BOCK HGX34e 2 Pole Hg Compressors
Product Information:
The product in question is a refrigerating compressor
manufactured by Bock. It is available in multiple models:
HGX34e/255-2, HGX34e/315-2, HGX34e/315-2 S, and HGX34e/380-2. The
product comes with an operating guide and a translation of the
original instructions.
About these instructions:
These instructions should be read before assembling and using
the compressor to avoid misunderstandings and prevent damage.
Improper assembly and use can result in serious or fatal injury.
Safety instructions provided in these instructions must be
followed. The instructions should be passed on to the end customer
along with the compressor unit.
Contents:
- Safety instructions
- Electrical connection information
- Commissioning instructions
- Maintenance guidelines
- Technical data
- Dimensions and connections
- Declaration of incorporation
Safety:
1.1 Identification of safety instructions:
- DANGER: Indicates a dangerous situation that
can cause immediate fatal or serious injury. - WARNING: Indicates a dangerous situation that
can cause fatal or serious injury. - CAUTION: Indicates a dangerous situation that
can cause fairly severe or minor injury. - ATTENTION: Indicates a situation that can
cause property damage. - INFO: Provides important information or tips
on simplifying work.
1.2 Qualifications required of personnel:
Working on compressors requires personnel who are qualified to
work on pressurized refrigerant systems. This includes engineers
and professionals with comparable training who can assemble,
install, maintain, and repair refrigeration and air-conditioning
systems. Personnel must be capable of assessing the work and
recognizing potential dangers.
1.3 General safety instructions:
Refrigerating compressors are pressurized machines and require
caution and care during handling. The maximum permissible
overpressure should not be exceeded, even for testing purposes.
1.4 Intended use:
The compressor should not be used in potentially explosive
environments. These assembly instructions describe the standard
version of the compressor manufactured by Bock and are intended for
installation in a machine.
Product Usage Instructions:
Follow these instructions for proper usage of the refrigerating
compressor:
Commissioning:
- Perform necessary preparations for start-up.
- Conduct a pressure strength test to ensure the compressor’s
integrity. - Perform a leak test to check for any refrigerant leaks.
- Complete the evacuation process.
- Add the required amount of refrigerant charge.
- Start the compressor.
- Avoid slugging during operation.
Maintenance:
- Prepare for maintenance tasks.
- Carry out the necessary work as specified.
- Refer to the spare parts recommendation and accessories for
replacements. - Use recommended lubricants or oil for maintenance.
- Follow the decommissioning process when necessary.
Note: For detailed technical data, dimensions, connections, and
declaration of incorporation, please refer to the user manual.
BOCK® HGX34e 2-pole
Operating guide
HGX34e/255-2 HGX34e/315-2 HGX34e/315-2 S HGX34e/380-2
Translation of the original instructions
AQ453056555765en-000201
About these instructions
Read these instructions before assembly and before using the compressor. This will avoid misunderstandings and prevent damage. Improper assembly and use of the compressor can result in serious or fatal injury. Observe the safety instructions contained in these instructions. These instructions must be passed onto the end customer along with the unit in which the compressor is installed.
D GB F E
2 | AQ453056555765en-000201
© Danfoss | Climate Solutions | 2023.07
Contents
1 Safety
1.1 Identification of safety instructions 1.2 Qualifications required of personnel 1.3 General safety instructions 1.4 Intended use
2 Product description 2.1 Short description 2.2 Name plate 2.3 Type key 3 Areas of application 3.1 Refrigerants 3.2 Oil charge 3.3 Limits of application 4 Compressor assembly 4.1 Storage and transport 4.2 Setting up 4.3 Maximum permissible inclination 4.4 Pipe connections 4.5 Pipes 4.6 Laying suction and pressure lines 4.7 Operating the shut-off valves 4.8 Operating mode of the lockable service connections – suction line valve 4.9 Operating mode of the lockable service connections – discharge line valve
5 Electrical connection
5.1 Information for contactor and motor contactor selection 5.2 Connection of the driving motor – star circuit 5.3 Connection of the driving motor – part-winding circuit 5.4 Circuit diagram 5.5 Electronic trigger unit INT69 G 5.6 Connection of the electronic trigger unit INT69 G 5.7 External connection INT69 G 5.8 Function test of the trigger unit INT69 G
6 Commissioning 6.1 Preparations for start-up 6.2 Pressure strength test 6.3 Leak test 6.4 Evacuation 6.5 Refrigerant charge 6.6 Start-up 6.7 Avoid slugging
7 Maintenance 7.1 Preparation 7.2 Work to be carried out 7.3 Spare parts recommendation/accessories 7.4 Lubricants / oil 7.5 Decommissioning
8 Technical data
9 Dimensions and connections
10 Declaration of incorporation
Page 4
6 8 10
14
D
GB
F
E
20
22
24 25 26
© Danfoss | Climate Solutions | 2023.07
AQ453056555765en-000201 | 3
1| Safety
1.1 Identification of safety instructions:
DANGER
Indicates a dangerous situation which, if not avoided, will cause immediate fatal or serious injury.
WARNING Indicates a dangerous situation which, if not avoided, may cause fatal or serious injury.
CAUTION Indicates a dangerous situation which, if not avoided, may cause fairly severe or minor injury.
ATTENTION Indicates a situation which, if not avoided, may cause property damage.
INFO
Important information or tips on simplifying work.
D
GB 1.2 Qualifications required of personnel
F
E
WARNING Inadequately qualified personnel poses the risk of accidents, the
consequence being serious or fatal injury. Work on compressors
is therefore reserved for personnel which is qualified to work on
pressurized refrigerant systems:
· For example, a refrigeration technician, refrigeration mechatronic
engineer. As well as professions with comparable training, which
enables personnel to assemble, install, maintain and repair refrigeration
and air-conditioning systems. Personnel must be capable of assessing
the work to be carried out and recognising any potential dangers.
4 | AQ453056555765en-000201
© Danfoss | Climate Solutions | 2023.07
1| Safety
1.3 General safety instructions
WARNING
Risk of accidents. Refrigerating compressors are pressurised machines and as such call for heightened caution and care in handling.
The maximum permissible overpressure must not be exceeded, even for testing purposes.
