Orifice, Filter insert). See Fig. 1, Item 16xx084H5051
Solenoid coil, 24V DC for Main Purge Valve. See Fig. 1, Item 16xx018F6757
PSU, 24V DC – optional for powering purge pointsxx080Z0055
Restrictor, in purge line after Main Purge Valve. See Fig. 1, Item 18 and Fig. 13.x084H5054
Compressor Cranck case heaterx084H5058
Condenser coil assy incl screwsx084H5059
Fan motor for condenser Incl fan grid and screwsx084H5060
Extraction Fanx084H5056
Air grid with filter (2 pieces)x084H5057
Pre-programmed MCX15B2 with application SW includedx084H5067
Pressure transmitter evaporator, soldered (AKS 32R)x060G3552
Compressor including Start relay box and Start and Run Capacitorx123B2156
Compressor Hi-temp sensorx084N2003
Expansion valve, R452Ax068U3881
Sight glassx014-0191
Pressure transmitter – R717, Threaded, AKS2050x060G5750
Thermostat for crankcase heater controlx060L111166
Temperature sensor – R717, AKS 21Mx084N2003
LLS 4000 liquid level switch G 3/4” **x084H6001
Pressure switch for FanxContact Danfoss
Pressure safety switchxContact Danfoss
  • For closing system flange during system pressure testing
  • See Fig. 1 and Fig. 10a

Introduction

The Danfoss Intelligent Purging System (IPS 8) is a stand-alone, self-contained purging unit designed to remove non-condensable gases (NC gases = air and other unwanted foreign gases) from industrial ammonia refrigeration systems. The IPS control can handle up to 8 purge points automatically. The ingress of NC gases into a refrigeration system is inevitable, regardless of the refrigerant, pressures, or temperatures. NC gases in the system will result in a decrease in system efficiency, both in terms of an increase in power consumption and reduced cooling capacity.
Due to having a different density than ammonia, the ingressed air will accumulate in specific areas of the system, where it can be removed using the Danfoss IPS 8. The accumulation areas are identified in the Connection locations section, along with recommended connection principles. The purger unit is an electronically controlled, self-contained R452A refrigerant system that runs independent of the main ammonia system and with only one flange connection to the ammonia plant. The flanged opening allows the ammonia gas/NC gas mix access to the purger’s heat exchanger, where it is split into ammonia condensate and NC gases. The ammonia condensate is returned by gravity to the main plant, while the NC gases are purged to the atmosphere through e.g. a water bath. Through the flanged opening, the purger unit has access to the parameters from the ammonia plant required for full electronic control. The unit runs automatically in 24-hour cycles, checking for the presence of NC gases and, if present, removes the NC gases. To regain and retain the design capacity of the main ammonia system and prevent future air accumulation, it is highly recommended to install the Danfoss IPS 8.

Features

  • State-of-the-art electronically controlled unit based on the Danfoss MCX controller platform
  • Reduced power consumption of the ammonia plant
  • Automatic purging response to NC gases in the refrigeration system
  • Continuous and smart monitoring of differential pressure between the system refrigerant and the purger’s refrigerant
  • Smart purging that minimizes refrigerant (ammonia) release to the environment
  • Self-contained unit operation, which functions independently from the main plant
  • An operation log for easy purging cycle data monitoring
  • Industry-standard Modbus RTU communication for remote monitoring and system integration
  • Reduced purging unit power consumption compared to other units due to on-demand operation only
  • Load scheme to identify which purge point is removing most NCC
  • Prepared to manage/control Bubbler
  • Option to install LLS 4000 to protect IPS for high column of ammonia liquid
  • Self-diagnostics for both unit and system operation to shut down in the event of malfunctions
  • Cost-effective installation with few mechanical and electrical connections
  • A fully brazed and leak-tested R452A cooling system, minimizing leakage risks
  • A plug-and-play stand-alone design, which simplifies installation and commissioning while reducing potential errors
  • No need for advanced settings
  • A compact and easy-to-handle design
  • IPS carry a registered patent

Working principle

The Danfoss IPS 8 is factory-tested and ready to use in ammonia plants with a condenser pressure of more than 6,5 bar (94 psi). The purger is charged with 900 gram (31.7 oz) of R452A. Only 1 mechanical connection is needed for the purger (see fig. 1). The flow of ammonia/NC gases from the main plant is done through the flange for ammonia (see 13 in Fig. 1 below), while the NC gas purge is done through the blow-off pipe after the purge restrictor (18). Through the flange for ammonia (13), a mixture of ammonia gas and NC gases enters the heat exchanger (12) part of the purger. The ammonia gas/NC gas mix is cooled down below the condensing temperature of the ammonia by the R452A circuit. At this point, ammonia gas condenses and returns by gravity to the ammonia plant whereas the NC gases accumulate in the heat exchanger (12) for subsequent purging. By condensing the ammonia gas, a new ammonia/NC gases mix is naturally pulled through. This new mix is separated through a continuous process. As the NC gas concentration in the heat exchanger (12) increases, the R452A heat exchanger pressure and temperature will simultaneously decrease. The controller continuously monitors the R452A heat exchanger pressure as well as ammonia pressure and temperature. When the R452A pressure reaches a predefined pressure difference when compared with the ammonia pressure (temperature) it prepares to purge the NC gases through the solenoid valve (16). The blow-off is activated by the solenoid (16) and through appropriate piping/hosing, should be led into a water bath. This process is recommended to retain small amounts of ammonia (see Installation section).Danfoss-089-0879-Intelligent-Purging-System-Ammonia-fig-3

Fig. 1 – Purger R452A lay-out

1Compressor (900 gram (31.7 oz) R452A) controlled via Digital Output, DO111Expansion valve, R452A
1aCompressor Cranck case heater12Heat exchanger Ammonia/R452A
2Thermostat for crankcase heater control13Welding Flange
3Discharge temp sensor R452A via Analog Input AI3, Pt 100014Pressure transmitter R452A. Measured via via Analog Input AI1, Pressure transmitter, AKS 32R
3aSuction temperature sensor R452A via Analog Input AI4, Pt 100015Pressure transmitter R717. Measured via Analog Input, AI2, Pressure transmitter, AKS 2050
4Pressure safety switch16Main Purge Valve controlled via Digital Output, DO2
5Condenser17NC temperature sensor R717. Measured via Analog Input, AI5, Pt1000
6Extraction fan18Restrictor, purge line
7Pressure switch for Condenser Fan19LLS 4000 Liquid Level Switch. Accessory. Not included with standard IPS
8Receiver
9Filter
10Sight glass

Working cycle

The Danfoss IPS 8 operates in 24-hour cycles, of which 45 minutes are dedicated to an R452A pull down. At power on, the pull down is initiated immediately. If no NC gases are detected during the 40 minute pull down, the system will close the solenoid valve at purge point 1 and open the solenoid valve at point 2. After a cycle time of 24 hours/N (Number of purge points), the compressor will pull down again condensing the ammonia. After 24 hours, all purge points have been vented one time. To identify NC gases, the controller utilizes upper and lower thresholds for R452A evaporating temperature. If, during pull down, the temperature continues decreasing and the lower threshold is passed, the controller considers this to be a high concentration of NC gases and opens the purge solenoid valve. The purge valve will stay open until sufficient condensing ammonia is present to lift the R452A evaporating temperature above the upper threshold. The compressor will continue running and if the temperature again decreases below the lower threshold, a new purge will be performed. This process will be repeated until the R452A heat exchanger temperature stays above the lower threshold for >40 minutes following the previous closure of the purge valve.

Label IDParameter NameDescription and selection optionsFactory setting
CM3PDTPull down time

Pull down time of compressor

40 min
CM4CSTCompressor start time See Fig. 2 for details1440 min (24 h)
 

VA5

 

PLT

Endless purging max time

Max time for endless purging on one point. When the time has expired, IPS will go to next Purge Point (PP)

 

24 h

See complete Parameter List – Table 01

Danfoss-089-0879-Intelligent-Purging-System-Ammonia-fig-4

Fig. 2 – Power on & Cycle at no NC gases present: CST (compressor start time) and PDT (pull down time) are configurable * Cycle (CST) = 24 hours/N (number of purge points)Danfoss-089-0879-Intelligent-Purging-System-Ammonia-fig-5

Fig. 3 – Purging procedure – Low R452A evap. temperature detected during PDT: Thresholds are configurable If low evaporator temperature is detected (passing lower threshold), the purging procedure will be repeated immediately

Danfoss-089-0879-Intelligent-Purging-System-Ammonia-fig-6

Air traps

Danfoss-089-0879-Intelligent-Purging-System-Ammonia-fig-7

For systems with low pressure liquid level control, the correct condenser/ receiver installation is as shown in Fig. 4 and Fig. 5. The discharge gas from the compressor (1) is led to the condenser (2) where it is condensed. The receiver (3) holds the liquid until there is a demand for liquid from the LP side, e.g., until the expansion valve (4) opens. If the expansion valve is closed, the liquid condensed in the condenser will need to be stored in the receiver and the level will increase. To ensure a free flow to the receiver, the gas must be allowed to leave the receiver; this process is accomplished through the pressure equalizing line (a). The pressure equalizing line makes the pressure in the receiver the same as in the compressor discharge line. The pressure in the condenser outlet is lower due to the pressure loss in the condenser. Since the condenser outlet pressure is lower than in the receiver, it is therefore necessary to mount the condenser higher than the receiver and allow for a higher liquid level in the piping between the condenser and the receiver (b). The liquid column in the line (b) compensates for the pressure difference between the condenser outlet and the receiver. Fig. 4 shows the liquid connection at the bottom of the receiver. If the liquid from the condenser is connected to the top of the receiver (Fig. 5), a slightly different arrangement must be made. The liquid line (b) from the condenser to the receiver will need to have a goose neck/liquid trap to ensure that the liquid column is actually established. As air is heavier than ammonia gas, the air will collect in two locations in this type of installation: On top of the liquid in the receiver (x) and/or on top of the liquid in the drop leg from the condenser (y).

Connection locations

  • Air purger installation in a low-pressure liquid level controlled installation

The correct locations for the air purger to be connected to the ammonia plant are: (See Fig. 6 and Fig. 7)

  • on top of the receiver or
  • on top of the liquid in the drop leg from the condenser.

The air purger (5) is connected to the two purge points through solenoid valves (px and py). Note that only one solenoid should be open at any given time, otherwise the liquid column in the condenser will be short-circuited. The air purger must have its own liquid return drop leg (c) connected in parallel with the condenser’s drop legs (b). When the purger is connected to the receiver i.e. solenoid (px) open, the liquid level in the air purgers drop leg (c) will be equal to the receiver liquid level (3); when the purger is connected to the condenser outlet i.e. solenoid (py) open, the liquid level will be equal to the liquid level in the condenser drop leg (b).Danfoss-089-0879-Intelligent-Purging-System-Ammonia-fig-8

Fig. 6 Purger connections (px) & (py). Drain piping (c) must be vertical/downward slope
Alternatively, the air purger draining of liquid can be achieved effectively through an HP float valve (6) to the low pressure side (see Fig. 7).Danfoss-089-0879-Intelligent-Purging-System-Ammonia-fig-9

Connection locations (continued)

  • Air purger installation in a high-pressure liquid level controlled installation

For systems with a high-pressure liquid level control, the air will collect in the float valve (3). (See Fig. 8). The compressor (1) supplies high-pressure gas to the condenser (2), where it is condensed. The float valve (3) will flash any liquid back to the LP side. The air purger (5) must be connected to the float valve through a solenoid valve (pv).The ammonia liquid condensed in the air purger must be drained through drain pipe (c) to the LP side via a float valve (6).Danfoss-089-0879-Intelligent-Purging-System-Ammonia-fig-10

General
The air purger must always be mounted above the highest liquid level to be able to drain the ammonia condensed in it. Otherwise, the air purger can flood and potentially purge ammonia liquid. The purger liquid return leg (c) must always be mounted vertically or at minimum, with a downward slope. The solenoid valves at the connection points must never be activated at the same time. Finalize purging at one location before switching to the next.

WARNING !
Follow the installation guide strictly during Purger installation. Install the Purger unit in a location where the bottom flange level and any gas inlet connection level is above any possible ammonia liquid level. Liquid drain piping from the purger must always have a downward slope. Install a shut off valve close to the bottom flange entrance to enable removal of the unit and closing for high pressure ammonia gas. Connect proper resistant piping to the purging outlet pipe and ensure the purged non-condensables are discharged into a water bath of max. 200 liter.