Risk of burns! – Depending on the operating conditions, surface temperatures of over 60°C on the discharge side or below 0°C on the suction side can be reached. – Avoid contact with refrigerant necessarily. Contact with refrigerant can cause severe burns and skin damage.
1.4 Intended use
D
WARNING The compressor may not be used in potentially explosive
environments!
GB
F
These assembly instructions describe the standard version of the compressor named in the title
E
manufactured by Bock. Bock refrigerating compressors are intended for installation in a machine
(within the EU according to the EU Directives 2006/42/EC Machinery Directive and 2014/68/EU Pres-
sure Equipment Directive).
Commissioning is permissible only if the compressor has been installed in accordance with these as-
sembly instructions and the entire system into which it is integrated has been inspected and approved
in accordance with legal regulations.
The compressors are intended for use in refrigeration systems in compliance with the limits of application.
Only the refrigerant specified in these instructions may be used.
Any other use of the compressor is prohibited!
© Danfoss | Climate Solutions | 2023.07
AQ453056555765en-000201 | 5
2| Product description
2.1 Short description · Semi-hermetic four-cylinder reciprocating compressor with oil pump lubrication. · Suction gas cooled drive motor.
Discharge shut-off valve
Valve plate
Oil pump D
GB
F
Fig. 1
E
Transport eyelet
Name plate Oil sight glass
Terminal box
Cylinder cover
Suction shut-off valve
Drive section Motor section
Fig. 2 Dimension and connection values can be found in Chapter 9
6 | AQ453056555765en-000201
© Danfoss | Climate Solutions | 2023.07
2| Product description
2.2 Name plate (example)
BOCK Bock GmbH, Benzstr. 7 72636 Frickenhausen, Germany
1
HGX34e/315-2
2
AX38125A001
3
24,3A
4
117A
5
19/28
Fig. 3
IP66
6
2277,,33
7 8
32,8 BSSEOEC555K5 lub E55 9
10
1 Type designation 2 Machine number
6 Voltage, circuit, frequency
} 7 Nominal rotation speed 50 Hz
3 maximum operating current 4 Starting current (rotor blocked)
8 Displacement 9 Oil type filled at the factory
5 ND (LP): max. permissible operating
10 Terminal box protection type
pressure (g) Low pressure side
HD (HP): max. permissible operating
pressure (g) High pressure side
D
Observe the limits of application diagrams!
Electrical accessories can change
GB
the IP protection class!
F
2.3 Type key (example)
E
HG X 3 4 e / 315-2 S
Motor variant 4) Number of poles Swept volume e-series Numbers of cylinders Size Oil charge ²) Series ¹)
¹) HG – Hermetic Gas-Cooled (suction gas-cooled) ²) X – Ester oil charge ³) S – More powerful motor e.g. air-conditioning applications
© Danfoss | Climate Solutions | 2023.07
AQ453056555765en-000201 | 7
3| Areas of application
3.1 Refrigerants · HFKW / HFC:
R134a, R407C
3.2 Oil charge
The compressors are factory-filled with the following oil type: – BOCK lub E55
Compressors with ester oil charge (BOCK lub E55) are marked with an X in the type designation (e.g. HGX34e/380-2).
INFO
For refilling, we recommend the above oil types.
Alternatives: see chapter 7.4
ATTENTION The oil level must be in the visible part of the sight glass; max.
damage to the compressor is oil level possible if overfilled or under- min. filled!
~~ 0,8 Ltr. Fig. 4 Fig. 4
3.3 Limits of application
D
ATTENTION Compressor operation is possible within the operating limits.
GB
These can be found in Bock compressor selection tool (VAP)
under vap.bock.de. Observe the information given there.
F
– Permissible ambient temperature (-20°C) – (+60°C)
E
– Max. permissible discharge end temperature 140°C.
– Max. permissible switching frequency 8x /h.
– A minimum running time of 3 min. steady-state condition
(continuous operation) must be achieved.
For operation with capacity regulator:
– Continuous operation, when the capacity regulator is activated, is
not permissible and can cause damage to the compressor.
– The suction gas superheat temperature may need to be reduced or
set individually when operating near to the threshold.
– When the capacity regulator is activated, the gas velocity in the system can not under certain circumstances ensure that suffici-
ent oil is transported back to the compressor. For operation with frequency converter:
– Control range of the compressor 15 – 50 Hz
– The maximum current and power consumption must not be exceeded. In the case of operation above the mains frequency,
the application limit can therefore be limited
– Use a heat protection thermostat. – Oil return at low frequency must be supplied.
When operating in the vacuum range, there is a danger of air entering
on the suction side. This can cause chemical reactions, a pressure
rise in the condenser and an elevated compressed-gas temperature.
Prevent the ingress of air at all costs!
8 | AQ453056555765en-000201
© Danfoss | Climate Solutions | 2023.07
3| Areas of application
Max. permissible operating pressure (LP/HP)1): 19/28 bar
1) LP = Low pressure HP = High pressure
D GB F E
© Danfoss | Climate Solutions | 2023.07
AQ453056555765en-000201 | 9
4| Compressor assembly
INFO
New compressors are factory-filled with inert gas. Leave this ser-
vice charge in the compressor for as long as possible and prevent
the ingress of air. Check the compressor for transport damage
before starting any work.
4.1 Storage and transport
?
Storage at (-30°C) – (+70°C), maximum permissible relative humidity 10% – 95%, no condensation Do not store in a corrosive, dusty, vaporous atmosphere or in a com-
bustible environment.
Use transport eyelet. Use lifting gear!
Do not lift manually!
4.2 Setting up
ATTENTION Fittings (e.g. pipe holders, additional units, mounting parts etc.) on the compressor are not permissible!
Provide adequate clearance for maintenance work.
D
Ensure adequate compressor ventilation.
GB
F
Do not use in a corrosive, dusty, damp atmosphere or a
combustible environment. E
Setup on an even surface or frame with sufficient loadbearing capacity. Single compressor preferably on vibration damper. Duplex and parallel circuits always rigid.
Sun protection: If the compressor is set up outdoors, it has to be protected from direct sunlight.
4.3 Maximum permissible inclination
ATTENTION Poor lubrication can damage the compressor. Respect the stated values
A
A
aa
A
A
aa
A max. 30°, max. 2 minutes
Fig. 5
a max. 15°, continuous operation
10 | AQ453056555765en-000201
© Danfoss | Climate Solutions | 2023.07
4| Compressor assembly
4.4 Pipe connections
ATTENTION
Damage possible. Do not solder as long as the compressor is under pressure. Superheating can damage the valve. Remove the pipe supports therefore from the valve for soldering and accordingly cool the valve body during and after soldering. Only solder using inert gas to inhibit oxidation products (scale).
Fig. 6: graduated internal diameter
The pipe connections have graduated inside diameters so that pipes
with standart millimetre and inch dimensions can be used.
The connection diameters of the shut-off valves are rated for maximum compressor output. The actual required pipe cross section must be matched to the output. The same applies for non-return valves.
4.5 Pipes
Pipes and system components must be clean and dry inside and free of scale, swarf and layers of
rust and phosphate. Only use air-tight parts.
Lay pipes correctly. Suitable vibration compensators must be provided to prevent pipes being
D
cracked and broken by severe vibrations.
Ensure a proper oil return.
GB
Keep pressure losses to an absolute minimum.
F
4.6 Laying suction and pressure lines
E
ATTENTION Improperly installed pipes can cause cracks and tears, the result being a loss of refrigerant.
INFO
Proper layout of the suction and discharge lines directly after
the compressor is integral to the system’s smooth running and
vibration behaviour.
A rule of thumb: Always lay the first pipe section starting from the shut-off valve downwards and parallel to the drive shaft.
Rigid fixed point
As short as possible
© Danfoss | Climate Solutions | 2023.07
Fig. 7
AQ453056555765en-000201 | 11
4| Compressor assembly
4.7 Operating the shut-off valves Before opening or closing the shut-off valve, release the valve spindle seal by approx. ¼ of a turn counter-clockwise. After activating the shut-off valve, re-tighten the adjustable valve spindle seal clockwise.
Release
Tighten
Valve spindle seal
Fig. 8
Fig. 9
4.8 Operating mode of the lockable service connections Suction line valve
Service connection closed
Connection cannot be shut off
D
GB
F
E
Spindle
Connection blocked
Pipe connection
Opening the shut-off valve:
Compressor
Spindle: turn to the left (counter-clockwise) as far as it will go.
–> Shut-off valve completely opened / service connection closed.
The connection which cannot be shut off is intended for safety devices.
Fig. 10
Service connection opened
Connection cannot be shut off
Spindle
Connection open
Pipe connection
Opening the service connection
Compressor
Spindle: Turn ½ – 1 turn clockwise.
–> Service connection opened / shut-off valve opened.
The connection which cannot be shut off is intended for safety devices.
Fig. 11
After activating the spindle, generally fit the spindle protection cap again and tighten with 14-16 Nm. This serves as a second sealing feature during operation.
12 | AQ453056555765en-000201
© Danfoss | Climate Solutions | 2023.07
4| Compressor assembly
4.9 Operating mode of the lockable service connections Discharge line valve
Service connection closed
Spindle
Connection blocked
Opening the shut-off valve: Spindle: turn to the left (counter-clockwise) as far as it will go. –> Shut-off valve completely opened / service connection closed.
Pipe connection
Compressor Fig. 12
Service connection opened
Spindle
Connection open
D
GB
Pipe connection
F
E
Opening the service connection Spindle: Turn ½ – 1 turn to the right clockwise. –> Service connection opened / shut-off valve opened.
Compressor Fig. 13
After activating the spindle, generally fit the spindle protection cap again and tighten with 14-16 Nm. This serves as a second sealing feature during operation.
© Danfoss | Climate Solutions | 2023.07
AQ453056555765en-000201 | 13
5| Electrical connection
5 Electrical connection
DANGER
Risk of electric shock! High voltage! Only carry out work when the electrical system is disconnected from the power supply!
ATTENTION When attaching accessories with an electrical cable, a minimum bending radius of 3 x the cable diameter must be maintained for laying the cable.
INFO
Connect the compressor motor in accordance with the circuit diagram
(see inside of terminal box).
Use suitable cable entry point of the correct protection type (see
name plate) for routing cables into the terminal box. Insert the strain
reliefs and prevent chafe marks on the cables.
Compare the voltage and frequency values with the data for the
mains power supply.
Only connect the motor if these values are the same.
D
5.1 Information for contactor and motor contactor selection
GB All protection devices and switching or monitoring units must be fitted in accordance with the local
F
safety regulations and established specifications (e.g. VDE) as well as with the manufacturer’s information. Motor protection switches are required! Motor contactors, feed lines, fuses and motor
E
protection switches must be rated on the basis of the maximum working current (see name plate).
For motor protection use a current-dependent and time-delayed overload protection device for moni-
toring all three phases. Set the overload protection device so that it must be actuated within 2 hours,
if there is 1.2 times the max. working current.
14 | AQ453056555765en-000201
© Danfoss | Climate Solutions | 2023.07
5| Electrical connection
5.2 Connection of the driving motor with star circuit Designation on the name plate
Y
Star-delta start-up is only possible on 230 V voltage supply. Example: 400 V Y
Direct start only
L1 L2 L3
D
5.3 Connection of the driving motor with part winding circuit Designation on the name plate
GB
F
Y/YY
E
Example:
Direct start YY with bridges
V2 W2 U2 V1 W1
U1
400 V
PW – start-up Y/YY without bridges
L1 L2 L3
PW II PW I
V2 W2
U2 V1 W1
U1
L1 L2 L3
L1 L2 L3
ATTENTION
Failure to do this results in opposed rotary fields and results in damage to the motor. After the motor starts up via partial winding 1, partial winding 2 must be switched on after a maximum delay of one second . Failure to comply can adversely affect the service life of the motor.