Connection points

Multi-point purging
As factory default, the Danfoss IPS 8 is configured to manage up to 8 purge points. (Multi-point purging. See Fig. 10). The actual amount of purge points connected needs to be setup in the MCX controller after power-up. The parameter in question for entering the actual number of purge point: V10, Max_PP (See Table 3). Single point purging setup is possible (See Fig. 09 -no purge solenoid valves). For single point purging the parameter in question for entering the actual number of purge point: V10, Max_PP must be set to 1 (See Table 3). Both power and control wiring of the installed solenoid valves coils should take place prior to first power up.

NEVER HAVE MORE THAN 1 PURGE POINT OPEN AT A TIME.
Always close one purge valve before opening the next. This is done by turning the purger unit power on and entering the number of actual purge points (V10, Max_PP) in the program. See section “Programming/configuration”.Danfoss-089-0879-Intelligent-Purging-System-Ammonia-fig-11

  • See Installation guide for Danfoss floats:
  • Type SV3 – Lit.No. : AN149486432996
  • Type ICFD used in ICFD – Lit.No. : AN250286497620
  • See Installation guide for LLS 4000 Liquid Level Switch: AN317523977313Danfoss-089-0879-Intelligent-Purging-System-Ammonia-fig-12

Installation

The Danfoss IPS 8 must be installed in accordance with locations recommended in the Connection locations and Connection points sections of this document. The unit has a protection rating of IP55 and may be installed outside, in ambient temperature ranges from from -10 °C to 43 °C / 14 °F to 109 °F). Avoid installation in direct sunlight as this may lead to excessive sunlight exposure and ambient temperatures above allowed limits. For ambient temperatures below -10 °C (14 °F) the air purger must be installed in a heated and ventilated area. The unit must be installed in a non- ATEX atmosphere as the purger unit is not explosion proof. The purger unit should be kept in an upright position at all times – from receipt to final installation.Use all 4 lifting eyes and suitable lifting gear during installation (unit weight = 100 kg/220 lbs). Install the unit on an even horizontal base 0.05 to 1.1 meter (2 to 43 in) above a service platform with sufficient support and allowing the purger subframe to be bolted to the support (see example in Fig. 12). Maintain recommended distances in all directions (Fig. 12) to allow fan cooling and servicing.

  • Always leave the unit off for at least 12 hours from finished installation to first time power up.
  • It is important that the support construction is level to ensure the internal liquid trap is properly filled. Angle to horizontal < 2 degrees

Lifting Procedure

Danfoss-089-0879-Intelligent-Purging-System-Ammonia-fig-13Danfoss-089-0879-Intelligent-Purging-System-Ammonia-fig-14Danfoss-089-0879-Intelligent-Purging-System-Ammonia-fig-15Danfoss-089-0879-Intelligent-Purging-System-Ammonia-fig-16

  1. Prepare the ammonia pipework with the weld flange according to Fig. 13 and Fig. 14. The main/drain piping should never be smaller than inner diameter Ø37 mm (1.5 in).
  2. Complete the supporting structure able to carry 100 kg (221 lbs).
  3. Lift the purger into position using the lifting eyes on each side of the purger’s cabinet. Remove the rubber plug from the flange opening. See Fig. 13.
  4. Connect the weld flange with the purger flange using the enclosed flat gasket and tighten the supplied 4 bolts diagonally to a torque of 60 Nm (44.3 ft-lb).
  5. Insert 4 bolts (not supplied) through the purger frame and the support construction and tighten.
  6. Perform a leak test to ensure an airtight connection.
  7. In the event the purger unit needs to be dismantled please contact Danfoss for instructions.
  8. Correctly install a suitable pipe/hose from the purge solenoid valve for blow-off of NC gases in accordance with local or national regulations.
  9. Prepare an outside water tank with a maximum of 200 liters (53 gal.) and ensure the piping allows the purged gas to be immersed in the water.
  10. Regularly check the pH level of the tank’s contents.
  11. The pH level should never exceed 12.6. Otherwise the water content must be renewed.
  12. Dispose of concentrated waste water in accordance with to local/national regulations.

Note: Prior to replacing the water in the water tank ensure that the purger is switched off and the shut off valve at the flanged purger inlet is closed. Leave the unit in this condition for a period to allow the remaining gas in the piping to be dissolved/released.
Watch out for bubbles. Establish a procedure for regular checking the pH level and bubble pattern. If continuous bubbles are observed in the water tank during ‘‘stand by” (Green light indicator) in normal operation, one or more of the purge solenoid valves needs repair or replacement.

Electrical wiring

  • The internal wiring of the purger is done at the factory. Only the electrical wiring for the main power supply, the purge point solenoids and optional bus communication needs wiring on site.
  • It is highly recommended that all external cables coming from the IPS 8 to the power supply and to all purge point solenoids are protected by metallic pipes.Danfoss-089-0879-Intelligent-Purging-System-Ammonia-fig-17

Controller box cover can only be opened at key unlock and with the main switch off.

Note: Authorized personel only

Danfoss-089-0879-Intelligent-Purging-System-Ammonia-fig-18

Electrical wiring (continued) 

Danfoss-089-0879-Intelligent-Purging-System-Ammonia-fig-19Danfoss-089-0879-Intelligent-Purging-System-Ammonia-fig-20Danfoss-089-0879-Intelligent-Purging-System-Ammonia-fig-21

Light Indicators

Danfoss-089-0879-Intelligent-Purging-System-Ammonia-fig-22

Lights ONStatusCompressor ONCompressor OFFPurge Valve ONPurge Valve OFFAlarm
GreenStand byxx
YellowRunxx
Green & YellowPurgingxx
Green & Yellow & RedUninterupted Long time purging (> 150 h)xx*
RedOccurs when: Check list of alarms description(x**)x**x
  • The purger continuous purging until max running period (default 160 h) is reached and the purger compressor will stop
  • The purger compressor stops when alarm occurs

Quick Startup
For the fastest possible system configuration after connecting all purge points to the IPS and following first power up of the IPS, follow these simple instructions:

  1. Navigate from the Main Menu to Login
  2. Enter password ‘200’.
  3. Choose ‘Parameters’.
  4. Choose ‘Unit Config’
  5. Choose ‘Valve Settings’
  6. Enter the amount of purge solenoid valves connected to the IPS.