© Danfoss | Climate Solutions | 2023.07
AQ453056555765en-000201 | 15
5.4 Circuit diagramm for direct start
QA1
FC1.1
I> I> I>
1
3
5
QA2
2
4
6
FC2
SF1
QA2
FC1.1
L1 L2 L3 N PE
PE
D
1
2
GB
3
4
F
5
6
E
7
M
8
-EC1 3~
9
10
BT1
11
12
12 14 11 L N B1 B2
INT69G
CAonmscphrelusßskoarstteernmVinearldbicohxter
Fig. 14
BT1
Cold conductor (PTC sensor) motor winding
BT2
Thermal protection thermostat (PTC sensor)
FC1
Load circuit safety switches
FC2
Control power circuit fuse
BP1
High pressure safety monitor
BP2
Safety chain (high/low pressure monitoring)
BT3
Release switch (thermostat)
16 | AQ453056555765en-000201
© Danfoss | Climate Solutions | 2023.07
L1.1 L2.1 L3.1 L1.2
QA2 N PE
EB1 P>
BP1
BT2
BT2
P
BP2
BT3
D GB F E
QA1 SF1 EC1 QA2 INT69 G EB1
Main switch Control voltage switch Compressor motor Compressor contactor Electronic trigger unit INT69 G Oil sump heater
© Danfoss | Climate Solutions | 2023.07
AQ453056555765en-000201 | 17
5| Electrical connection
5.5 Electronic trigger unit INT69 G
The compressor motor is fitted with cold conductor temperature sensors (PTC) connected to the electronic trigger unit INT69 G in the terminal box. In case of excess temperature in the motor winding, the INT69 G deactivates the motor contactor. Once cooled, it can be restarted only if the electronic lock of the output relay (terminals B1+B2) is released by interrupting the supply voltage.
The hot gas side of the compressor can also be protected against overtemperature using thermal protection thermostats (accessory).
The unit trips when an overload or inadmissible operating conditions occur. Find and remedy the cause.
INFO
The relay switching output is executed as a floating changeover
contact. This electrical circuit operates according to the quiescent
current principle, i.e. the relay drops into a the idle position and
deactivates the motor contactor even in case of a sensor break or
open circuit.
5.6 Connection of the trigger unit INT69 G D
GB 1 F E
INFO
Connect the trigger unit INT69 G in accordance with the circuit dia-
2
3
4
5
gram. Protect the trigger unit with a delayed-action fuse (FC2) of
max. 4 A. In order to guarantee the protection function, install the trigger unit as the first element in the control power circuit.
or Protection MP10
L
S
M
1 N N 43 43 11 12 14
ATTENTION Measure circuit BT1 and BT2 (PTC sensor) must not come Ri1nto conRt2act with ex ternal voltage. This would destroy the trigger X2un1it2IN3T649 G5 a6nd PTC sensors.
INT69 G
OG OG
LN
+
Steuerstrom- BT1
–
kreis
+
BT2
–
+
BT1
+
BT2
–
B1 B2
12 14 11
N L
CSotenutreorlstcriorcmu-it
kreis
Fig. 15 Terminal box
18 | AQ453056555765en-000201
© Danfoss | Climate Solutions | 2023.07
0 5| Elec1trical con2 nection3
4
5
6
0
1
2
3
4
5
6
5.7 External connection INT69 G
Schaltschrank
SSwcihtaclhtsccharbainnket
INT69G INT69G
1 2 3 4 5 6 7 8 09 10 11 12
BT1
Cold conductor (PTC
sensor) motor winding
1 2 3 4 5 6 7 8 09 10 11 12
BT2
Heat protection thermo-
stat (PTC sensor)
EB1
Oil sump heater
EB1
BT1 BT2 BT2
D
EB1 Terminal BBTo1 x BT2 BT2
Fig. 16
GB
F 5.8 Function test of the trigger unit INT69 G
E Before commissioning, after troubleshooting or making changes to the control power circuit, check
the functionality of the trigger unit. Perform this check using a continuity tester or gauge.
Gauge state
Relay position
Relay position INT69 G
1. Deactivated state
11-12
2. INT69 G switch-on 3. Remove PTC connector
11-14 11-12
B2 12 14 11
1
4. Insert PTC connector
11-12
1
nderung nderung
Datum Datum
5. ReDsateumt af0t4e.12r.20m09 ains on
Bearb.
bauknecht
Name
GDeapturm. NBeoarmrb.
0084..0152..22002009 bauknecht
Urspr.
Gepr.
08.05.2020
Name Norm
Urspr.
11-14
Ers. f. Ers. f.
Ers. d. Ers. d.
Fig. 17
HG22e/34e HC
HG22e/34e HC
© Danfoss | Climate Solutions | 2023.07
AQ453056555765en-000201 | 19
6| Commissioning
6.1 Preparations for start-up
INFO
To protect the compressor against inadmissible operating conditions,
high pressure and low pressure pressostats are mandatory on the
installation side.
The compressor has undergone trials in the factory and all functions have been tested. There are therefore no special running-in instructions.
Check the compressor for transport damage!
6.2 Pressure strength test
The compressor has been tested in the factory for pressure integrity. If however the entire system is to be subjected to a pressure integrity test, this should be carried out in accordance with EN 378-2 or a corresponding safety standard without the inclusion of the compressor.
6.3 Leak test
DANGER Risk of bursting!
The compressor must only be pressurised using nitrogen (N2). Never pressurise with oxygen or other gases!
D
The maximum permissible overpressure of the compressor must
not be exceeded at any time during the testing process (see name
GB
plate data)! Do not mix any refrigerant with the nitrogen as this
F
could cause the ignition limit to shift into the critical range.
E
Carry out the leak test on the refrigerating plant in accordance with EN 378-2 or a corresponding
safety standard, while always observing the maximum permissible overpressure for the compressor.
6.4 Evacuation
ATTENTION
Do not start the compressor if it is under vacuum. Do not apply any voltage – even for test purposes (must only be operated with refrigerant).
Under vacuum, the spark-over and creepage current distances of the terminal board connection bolts shorten; this can result in winding and terminal board damage.
First evacuate the system and then include the compressor in the evacuation process. Relieve the compressor pressure. Open the suction and pressure line shut-off valves. Evacuate the suction and discharge pressure sides using the vacuum pump. At the end of the evacuation process, the vacuum should be < 1.5 mbar when the pump is switched off. Repeat this process as often as is required.
20 | AQ453056555765en-000201
© Danfoss | Climate Solutions | 2023.07
6| Commissioning
6.5 Refrigerant charge
CAUTION Wear personal protective clothing such as goggles and protective gloves!
Make sure that the suction and pressure line shut-off valves are open.
With the compressor switched off, add the liquid refrigerant directly to the condenser or receiver, breaking the vacuum. If the refrigerant needs topping up after starting the compressor, it can be topped up in vapour form on the suction side, or, taking suitable precautions, also in liquid form at the inlet to the evaporator.
ATTENTION Avoid overfilling the system with refrigerant!
To avoid shifts in concentration, zeotropic refrigerant blends must always only be filled into the refrigerating plant in liquid form. Do not pour liquid coolant through the suction line valve on the compressor. It is not permissible to mix additives with the oil and refrigerant.
6.6 Start-up
D
WARNING Ensure that both shut-off valves are open before starting the
GB
compressor! F
Check that the safety and protection devices (pressure switch, motor protection, electrical
E
contact protection measures, etc.) are all functioning properly.
Switch on the compressor and allow to run for a minimum of 10 min.
Check the oil level by: The oil must be visible in the sightglass.
ATTENTION If larger quantities of oil have to be topped up, there is a risk of oil hammer effects. If this is the case check the oil return!
6.7 Avoiding slugging
ATTENTION Slugging can damage the compressor and cause refrigerant to leak.
To prevent slugging:
The complete refrigeration system must be properly designed. All components must be compatibly rated with each other with regard to output (particularly the evaporator and expansion valves). Suction gas superheat at the compressor input should be min. 7 – 10 K. (check the setting of the expansion valve). The system must reach a state of equilibrium. Particularly in critical systems (e.g. several evaporator points), measures are recommended such as replacement of liquid traps, solenoid valve in the liquid line, etc. There should be no movement of coolant whatsoever while the compressor is at a standstill.
© Danfoss | Climate Solutions | 2023.07
AQ453056555765en-000201 | 21
7| Maintenance
7.1 Preparation WARNING
Before starting any work on the compressor: Switch off the compressor and secure it to prevent a restart. Relieve compressor of system pressure. Prevent air from infiltrating the system!
After maintenance has been performed: Connect safety switch. Evacuate compressor. Release switch lock.
7.2 Work to be carried out
Oil change: In principle, an oil change is not mandatory if the system is correctly manufactured
and operated. However, based on decades of experience we recommend that the following oil
change/service work is carried out:
– First oil change during the first maintenance of the system.
– Then after every 10,000 – 12,000 operating hours, though no more than 3 years, clean the
oil strainer at the same time. Dispose of the oil inside in accordance with the applicable
national regulations. D
Annual checks: Oil level, leak tightness, running noises, pressures, temperatures, function of
GB
auxiliary devices such as oil sump heater, pressure switch.
F
E
7.3 Spare parts recommendation/accessories
Available spare parts and accessories can be found on our compressor selection tool under vap.bock.de as well as at bockshop.bock.de.
Only use genuine Bock spare parts!
22 | AQ453056555765en-000201
© Danfoss | Climate Solutions | 2023.07
7| Maintenance
7.4 Lubricants / oil
The oil type filled as standard in the factory is marked on the name plate, and this should always be used, even in the case of maintenance units. Alternative oil types can vary significantly in quality due to additives or inferior raw materials by the manufacturer. Validation within the compressors entire operating limits can not be guaranteed, if such alternative oil types are used. It is for this reason, that we only recommend the use of oil from Bock! Bock assumes no liability for any damage arising from alternative oil types.
Refrigerants
HCFC (e.g. R134a, R407C)
Bock standard oil types BOCK lub E55
7.5 Decommissioning
Close the shut-off valves on the compressor. Drain the refrigerant (it must not be discharged into the environment) and dispose of it according to the regulations. When the compressor is depressurised, undo the fastening screws of the shut-off valves. Remove the compressor using an appropriate hoist. Dispose of the oil inside in accordance with the applicable national regulations.
D GB F E
© Danfoss | Climate Solutions | 2023.07
AQ453056555765en-000201 | 23
8| Technical data
Oil charge
Weight
D GB F E
24 | AQ453056555765en-000201
Type HGX34e/255-2
No. of cylinders
Displacement 50 Hz
(2900 rpm)
m3/h
Voltage 1
Electrical data 3
Max. Operating current
2 Y
Max. power consumption
2
Starting current
(rotor locked)
Y
Connections 4
Discharge Suction
line
line
DV
SV
Sound pressure
level
L/M/H 5
A
kW
A
kg mm (inch) mm (inch) Ltr.
dB(A)
44,3
25,8
16,0
117 95
62 / 59 / 58
380-420 V Y – 3 – 50 Hz
HGX34e/315-2
54,7
4
HGX34e/315-2 S
54,7
24,3
14,7
117 94
64 / 62 / 60,5
22 (7/8) 35 (13/8) 1,3
32,2
19,0
172 102
66 / 64 / 63
© Danfoss | Climate Solutions | 2023.07
HGX34e/380-2
66,1
38,0
23,5
172 102
67 / 64,5 / 64
1 Tolerance (± 10%) relative to the mean value of the voltage range. Other voltages and types of current on request.
2 – The specifications for max. power consumption apply for 50Hz operation. For 60Hz operation, the specifications have to be multiplied by the factor
1.2. The max. working current remains unchanged.
– Take account of the max. operating current / max. power consumption for
design of fuses, supply lines and safety devices. Fuse: Consumption
category AC3
3 All specifications are based on the average of the voltage range
4 For solder connections
5 L = low temperature (-35 / 40 °C), M = normal cooling (-10 / 45 °C), H = air conditioning (5 / 50°C) sound pressure level measured in low reflection measuring area, measuring distance 1m. Compressor operation at 50 Hz (1450 rpm), refrigerant R404A. Values stated are average values, tolerance ± 2 dB(A).