Navigation – built in MCX controller
(Placed at the rear of the front panel door)

  • After switching on the controller, a display window will momentarily show the actual software version, followed by the default main operating window shown in Fig. 26.
  • While in operation mode, the Up/Down arrow buttons lead the user to the status windows described in Table 01 below.Danfoss-089-0879-Intelligent-Purging-System-Ammonia-fig-23Danfoss-089-0879-Intelligent-Purging-System-Ammonia-fig-25
  • By pressing Danfoss-089-0879-Intelligent-Purging-System-Ammonia-fig-26the main menu will show up with the options below

Main menu navigation

Label IDParameter NameDescription and selection optionsMin.Max.Value/ TypeUnitRWMODBUS

Register

StUGeneral > Setup
 

 

y01

 

 

Main switch

Release the IPS for operation

OFF: the IPS is forced out of operation

ON: the controller released for operation. Observe if DI1, On/ Off – External Mainswitch must also be ON to release the IPS for operation

 

 

0

 

 

1

 

 

0 – OFF

 

Enum 1

 

 

RW

 

 

3001

 

 

y07

 

Restore default parameters

Back factory settings

No: Not active

Yes: All parameters will be returned to factory default settings, and the alarm list will be cleared. The parameter will automatically be set back to ‘No’ when factory reset has finished (after a few seconds).

 

 

0

 

 

1

 

 

0 – NO

 

Enum 2

 

 

RW

 

 

3002

SErGeneral > Serial settings
 

SEr

Serial address (Modbus and CAN)Enter ID adress of the controller

Only relevant if connected to external equipment (like PLC) or other Danfoss equipment.

 

1

 

100

 

1

 

RW

 

3006

 

 

 

 

bAU

 

 

 

 

Serial baudrate (Modbus)

Baudrate

The system unit usually communicates with 38.400.

0=0

1=12 corresponds to 1200

2=24 corresponds to 2400

3=48 corresponds to 4800

4=96 corresponds to 9600

5=144 corresponds to 14400

6=192 corresponds to 192000

7=288 corresponds to 288000

8=384 corresponds to 38400

 

 

 

 

0

 

 

 

 

8

 

 

 

 

8 – 384

 

 

 

 

Enum 3

 

 

 

 

RW

 

 

 

 

3007

 

COM

 

Serial settings (Modbus)

Serial mode

0=8N1

1=8E1

2=8N2

 

0

 

2

 

1 – 8E1

 

Enum 4

 

RW

 

3008

ExPGeneral > Expansion settings
 

 

Ex1

 

 

Enable expansion

Enable expansion of extra purge point

Panel with MCX contoller to purge extra purge points, in addition to the 8 purge points at the main IPS

No: Disabel Yes: Enable

 

 

0

 

 

1

 

 

0 – NO

 

Enum 2

 

 

RW

 

 

3013

Ex2Expansion addressExpansion adress of MCX controller

Located in external panel (outside main IPS electrical panel)

0255125RW3014
CMPUnit config > Compressor
CM3PDTPull down time

Pull down time of compressor

1CM440minRW3016
CM4CSTCompressor start time

See Fig. 2 for details

18020001440minRW3017
 

VA5

 

PLT

Endless purging max time

Max time for endless purging on one point. When the time has expired, IPS will go to next Purge Point (PP)

 

2

 

768

 

24

 

h

 

RW

 

3018

VALUnit config > Valve settings
 

VA2

 

DeltaTValveOFF

Temperatue difference Open/Close Main Purge valve Temperature diffrence between opening and and closing setpoint of main Purge valve on DO2 

2.0

 

10.0

 

5.0

 

RW

 

3019

V10Max_PPMax number of Purge points

Enter number of purge point (valves) connected to IPS

1168RW3026
BUBUnit config > Bubbler settings
 

 

BU6

 

 

On/Off Bubbler

Bubbler connected?

Select if a bubbler is connected and water valve (on DO15)will be controlled

OFF: Function disabled ON: Function enabled

 

 

0

 

 

1

 

 

0 – OFF

 

Enum 1

 

 

RW

 

 

3032

 

BU1

 

Bubbler time

Bubbler time

Time for water valve to open for adding water to bubbler after start of compressor

 

0

 

720

 

30

 

s

 

RW

 

3033

 

BU2

 

Bubbler manual off time

Bubbler manual off time

Only active if BU3, Bubbler man start=ON Se description for BU3, Bubbler man start

 

0

 

100

 

1

 

min

 

RW

 

3034

 

 

BU3

 

 

Bubbler man start

Manual opening of water valve for bubbler

Select manual opening of water valve – DO15

OFF: Function disabled

ON: Function enabled. Water valve will be open for the time ,given by BU3, Bubbler man start, have expired and close again

 

 

0

 

 

1

 

 

0 – OFF

 

Enum 1

 

 

RW

 

 

3035

Human Machine Interface (HMI) is the interface between the IPS and the user. Here the key pad and the display on the MCX15B2

Label IDParameter NameDescription and selection optionsMin.Max.Value/ TypeUnitRWMODBUS

Register

 

BU4

 

Clean period

Bubbler cleaning program

Setting of time between start cleaning of bubbler. Se description for BU5, Clean duration

 

0

 

72

 

24

 

h

 

RW

 

3036

 

BU5

 

Clean duration

Bubbler cleaning program – duration

Once the Cleaning start period, given by BU4, Clean period, has has passed, the water valve – DO15, will open until the time give by BU5, Clean duration has expired

 

0

 

100

 

5

 

min

 

RW

 

3037

 

BU7

 

Water stop delay

Water stop delay

Delay for closing water valve – DO15 after main purge valve – DO2 is closed

 

0

 

360

 

30

 

sec

 

RW

 

3038

LIMUnit config > Limits settings
LI3BPLMinCalibration Low Pressure tranmitter R452A. [bar]

Minimum value

-1.025.00.1barRW3051
F06BPLMinCalibration Low Pressure tranmitter R452A. [psi]

Minimum value

-14.5362.61.4PsiRW3052
LI6BPHMaxCalibration of High Pressure tranmitter R717. Min [bar]

Maximum value

-1.059.024.0barRW3057
F09BPHMaxCalibration of High Pressure tranmitter R717. Min [psi]

Maximum value

-14.5855.7348.0PsiRW3058
 

 

CM1

 

 

Setpoint

Setpoint [bar]

Minimum pressure at when the purging process will start.

If the P717 pressure (AI2) – is lower than this setpoint, Purge point 1 will open, then Purge point 2 automaticly etc.