9| Dimensions and connections
7
7 HGX34e 2-poleig
6
6
5
5
4
4
3
135 273
135
+ 2
318 115
318 +2 115
46 78
Centre of gravity
X
17406 78 310
170 310
417 (450)
417 (450)
+2
535 (568)
+2
535 (568)
W
W Vibration
M10 Vdamper
X A B,L C
F,M J
282 +2
DV B1
A B,L C F,M J
4x 15 230 272
X
282 +2
DV B1
H,D1 O,K
4x 15 230 272 +2
(568)
X
Anschlüsse / Connections
Anschlüsse Connections
SV
Saugabsperrventil, Rohr Suction line valve, tube
(LS)*V Saugabspemrrmve (L)* Suction linemvma
Druckabsperrventil, Rohr DV
Discharge line valve, tube
(LD)V* Druckabspmermrv (L)* Discharge lminme
A ACnosncnhelcutsiosnSsauucgtsioenites,idneic, hntoat blosAcpkearbrACblenoasnrcnhelcutsiosnSZsoaululc
A1 B
H,D1 Anschluss Saugseite, absperrAba1r
Connection suction side, lockable
Anschluss Sau ConnectionZsoullc
Anschluss Druckseite, Connection discharge
nicht side,
naobBtslpoecrkACrabnobasnlrecnhelcutsiosnDZdoruilsl
B1 C
O,K Anschluss Druckseite,
Connection discharge
saibdsep, elorcrBbk1aarblACenosncnhelcutsiosnDZdoruilsl
CAonnsncehclutisosnÖolidl prurecksssiucrheesrhaefeittsysCscwhaitClctAehonrnsncehclutisosnZÖoolildll
D1 ACnosncnhelcutsiosnÖolrilürcektfuürhnrufrnogmvooiml sDeÖ1plaabrACasntocoshnrcenhiedlcuetsriosnÖZoolrillül
Ölablass F
Oil drain
Ölablass
F Oil drain
m
Stopfen Ölfüllung H
Oil charge plug
Stopfen Ölfüllu H Oil charge pZloulgl
J
Anschluss Ölsumpfheizung Connection oil sump heater
J
Anschluss Ölsu ConnectionZooilll
Schauglas K
Sight glass
Schauglas K Sight glassZoll
L ACnosncnhelcutsiosnWthäermrmeaslcphruottzethcteiormn oLthsetarmtACnoosnsctnahetlcutsiosnWZtohälelr
Ölsieb M
Oil filter
Ölsieb
M Oil filter
m
O
Anschluss Ölspiegelregulator O Connection oil level regulator
Anschluss Ölsp ConnectionZooilll
W
Anschluss Kältemittel EinspritzWung Connection for refrigerant injection
Anschluss Kält ConnectionZfoolrl
D (L)* = Lötanschluss / brazing conne(cLt)i*on= Lötansch
3 0 2 0
3 0 2 0
3 0 2 0
40
SV A1 A SV A1 A
GB
Dimensions in ( ) for HGX34e/315-2 S + 380-2 SV 90° rotatable
SV Suction line DV Discharge line
see technical data, Chapter 8
Dimensions in mm Fig. 18
F
ESchwin
M10 Vibratio 40
A A1 B B1 C
1 Maße in ( ) für Connection suction side, not lockable /8″ NPTF Dimensions in
H( )GfXor3H4eGMD/3Xiam13ß5e4e-ne2is/n3iSo1(n+5)s-f32üin8rS0H(-+)2Gf3Xo8r30H4-eG2/3X1354-e2/3SÄS1nu+5db-eje32rcu8tnS0tgoe-+c2nh3vaon8rgb0ee-hw2aitlhteonut
ÄnderMunagßeeninvomrbmehalten noticSeubjecDtimtoecnhsaionngseiwn imthmout
7 HalbhermetischerHVaelrbdhicehrmteertHisGch/eSr eVmerid-hicehrmteer tHicGco/ mSepmreis-hseorrmHeGtic compressor HG
Connection suction side, lockable /16″ UNF Typ / type
Teile-Nr./ part-no.
TtyyTtpypyepp/e/
Tpaerilte-n-NoTpr..ae/rilte-n-NTtoyyr.p.p/e/
Typ / type
TpaeriltTpe-aen-Nriolter.-.n-/Nor../TtyyppeTty/yppe/
Tpaerilte-n-NoTpr..ae/rilte-n-NTtoyyr.p.p/e/
Typ / type
Zeichn.-Nr. TpaeTpriaelteri-ltn-e-Non-Nr.o.r/../
Typ / type
Teile-N part-no
1 HG34e/215-4 Connection discharge side, not lockable /8″ NPTF HG34e/255-4
HG34e/315-4 HG34e/380-4
7 HG34e/215-4 HC Connection discharge side, lockable /16″ UNF HG34e/255-4 HC
16050 16051 16052 16053 16066 16067
HGHG34Xe3/241e5/2-145-4 16050 160H5G8 X34He/G23145e-4/215-4 S 1601568054 HG3H4GeX/23145e-/421S5-4 S 16054 160H6G2 X34He/G2X153-44eS/255-2
HGHG34Xe3/245e5/2-545-4 16051 160H5G9 X34He/G23545e-4/255-4 S 1601569055 HG3H4GeX/23545e-/425S5-4 S 16055 160H6G3 X34He/G2X553-44eS/315-2
HHHGGGHHHGGG333444XXXeee333///233444118eee550///332—181444505H–M44CL
3
16052 16053 L1G6066
111666002HHH668GGG015 XXX333444HHHeee///GGG332333181444505eee–M44///233L1185503—L444GSSS
HC 111666002111668666015000557670 HHHGGG333HHH444GGGeeeXXX///233333118444550eee—///444332181SSS505H–S44CSS5
16056 16057 LG16070
111666002HHH668GGG456 XXX333444HH-eee///GG332XX18150533–44S44eeSS//53381L05G–22
S
HGHG34Xe3/245e5/2-545HMCL 4 L1G6067 162H8G7 X34He/G23545eM/2L554-L4GS HC 1621867071 HG3H4GeX/23545e-/425S5HSC6 LG16071 162H8G8 X34-e/255 S 6 LG
1610660274 1610660375 111666110026666800-4567767 1628-8
HGX34e/255-2
1607
HGX34e/315-2
1607
HGX34e/315-2 S 1607
1.0850 HGX34e/380-2
–
1607 –
–
–
HG34e/315-4 HC
Connection oil pressure safety switch 1/8″ NPTF HG34e/380-4 HC
16068 HGHG34Xe3/341e5/3-145HMCL 5 L1G6068 162H8G9 X34He/G33145eM/3L155-L4GS HC 1621869072 HG3H4GeX/33145e-/431S5HSC7 LG16072 162H9G0 X34-e/315 S 7 LG 16069 HGHG34Xe3/348e0/3-840HMCL 6 L1G6069 162H9G1 X34He/G33840eM/3L806-L4GS HC 1621961073 HG3H4GeX/33840e-/438S0HSC9 LG16073 162H9G2 X34-e/380 S 9 LG
1629-0 1629-2
–
–
D1 Connection oil return from oil separator
F
Oil drain
Gußtoleranzen
1/4″ NPTF –
/
General
castinGg utoßletorlaenracensz:en –
/
GenerZael iccahsntuinnggtso-lNerra. n/ ces: Drawing-No.