Once purging a given Purge point and P717 pressure (AI2) – is higher than this setpoint, the cycle with compressor will start.

See also V48, Setpoint_Out

 

 

5.0

 

 

12.0

 

 

6.5

 

 

bar

 

 

RW

 

 

3061

 

 

F10

 

 

Setpoint

Setpoint [psi]

Minimum pressure at when the purging process will start.

If the P717 pressure (AI2) – is lower than this setpoint, Purge point 1 will open, then Purge point 2 automaticly etc.

Once purging a given Purge point and P717 pressure (AI2) – is higher than this setpoint, the cycle with compressor will start.

See also V48, Setpoint_Out

 

 

41.0

 

 

174.0

 

 

94.2

 

 

Psi

 

 

RW

 

 

3062

UNIService > Unit
 

UN1

 

Unit sensor

Display unit

0:MET: Metric units – Celsius (°C) and Bar 1:IMP: Imperial units – Fahrenheit (°F) and psi

 

0

 

1

0 –

Metric

Enum 6 

RW

 

3065

LOGStatus var > MCX Design Hotspots
C01Reset AlarmsReset Alarms020RW1859
 

V02

 

SystemOnOff

System ON / OFF

Status of both intermal and external mainswitch and internal main switch

 

-32768

 

32767

 

0

 

Read

 

8101

V03ValveStatusPurge Valve status

Startus of Main purge valve AKVA – DO2

-32768327670Read8102
V04CompressorStatusCompressor Status

Startus of Compressor operation – DO1

-32768327670Read8103
 

V06

 

PressTotemp

Pressure to temperature

Pressure form Low Pressure tranmitter R452A, AI1 calculated to temperature

 

-327.7

 

327.7

 

0.0

 

Read

 

8104

 

V07

 

ValveCount

Valve counter

The amount of purge valve activations for Main purge valve AKVA

– DO2

 

-2147483648

 

2147483647

 

0

 

Read

 

8105

 

V08

 

ComprTime

ComprTime

Remaining time for compressor pull-down for the actual purge point cycle

 

-2147483648

 

2147483647

 

0

 

Read

 

8107

V09COmprStartAfterCOmprStartAfter

Delay of compressor start between the purging cycles

-214748364821474836470Read8109
V11ValveHourValve Hours

The amount of hours that the main purge valve has been active

-214748364.8214748364.70.0Read8111
 

V12

 

StatusKL

Startus of relay (KL) operation compressor

Status of KL01 relay (compressor) See electrical diagram

 

-32768

 

32767

 

0

 

Read

 

8113

V13WaringComprWarning compressor

Indicates problem with compressor status

-32768327670Read8114
 

 

 

 

 

V14

 

 

 

 

 

ValveSetpoint

Main Purge valve setpoint

Temperature threshhold for the opening of the Main purge valve AKVA on DO2

Correspond to “”VOpenT”” on HMI

By default (“”VClseT”” – “”VOpenT””)= 5K(9R)

The 5K(9R) window will move with the Psat717 on AI2.

If Psat717 is increasing both “”VClseT”” and “”VOpenT”” will increase, but with with a difference with 5K(9R)

If Psat717 is decreasing both “”VClseT”” and “”VOpenT”” will decrease, but with with a difference with 5K(9R)

See also:

V15, Valve Close V42, BPHStatus

 

 

 

 

 

-2147483648

 

 

 

 

 

2147483647

 

 

 

 

 

0

 

 

 

 

 

Read

 

 

 

 

 

8115

Label IDParameter NameDescription and selection optionsMin.Max.Value/ TypeUnitRWMODBUS

Register

 

 

 

 

V15

 

 

 

 

ValveClose

Main Purge valve setpoint

Temperature threshhold for the closing of the Main purge valve AKVA on DO2

Correspond to “”VClseT”” on HMI

By default (“”VClseT”” – “”VOpenT””)= 5K(9R)

If Psat717 is increasing both “”VClseT”” and “”VOpenT”” will increase, but with with a difference with 5K(9R)

If Psat717 is decreasing both “”VClseT”” and “”VOpenT”” will decrease, but with with a difference with 5K(9R)

See also V14, ValveSetpoint V42, BPHStatus

 

 

 

 

-2147483648

 

 

 

 

2147483647

 

 

 

 

0

 

 

 

 

Read

 

 

 

 

8117

 

V16

 

Event1

Purge event no. 1

Purge cycle event counts of minutes that the purge valve has been open, during a finished cycle

 

-3276.8

 

3276.7

 

0.0

 

Read

 

8118

 

V17

 

Event2

Purge event no. 2

Purge cycle event counts of minutes that the purge valve has been open, during a finished cycle

 

-3276.8

 

3276.7

 

0.0

 

Read

 

8120

 

V18

 

Event3

Purge event no. 3

Purge cycle event counts of minutes that the purge valve has been open, during a finished cycle

 

-3276.8

 

3276.7

 

0.0

 

Read

 

8122

 

V19

 

Event4

Purge event no. 4

Purge cycle event counts of minutes that the purge valve has been open, during a finished cycle

 

-3276.8

 

3276.7

 

0.0

 

Read

 

8124

 

V20

 

Event5

Purge event no. 5

Purge cycle event counts of minutes that the purge valve has been open, during a finished cycle

 

-3276.8

 

3276.7

 

0.0

 

Read

 

8126

 

V21

 

Event6

Purge event no. 6

Purge cycle event counts of minutes that the purge valve has been open, during a finished cycle

 

-3276.8

 

3276.7

 

0.0

 

Read

 

8128

 

V22

 

Event7

Purge event no. 7

Purge cycle event counts of minutes that the purge valve has been open, during a finished cycle

 

-3276.8

 

3276.7

 

0.0

 

Read

 

8130

V23PP1Percentage for purge point valve no. 1

The time percentage split for this purge point

-32768327670Read8132
V24PP2Percentage for purge point valve no. 2

The time percentage split for this purge point

-32768327670Read8134
V25PP3Percentage for purge point valve no. 3

The time percentage split for this purge point

-32768327670Read8136
V26PP4Percentage for purge point valve no. 4

The time percentage split for this purge point

-32768327670Read8138
V27PP5Percentage for purge point valve no. 5

The time percentage split for this purge point

-32768327670Read8140
V28PP6Percentage for purge point valve no. 6

The time percentage split for this purge point

-32768327670Read8142
V29PP7Percentage for purge point valve no. 7

The time percentage split for this purge point

-32768327670Read8144
V30PP8Percentage for purge point valve no. 8

The time percentage split for this purge point

-32768327670Read8146
V31Val1Status for purge point valve no. 1

This indicates if the purge point is active (open)

-32768327670Read8148
V32Val2Status for purge point valve no. 2

This indicates if the purge point is active (open)

-32768327670Read8149
V33Val3Status for purge point valve no. 3

This indicates if the purge point is active (open)

-32768327670Read8150
V34Val4Status for purge point valve no. 4

This indicates if the purge point is active (open)

-32768327670Read8151
V35Val5Status for purge point valve no. 5

This indicates if the purge point is active (open)

-32768327670Read8152
V36Val6Status for purge point valve no. 6

This indicates if the purge point is active (open)

-32768327670Read8153
V37Val7Status for purge point valve no. 7

This indicates if the purge point is active (open)

-32768327670Read8154
V38Val8Status for purge point valve no. 8

This indicates if the purge point is active (open)

-32768327670Read8155
 

V40

 

TempStatus

NonCondensable gas Temperature sensor

NC temperature sensor

The measured NC temperature sensor. From AI5

 

-32768

 

32767

 

0

 

Read

 

8156

V41BPLStatusLow Pressure tranmitter R452A

The measured pressure R452A. From AI1

-32768327670Read8157
V42BPHStatusHigh Pressure tranmitter R717

The measured pressure R717. From AI2

-214748364821474836470Read8158
 

V43

 

DisTemp

Discharge Temperature

The measured temperature on the discharge line of compressor. From AI3

 

-32768

 

32767

 

0

 

Read

 

8159

Label IDParameter NameDescription and selection optionsMin.Max.Value/ TypeUnitRWMODBUS

Register

 

V44

 

SuctionTemp

Suction Temperature

The measured temperature at the main purge valve. From AI4

 

-2147483648

 

2147483647

 

0

 

Read

 

8160

 

 

V45

 

 

TshValveStatus

LOW charge operation

Linked to below mention text on HMI

If V46, TshCalculate > 15 K then showing “”TshValve OFF”” the main purge valve, D02 will close

If V46, TshCalculate < 15 K then showing “”TshValve ON”” is normal

operation

 

 

-32768

 

 

32767

 

 

0

 

 

Read

 

 

8161

 

 

 

V46

 

 

 

TshCalculate

Superheat calculated

Calculated Superheat= (T452- P452[C])

T452: Suction Temperature R452A sensor from AI4

P452[C]: Low Pressure tranmitter R452A from AI1 calculated into temperature

Shown on HMI as “”Tsh Calculate””

See also:

V06, PressTotemp V44, SuctionTemp

 

 

 

-2147483648

 

 

 

2147483647

 

 

 

0

 

 

 

Read

 

 

 

8162

 

V47

 

ALARActive

Alarm active

One or more alarms active 0: No Alarm

1: One or more alarms active

 

0

 

1

 

0

 

Read

 

8164

 

V48

 

Setpoint_Out

Read out of setpoint

Similar to readout on HMI: “”P717Off”” See also CM1, Setpoint

 

-2147483648

 

2147483647

 

0

 

Read

 

8165

 

V49

 

Point_Status

Read out of which Purge point No. is active

Readout of which Purge point number that is actively purging. Similar to number in HMI

 

-32768

 

32767

 

0

 

Read

 

8167

V50SysOFFRead out if IPS is not in operation

Read out if IPS is not in operation

-32768327670Read8168
V51PP9Percentage for purge point valve no. 9

The time percentage split for this purge point

-214748364821474836470Read8169
V52PP10Percentage for purge point valve no. 10

The time percentage split for this purge point

-214748364821474836470Read8171
V53PP11Percentage for purge point valve no. 11

The time percentage split for this purge point

-214748364821474836470Read8173
V54PP12Percentage for purge point valve no. 12

The time percentage split for this purge point

-214748364821474836470Read8175
V55PP13Percentage for purge point valve no. 13

The time percentage split for this purge point

-214748364821474836470Read8177
V56PP14Percentage for purge point valve no. 14

The time percentage split for this purge point

-214748364821474836470Read8179
V57PP15Percentage for purge point valve no. 15

The time percentage split for this purge point

-214748364821474836470Read8181
V58Val9Status for purge point valve no. 9

This indicates if the purge point is active (open)

-32768327670Read8183
V59Val10Status for purge point valve no. 10

This indicates if the purge point is active (open)

-32768327670Read8184
V60Val11Status for purge point valve no. 11

This indicates if the purge point is active (open)

-32768327670Read8185
V61Val12Status for purge point valve no. 12

This indicates if the purge point is active (open)

-32768327670Read8186
V62Val13Status for purge point valve no. 13

This indicates if the purge point is active (open)

-32768327670Read8187
V63Val14Status for purge point valve no. 14

This indicates if the purge point is active (open)

-32768327670Read8188
V64Val15Status for purge point valve no. 15

This indicates if the purge point is active (open)

-32768327670Read8189
V66ResetMemReset Memory010RW9902
V66PLT_Out_TimerTimeout for PLT timer-214748364821474836470Read8191
 

V67

 

Bubler

Water solenoid for Bubbler Status

This indicates if the Water solenoid is closed or open. Connected on DO15

 

-32768

 

32767

 

0

 

Read

 

8193

V68ICFD_StatusICFD Status

This indicates if the ICFD is closed or open. Connected on DO6

-32768327670Read8194
V69Val16Status for purge point valve no. 16

This indicates if the purge point is active (open)

-32768327670Read8195
 

V70

 

Liter

Amount of NC liters removed

Show how many liters of Non Condensable gases have been removed in total

 

-2147483648

 

2147483647

 

0

 

Read

 