Te Pa
Baumustergeprüft Nein / No
/
Type
examBNaienuinamt/iouNnso:tergeprüft
/
Type
examination:
M12 x 1,5 1. 0850 -1 Gewicht / Weight: (kg) –
Gewicht / Weight: (kg) –
H
Oil charge plug
Allgemeintoleranzen DIN ISO 2768-mK-E
/
GeneralADtloIlNgleeIrmSanOecine2ts7o6le8r-amnKze-En
/BGeenneernalntoulnergan/cDesescrip
1/4″ NPTF über / above 0.5 6 üb3e0r / ab1o2v0e 400.05 6 30 120 40
bis / up to
6 30 12b0is / u4p0t0o 10006 30 120 400 100
J
Connection oil sump heater
K
Sight glass
3 ±0.1 ±0.2 ±0.3 ±0.5 ±±00..81 ±0.2 ±0.3 ±0.5 ±0. /8″ NPTF Unbemaßte Radien / UndimenUsinobneemd araßdteii:R-adien / UOnbdeimrfeläncshioenneadngraadbiei:n-/
Indication of surface textu
1 1/8″- 18 UNEF DIN EN ISO 1302
L Connection thermal protection thermostat 1/8″ NPTF eoncrkefLpreshsWaonpiriupeegnwostaapiorfiwiopineeorrprrnteeatdgnrnsl)ai,rn.esfndosr000tccfrrjijmhohesanu|||aiuesdtfÖBBszmeistt,eeoiltodsrttanirrerVcZnsiiunhffeusffscerpsttuprkto(sBBaracsretnoctellaiaakdrtclltrhueittohoettnnsaneg,34in)odrd.gnheaelfesiüvlisieerptfsrredyessriveoitccefhWhnpewtaaairoielrrrtntednes, r000ajijls|||
Betrifft Blatt 4 ÖZludbruechkösricführe2rh-peoitlsesnchtfaelrtnetr Betrifft Blatt 3
(aBlsetZriuffbt eBhlaötrt
f3ü)r
2-pol
entfernt
(Betrifft
11205 1B1la2t0t 63) 11160
29.10.20 29.10.20 08.10.20
1S1. 2B0ü5ttner 1S1. 2B0ü6ttner 1S1. 1B6ü0ttner
J.2K9.e1u0e.2rl0eber J.2K9.e1u0e.2rl0eber J.0K8e.1u0e.r2le0ber
S. Büttner S. Büttner S. Büttner
J. Keuerleber J. Keuerleber J. Keuerleber
7 ©OMDanfos7s | OCCloiilmnfinaltteeecrStiool6untiooinl sle| v2e0l2r3e.0g7ula6tor 5 5 AQ4543056515517/M685″1e-2n-1×080410,U250N1E|F25 3 hhwmuudrhetznhauefmneidemomble.hredtotwuen,reeeiuriaoregofntnteesptiesssglfdvvuangtntnAiGrfttodegrteeenbühoeeotthialtw.nntsernrlgeriidornfseessn–,-..steuOatsdcduicosoZ0000tfehvaotnftwieenmhmhhhhounfdrnewinieapascadFr,||||eMchfgstVelalki.tABBBeldpicrletslwssitha/asrmeueee.avtitdtutiReerslftttiuhewAuesinnnrrrbsordenliiilitfutllufffa,ärgtlevfffPrthütlirittthzutogec.eaibsuegtnkhBBBmitieenexlultiiistctpcnlllnnayreSaaaohratgenrh-ecmetttg,sdevsdhmtttsguGmlsiadeoeenI322ouendrussgdntva+bheitneleleaurianiis3zaalcdTttletahtbvauDesrietoolotcnstieoio.rrhoraisibktnlZzsnthieueznaumfdeom.hd-otweiurNaoeofesislfdvvntnAitrtegteeehethi.lnntsrnrliirseess–,-..Lt GZ0000hhhhu-Bs||||ta.ABBBu/ueeerRftttenrrreiiiihfffavfffettth.BBBmllleaaatttvttt o322n+3Teile-Nr. LG-Baureihe
10699 10977 10724
15.07.20 28.02.20 28.01.20
J.1F0a6ß9b9ender 1S0. 9B7ü7ttner
J.1F0a7ß2b4ender
J.1K5e.0u7e.r2le0ber J. Faßbender
28A..0L2a.2y0h
S. Büttner
J.2K8e.0u1e.r2le0ber J. Faßbender
J. Keuerleber A. Layh
J. Keuerleber
10928
15.01.20 J.1F0a9ß2b8ender 15A..0L1a.2y0h J. Faßbender
A. Layh
Änd.-Nr. / Mod-No. Datum / DaÄtendB.-eNarr.b/. M/ Eoddi-tNedo. GDeapturümft//DAaptper.BMeaarßb./ D/ EimdeitnesdioGneprüft /PAapspsru. nMga/ßC/leDaimraenncseion
Rz 160
R
s
t
GEPAasBsoucnkgG/mCblHea-rBaennczestraße
10| Declaration of incorporation
Declaration of incorporation for incomplete machinery in accordance with EC Machinery Directive 2006/42/EC, Annex II 1. B
Manufacturer:
Bock GmbH Benzstraße 7 72636 Frickenhausen, Germany
We, as manufacturer, declare in sole responsibility that the incomplete machinery
Name: Types:
Semi-hermetic compressor HG(X)12P/60-4 S (HC) …………………… HG(X)88e/3235-4(S) (HC) UL-HGX12P/60 S 0,7……………………… UL-HGX66e/2070 S 60 HGX12P/60 S 0,7 LG …………………….. HGX88e/3235 (ML/S) 95 LG HG(X)22(P)(e)/125-4 A …………………… HG(X)34(P)(e)/380-4 (S) A HGX34(P)(e)/255-2 (A) ………………….. HGX34(P)(e)/380-2 (A)(K) HA(X)12P/60-4 ……………………………… HA(X)6/1410-4 HAX22e/125 LT 2 LG ……………………. HAX44e/665 LT 14 LG HGX12e/20-4 (ML/S) CO2 (LT) ……….. HGX44e/565-4 S CO2 UL-HGX12e/20 (S/ML) 0,7 CO2 (LT)… UL-HGX44e/565 S 31 CO2 HGX12/20-4 (ML/S/SH) CO2T………….. HGX46/440-4 (ML/S/SH) CO2 T UL-HGX12/20 ML(P) 2 CO2T…………. UL-HGX46/440 ML(P) 53 CO2T HGZ(X)7/1620-4 ……………………………. HGZ(X)7/2110-4 HGZ(X)66e/1340 LT 22…………………… HGZ(X)66e/2070 LT 35
HRX40-2 CO2 T H………………………….. HRX60-2 CO2 T H
Name:
Open type compressor
Types:
D
F(X)2 …………………………………… F(X)88/3235 (NH3) FK(X)1………………………………….. FK(X)3
GB
Serial number:
FK(X)20/120 (K/N/TK)…………….. FK(X)50/980 (K/N/TK) BC00000A001 BN99999Z999
F
complies with the following provisions of the above-mentioned Directive:
E
According to Annex I, points 1.1.2, 1.1.3, 1.1.5, 1.3.2, 1.3.3, 1.3.7, 1.5.1, 1.5.2, 1.5.13 and
1.7.1 to 1.7.4 (excepted 1.7.4 f) are fulfilled.
Applied harmonised standards, in particular:
EN ISO 12100 :2010
EN 12693
:2008
Safety of machinery — General principles for design — Risk assessment and risk reduction Refrigerating systems and heat pumps — Safety and environmental requirements — Positive displacement refrigerant compressors
Remarks:
We also declare that the special technical documentation for this incomplete machine has been created in accordance with Annex VII, Part B and we obligate to provide these upon reasoned request from the individual national authorities by data transfer.
Commissioning is prohibited until it has been confirmed that the machinery into which the incomplete machine above is to be incorporated complies with the EC Machinery Directive and an EC Declaration of Conformity, Annex II. 1. A exists.
Authorized person for compiling and handing over technical documentation:
Bock GmbH Alexander Layh Benzstraße 7 72636 Frickenhausen, Germany
Frickenhausen, 04th of January 2021
i. A. Alexander Layh, Global Head of R&D
26 | AQ453056555765en-000201
© Danfoss | Climate Solutions | 2023.07
10| Declaration of incorporation
Declaration of incorporation of partly completed machinery in accordance with UK Statutory Instrument Supply of Machinery (Safety) Regulations 2008, Annex II 1. B
Manufacturer:
Bock GmbH Benzstraße 7 72636 Frickenhausen, Germany
We, as manufacturer, declare in sole responsibility that the partly completed machinery
Name: Types:
Semi-hermetic compressor HG(X)12P/60-4 S (HC) …………………… HG(X)88e/3235-4(S) (HC) UL-HGX12P/60 S 0,7……………………… UL-HGX66e/2070 S 60 HGX12P/60 S 0,7 LG …………………….. HGX88e/3235 (ML/S) 95 LG HG(X)22(P)(e)/125-4 A …………………… HG(X)34(P)(e)/380-4 (S) A HGX34(P)(e)/255-2 (A) ………………….. HGX34(P)(e)/380-2 (A)(K) HA(X)22e/125-4 ……………………………..HA(X)6/1410-4 HAX22e/125 LT 2 LG ……………………. HAX44e/665 LT 14 LG HGX12e/20-4 (ML/S) CO2 (LT) ……….. HGX44e/565-4 S CO2 UL-HGX12e/20 (S/ML) 0,7 CO2 (LT)… UL-HGX44e/565 S 31 CO2 HGX12/20-4 (ML/S/SH) CO2T………….. HGX46/440-4 (ML/S/SH) CO2 T UL-HGX12/20 ML(P) 2 CO2T…………… UL-HGX46/440 ML(P) 53 CO2T HGZ(X)7/1620-4 ……………………………. HGZ(X)7/2110-4 HGZ(X)66e/1340 LT 22…………………… HGZ(X)66e/2070 LT 35
HRX40-2 CO2 T H………………………….. HR(Z)X60-2 CO2 T (H)(V)
Name:
Open type compressor
Types:
F(X)2 …………………………………………… F(X)88/3235 (NH3)
FK(X)1………………………………………….. FK(X)3
FK(X)20/120 (K/N/TK)…………………….. FK(X)50/980 (K/N/TK)
D
Serial number:
BC00000A001 BN99999Z999
GB
complies with the following provisions of the above-mentioned Statutory instrument:
F
According to Schedule 2, part1, points 1.1.2, 1.1.3, 1.1.5, 1.3.2, 1.3.3, 1.3.7, 1.5.1, 1.5.2,
E
1.5.13 and 1.7.1 to 1.7.4 (excepted 1.7.4 f) are fulfilled.
Designated standards: EN ISO 12100 :2010
EN 12693
:2008
Safety of machinery — General principles for design — Risk assessment and risk reduction Refrigerating systems and heat pumps — Safety and environmental requirements — Positive displacement refrigerant compressors
Remarks:
We also declare that the special technical documentation for this partly completed machine has been created in accordance with Annex II, 1. B and we obligate to provide these upon reasoned request from the individual national authorities by data transfer.
Commissioning is prohibited until it has been confirmed that the machinery into which the partly completed machine above is to be incorporated complies with the UK Statutory Instrument Supply machinery (Safety) regulations 2008 and an EC Declaration of Conformity, Annex II, 1. A exists.
Authorized person for compiling and handing over technical documentation:
Bock GmbH Alexander Layh Benzstraße 7 72636 Frickenhausen, Germany
Frickenhausen, 14th of October 2022
i. A. Alexander Layh, Global Head of R&D
© Danfoss | Climate Solutions | 2023.07
AQ453056555765en-000201 | 27
28 | AQ453056555765en-000201
© Danfoss | Climate Solutions | 2023.07