8196

V71PP16Percentage for purge point valve no. 16

The time percentage split for this purge point

-214748364821474836470Read8198
ALARMS

E type: System related

A type: General Process alarms All Auto Reset, except E13

Parameter NameDescriptionMin.Max.Value/ TypeUnitRWADU
A01General alarmIf DI3, General Alarms is OFF, it leads to shut down of IPS 801AUTOACTIVERead1901 .08
E01NC Temp Sensor FaultAI5, NC temperatrue sensor fault01AUTOACTIVERead1901 .09
E02BPL Sensor FaultAI1, Low Pressure R452A tranmitter fault01AUTOACTIVERead1901 .10
E03BPH Sensor FaultAI2, High Pressure R717 tranmitter fault01AUTOACTIVERead1901 .11
E04Dis.Temp.Sens Low temperatureAI3, Discharge Temperature R452A sensor. Low temperature alarm01AUTOACTIVERead1901 .12
E05Dis.Temp.Sens Hi temperatureAI3, Discharge Temperature R452A sensor. High temperature alarm01AUTOACTIVERead1901 .13
E06Low pressure BPLAI1, Low Pressure R452A tranmitter. Low pressure alarm01AUTOACTIVERead1901 .14
E07Hi pressure BPLAI1, Low Pressure R452A tranmitter. High pressure alarm01AUTOACTIVERead1901 .15
E08Low pressure BPHAI2, High Pressure R717 tranmitter. Low pressure alarm01AUTOACTIVERead1901 .00
E09Hi pressure BPHAI2, High Pressure R717 tranmitter. High pressure alarm01AUTOACTIVERead1901 .01
E10System is OFFIf DI2, (external) Main Switch is OFF, it leads to shut down of IPS01AUTOACTIVERead1901 .02
E11Memory is fullA memory reset is required01AUTOACTIVERead1901 .03
E12Totla purge time errorOccurs when PLT is activated. System will automatically restart when CST has expired01AUTOACTIVERead1901 .04
 

E13

 

Compressor EROR

Feedback from compressor relay KL1 in electrical panel of IPS

If DI1, Status KL1 – Compressor in operation, is OFF, while DO1, Compressor is ON, it leads to to shut down of IPS

 

0

 

1

 

AUTO

 

ACTIVE

 

Read

 

1901 .05

E14Liquid alarmIf DI4, LLS 4000 is OFF (liquid in the evaporator), it leads to shut down of IPS01Manual ModeACTIVERead1901 .06
E15Memory wrong!Carry out: Reset to factory setting01AUTOACTIVERead1901 .07
E16Discharge sensor errorAI3, Discharge Temperature R452A sensor fault01AUTOACTIVERead1902 .08
E17Suction sensor errorAI4, Suction Temperature R452A sensor fault01AUTOACTIVERead1902 .09
E18Tsh AlarmSuperheat alarm. If V46, TshCalculate> Alarm setting default Delta 15 K (LI7, Tsh Danfoss only.)01AUTOACTIVERead1902 .10
E19NC.Temp.Sensor Hi temperatureAI5, NonCondensable gas Temperature sensor High temperature alarm01AUTOACTIVERead1902 .11
E20NC.TempSens Low temperatureAI5, NonCondensable gas Temperature sensor Low temperature alarm (-10 0C)01AUTOACTIVERead1902 .12
E21TempSucion.Sens Hi temperatureAI4, Suction Temperature R452A sensor. High temperature alarm01AUTOACTIVERead1902 .13
E22TempSucion.Sens Low temperatureAI4, Suction Temperature R452A sensor. Low temperature alarm01AUTOACTIVERead1902 .14
E23Configuration errorNo Expansion panel found01AUTOACTIVERead1902 .15
E24Link errorNo Expansion panel lost. Check CAN connection01AUTOACTIVERead1902 .00
I/O CONFIGURATION
PARAMETER NAMEDescriptionMINMAXVALUE/ TYPEUNITRWADU
AIANALOG INPUTS
1BPL-1/34Low Pressure R452A tranmitter-1.034.00-5 VRead18503
2BPH-1/59High Pressure R717 tranmitter-1.059.00-5 VRead18504
3Dis. TempDischarge Temperature R452A sensor-30.0170.0PT1000Read18502
4Suction TempSuction Temperature R452A sensor-50.0170.0PT1000Read18506
5NC TempNonCondensable gas Temperature sensor-50.0170.0PT1000Read18505
6
7
8
9
10
11
12
13
14
15
16
17
18
Parameter NameDescriptionMin.Max.Value/ TypeUnitRWADU
DIDIGITAL INPUTS
1Status KL1Status KL1 – Compressor in operation01N.O.Read17504
2On/OffOn/Off – External Mainswitch01N.O.Read17502
3General AlarmGeneral Alarm – SW prepared01N.O.Read17503
4LiquidAlarmLiquid Alarm – from LLS 4000/4000U01N.O.Read17505
5SwitchSwitch – Switch to the next purge point (pulse). SW prepared01N.O.Read17506
6Bubbler OnBubbler On – Force Bubbler solenoid ON. SW prepared01N.O.Read17507
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
AOANALOG OUTPUTS
1
2
3
4
5
6
7
8
9
10
DODIGITAL OUTPUTS
1CompressorCompressor01N.O.Read18007
2ValveValve – Main purge valve AKVA01N.O.Read18008
3GreenGreen – Lamp in front panel – Standby01N.O.Read18004
4YellowYellow- Lamp in front panel – Run01N.O.Read18005
5DO_RedRed – Lamp in front panel – Error01N.O.Read18006
6ICFD_ValveICFD_Valve01N.O.Read18017
7Valve1Purge valve no. 101N.O.Read18009
8Valve2Purge valve no. 201N.O.Read18010
9Valve3Purge valve no. 301N.O.Read18011
10Valve4Purge valve no. 401N.O.Read18012
11Valve5Purge valve no. 501N.O.Read18013
12Valve6Purge valve no. 601N.O.Read18014
13Valve7Purge valve no. 701N.O.Read18015
14Valve8Purge valve no. 801N.O.Read18016
15BublerWater valve for bubler01N.O.Read18018
16Valve9Purge valve no. 901N.O.Read18019
17Valve10Purge valve no. 1001N.O.Read18020
18Valve11Purge valve no. 1101N.O.Read18021
19Valve12Purge valve no. 1201N.O.Read18022
20Valve13Purge valve no. 1301N.O.Read18023
21Valve14Purge valve no. 1401N.O.Read18024
22Valve15Purge valve no. 1501N.O.Read18025
23AlarmAlarm01N.O.Read18002

Occurring active alarms, possible reasons and recommended action

LabelParameter NameDescriptionPossible ReasonRecommended action
ALARMS
 

A01

 

General alarm

 

Input from AI3 Leads to shut down of IPS 8

 

Fault in system connected to the DIO4

 

Input from AI3 Leads to shut down of IPS 9

E01Temp Sensor FaultIndicates no signal from temperature sensor (R452a)Broken wire to R452a temperature sensorRepair temperature sensor wire or replace temperature sensor
E01Temp Sensor FaultIndicates no signal from temperature sensor (R452a)Electrical supply failure supplying R452a temperature sensorRepair or replace power source
 

E01

 

Temp Sensor Fault

Indicates no signal from temperature sensor (R452a)Temperature measurement of the R452a line is out of rangeCompare temperature with another temperature sensor reading and replace temperature sensor if needed
E02BPL Sensor FaultIndicates no signal from pressure transmitter (R452a)Broken wire to R452A pressure transmitterRepair pressure transmitter wire or replace pressure transmitter
E02BPL Sensor FaultIndicates no signal from pressure transmitter (R452a)Electrical supply failure to the R422a pressure transmitterRepair or replace power source
 

E02

 

BPL Sensor Fault

Indicates no signal from pressure transmitter (R452a)Pressure measurement of the R452a line is out of rangeCompare pressure with another pressure reading and replace pressure transmitter if needed
E03BPH Sensor FaultIndicates no signal from pressure transmitter (R717)Broken wire to R717 pressure transmitterRepair pressure transmitter wire or replace pressure transmitter
E03BPH Sensor FaultIndicates no signal from pressure transmitter (R717)Electrical supply failure to the R717 pressure transmitterRepair or replace power source
 

E03

 

BPH Sensor Fault

Indicates no signal from pressure transmitter (R717)Pressure measurement of the R717 line is out of rangeCompare pressure with another pressure reading and replace pressure transmitter if needed
E04Low temperatureIndicates too low ambient temperature (<-10 °C)Too low ambient temperatureMove the IPS to a higher ambient temperature
E05High temperatureIndicates too high ambient temperature (>120 °C)Too high ambient temperatureMove the IPS to a lower ambient temperature
E05High temperatureLow R452a charge because of possible leakLocate and repair leakMove the IPS to a lower ambient temperature
 

E06

 

Low pressure BPL

 

Indicates too low R452a pressure

 

Choked restrictor / wrong piping

Factory setting 0.3 bar, we can have several problems: a) Restrictor is blocked (clean it).

b) Wrong piping and as addition ammonia is

draining, so check piping’s. c) Check SV float

E07High pressure BPLIndicates too high R452a pressureR452s system pressure too higha) Expansion valve is not working

b) To high ambient temperature (24 bar /54 ºC)

E08Low pressure BPHIndicates too low R717 pressureClosed stop valvePurge points are blocked, or flange is blocked with rubber plug
E09High pressure BPHIndicates too high R717 pressureR717 system pressure too highPressure is 24 bar
E10System is OFFIndicates status of the main switchMain switch is OFFSwitch ON the main switch
E11Memory is fullA memory reset is requiredMemory is full from long time operationClean MCX memory by means of finding Parameters_UnitConfig_
E12Totla purge time errorThis occurs when PLT is activated System will automatically restart when CST has expiredRestrictor is blockedReplace the restrictor
E13Compressor ERRORIndicates no status is being received from relay KL01Possible broken wire from the MCXRepair broken wire from the MCX
E14Liquid alarmSignal from the LLS that there is liquid in the evaporatorCheck piping
E15Memory wrong!Wrong counter valuesCarry out: Reset to factory setting
E16Discharge sensor errorIndicates no signal from temperature sensorCheck sensor
E17Suction sensor errorIndicates no signal from temperature sensorCheck sensor
  • All alarms except (*) activates red light on box outside
  • For alarms not resettable and/or cause not identified, please contact Danfoss
  • Level legend: 0 = Read view, 2 = Installer view (code 200) 3 = Danfoss Service view (Contact Danfoss)

Good Practice

  • The wiring of Modbus RTU (RS485) must be carried out in accordance with the standard ANSI/TIA/EIA-485-A-1998.
  • Galvanic separation shall be provided for segments crossing buildings.
  • The common ground shall be used for all devices on the same network inclusive router, gateways etc.
  • All bus connections in the cables are made with twisted pair wires.
  • The recommended cable type for this is AWG 22/0.32 mm2. If used for longer distances please use a AWG 20/0.5mm2 or AWG 18/0.75mm2 cable. The cables characteristic impedance shall be between 100 – 130Ω The capacitance between conductors shall be less than 100 pf per meter.

Note: the length of the cables influences the communication speed used. Longer cable lengths mean lower baud rate should be used. Maximum cable length allowed is 1200m. Use a minimum 20 cm distance between 110V/230V/400V power line cables and bus cables.

Maintenance/Service/Disposal

Table 03 Maintenance checklist – Perform once a year minimum

1Use P&I dagram and check that all powered components are working properly
2Check for alarms in the MCX controller
3Fans, air filters and fins must be cleaned for dirt and dust
4Expansion valve must be inspected and must be replaced if damaged
5Ensure expansion valves sensor bulb has good contact with suction line
6Replace water in water bubble bath. Check pH level frequently and replace when pH > 12.6
7Check cover is mounted correctly and all bolts are tightened accordingly
8Check and verify the amperage of the unit
9Check for abnormal compressor noises in normal operating conditions (may indicate loose bolts, worn bearings or pistons)

Table 04 Procedure to isolate IPS for servicing

MultipointSingle point purging from receiver
 

1

Close all supply lines from the purge points of the ammonia system.

Do not close any stop valve between IPS 8 and float valve

 

Restart the controller to force pump-down

2Restart the controller to force pump-downWait 20 minutes
3Wait 20 minutes
4Stop the compressor by turning the compressor switch QM1 to the off positionStop the compressor by turning the compressor switch QM1 to the off position
5Close the SVA shut-off valve in the drain line (located under the IPS 8)Close the SVA shut-off valve in the drain line (located under the IPS 8)
 

6

Release the remaining system pressure to atmosphere by opening the SNV drain valve. This can also be done by

attaching a permanent magnet on the AKVA 10 valve for forced

opening

Release the remaining system pressure to atmosphere by opening the SNV drain valve. This can also be done by

attaching a permanent magnet on the AKVA 10 valve for forced

opening

Disposal of the IPS 8
If an IPS 8 unit is worn out and has to be replaced, the disposal must be done in accordance with national legislation and only done by competent personnel.

Danfoss A/S

Any information, including, but not limited to information on the selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product. All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals