BOCK UL-HGX12e CO2 LT Reciprocating Compressor
Product Information
The product is a reciprocating compressor designed for CO2
applications. It is available in different models: UL-HGX12e/20 ML
0,7 CO2 LT, UL-HGX12e/30 ML 1 CO2 LT, UL-HGX12e/40 ML 2 CO2 LT,
UL-HGX12e/20 S 1 CO2 LT, UL-HGX12e/30 S 2 CO2 LT, and UL-HGX12e/40
S 3 CO2 LT. Please note that this information is based on the
current level of knowledge and may change due to further
development.
Product Usage Instructions
Safety
- Identification of safety instructions:
- Danger: Indicates a dangerous situation which,
if not avoided, will cause immediate fatal or serious injury. - Warning: Indicates a dangerous situation
which, if not avoided, may cause fatal or serious injury. - Caution: Indicates a dangerous situation
which, if not avoided, may immediately cause fairly severe or minor
injury. - Note: Indicates a situation which, if not
avoided, may cause property damage.
- Danger: Indicates a dangerous situation which,
Electrical Connection
Refer to the user manual for detailed information on electrical
connection, including information for contactor and motor contactor
selection, connection of the driving motor, circuit diagram for
direct start, electronic trigger unit INT69 G, connection of the
electronic trigger unit INT69 G, functional test of the electronic
trigger unit INT69 G, oil sump heater, selection and operation of
frequency converters.
Technical Data
Refer to the user manual for technical data of the product.
Dimensions and Connections
Refer to the user manual for dimensions and connections of the
product.
Declaration of Incorporation
Refer to the user manual for the declaration of
incorporation.
UL-Certificate of Compliance
Refer to the user manual for the UL-Certificate of
Compliance.
Reciprocating Compressor
BOCK® UL-HGX12e CO2 LT
Operating guide
UL-HGX12e/20 ML 0,7 CO2 LT UL-HGX12e/30 ML 1 CO2 LT UL-HGX12e/40 ML 2 CO2 LT
UL-HGX12e/20 S 1 CO2 LT UL-HGX12e/30 S 2 CO2 LT UL-HGX12e/40 S 3 CO2 LT
Translation of the original instructions
AQ450435606290en-US0201
Foreword
Risk of accidents. Refrigerating compressors are pressurized machines and, as such, call for heightened caution and care in handling. Improper assembly and use of the compressor can result in serious or fatal injury! · To avoid serious injury or death, observe all safety instructions contained in these
instructions before assembly and before using the compressor! This will avoid misunderstandings and prevent serious or fatal injury and damage! · Never use the product improperly but only as recommended by this manual! · Observe all product safety labels! · Refer to local building codes for installation requirements!
CO2 applications require a completely new kind of system and control. They are not a general solution for the substitution of F-gases. Therefore, we expressly point out that all information
in these assembly instructions has been provided according to our current level of knowledge
and may change due to further development.
Legal claims based on the correctness of the information cannot be made at any time and are
hereby expressly excluded.
D
Unauthorized changes and modifications to the product not covered by this manual are prohibited and
US
will void the warranty!
This instruction manual is a mandatory part of the product. It must be available to the personnel who
operate and maintain this product. It must be passed onto the end customer along with the unit in which the compressor is installed.
This document is subject to the copyright of Bock GmbH, Germany. The information provided in this
manual is subject to change and improvements without notice.
Contents
Page
1 Safety……………………………………………………………………………………………………………..4 1.1 Identification of safety instructions…………………………………………………………………………… 4 1.2 Qualifications required of personnel………………………………………………………………………….. 4 1.3 Safety instructions…………………………………………………………………………………………………..5 1.4 Intended use………………………………………………………………………………………………………….. 5
2 Product description…………………………………………………………………………………………. 6 2.1 Short description……………………………………………………………………………………………………. 6 2.2 Name plate……………………………………………………………………………………………………………. 7 2.3 Type key…………………………………………………………………………………………………………………7
2 | AQ450435606290en-US0201
© Danfoss | Climate Solutions | 2023.06
Contents
Page
3 Areas of application………………………………………………………………………………………….8 3.1 Refrigerants…………………………………………………………………………………………………………… 8 3.2 Oil charge……………………………………………………………………………………………………………… 8 3.3 Limits of application……………………………………………………………………………………………….. 9
4 Compressor assembly……………………………………………………………………………………… 10 4.1 Storage and transportation……………………………………………………………………………………….10 4.2 Setting up……………………………………………………………………………………………………………… 10 4.3 Pipe connections……………………………………………………………………………………………………. 11 4.4 Pipes……………………………………………………………………………………………………………………..11 4.5 Flange shut-off valves (HP/LP)…………………………………………………………………………………. 11 4.6 Laying suction and pressure lines…………………………………………………………………………….. 12 4.7 Operating the shut-off valves…………………………………………………………………………………… 12 4.8 Operating mode of the lockable service connections…………………………………………………… 13 4.9 Oil return………………………………………………………………………………………………………………..14 4.10 Suction pipe filter…………………………………………………………………………………………………….14
5 Electrical connection………………………………………………………………………………………..15
5.1 Information for contactor and motor contactor selection……………………………………………….15
5.2 Connection of the driving motor…………………………………………………………………………………16
5.3 Circuit diagram for direct start 280 V / 460 V Y……………………………………………………….. 18
5.4 Electronic trigger unit INT69 G…………………………………………………………………………………. 20
5.5 Connection of the electronic trigger unit INT69 G…………………………………………………………20
D
5.6 Functional test of the electronic trigger unit INT69 G…………………………………………………… 21 US
5.7 Oil sump heater……………………………………………………………………………………………………….21
5.8 Selection and operation of frequency converters………………………………………………………… 21
6 Commissioning……………………………………………………………………………………………….. 22 6.1 Preparations for start-up…………………………………………………………………………………………. 22 6.2 Pressure strength test…………………………………………………………………………………………….. 22 6.3 Leak test………………………………………………………………………………………………………………. 22 6.4 Evacuation…………………………………………………………………………………………………………….. 23 6.5 Refrigerant charge………………………………………………………………………………………………….. 23 6.6 Start-up………………………………………………………………………………………………………………… 24 6.7 Pressure switch……………………………………………………………………………………………………… 24 6.8 Pressure relief valves……………………………………………………………………………………………….25 6.9 Avoiding slugging…………………………………………………………………………………………………….26 6.10 Filter dryer…………………………………………………………………………………………………………….. 26
7 Maintenance…………………………………………………………………………………………………… 26 7.1 Preparation……………………………………………………………………………………………………………. 26 7.2 Work to be carried out…………………………………………………………………………………………….. 27 7.3 Spare parts recommendation / accessories……………………………………………………………….. 27 7.4 Lubricants………………………………………………………………………………………………………………27 7.5 Decommissioning…………………………………………………………………………………………………… 27
8 Technical data………………………………………………………………………………………………… 28
9 Dimensions and connections……………………………………………………………………………. 30
10 Declaration of incorporation…………………………………………………………………………….. 32 11 UL-Certificate of Compliance……………………………………………………………………………. 34
© Danfoss | Climate Solutions | 2023.06
AQ450435606290en-US0201| 3
1 | Safety
1.1 Identification of safety instructions:
Indicates a dangerous situation which, if not avoided, will cause immediate fatal or serious injury Indicates a dangerous situation which, if not avoided, may cause fatal or serious injury Indicates a dangerous situation which, if not avoided, may immediately cause fairly severe or minor injury. Indicates a situation which, if not avoided, may cause property damage
Important information or tips on simplifying work
1.2 General safety instructions
D
Risk of accident.
Refrigerating compressors are pressurized machines and therefore
US
require particular caution and care in handling.
The maximum permissible overpressure must not be exceeded, even for testing purposes.
Danger of suffocation! CO2 is a nonflammable, acidic, colorless and odorless gas and heavier than air. Never release significant volumes of CO2 or the entire contents of the system into closed rooms!
Safety installations are designed or adjusted in accordance with EN
378-2 or appropriate national safety standards.
Risk of burns! · Depending on the operating conditions, surface temperatures of over
140°F (60°C) on the pressure side or below 32°F (0°C) on the suction side can be reached. · Avoid contact with refrigerant under any circumstances. Contact with refrigerant can lead to severe burns and skin irritations.
4 | AQ450435606290en-US0201
© Danfoss | Climate Solutions | 2023.06
1 | Safety
1.3 Intended use
The compressor may not be used in potentially explosive environments!
· These assembly instructions describe the standard version of the compressors named in the title manufactured by Bock. Bock refrigerating compressors are intended for installation in a machine (within the EU according to the EU Directives 2006/42/EC Machinery Directive and 2014/68/EU Pressure Equipment Directive, outside the EU according to the respective national regulations and guidelines).
Commissioning is only permissible if the compressors have been installed in accordance with these assembly instructions and the entire system into which they are integrated has been inspected and approved in accordance with legal regulations.
The compressors are intended for ance with the limits of application.
use
with
CO2
in
transcritical
and/or
subcritical
systems
in
compli-
Only the refrigerant specified in these instructions may be used!
Any other use of the compressor is prohibited!
1.4 Qualifications required of personel D
Inadequately qualified personnel poses the risk of accidents, the
US
consequence being serious or fatal injury. Work on compressors must
therefore only be performed by personnel with the qualifications listed
below:
· e.g., a refrigeration technician or refrigeration mechatronics engineer.
· As well as professions with comparable training, which enable personnel
to assemble, install, maintain and repair refrigeration and air-conditioning
systems.
· Personnel must be capable of assessing the work to be carried out and
recognizing any potential dangers.
© Danfoss | Climate Solutions | 2023.06
AQ450435606290en-US0201| 5
2 | Product description
2.1 Short description
· Semi-hermetic two-cylinder reciprocating compressor with suction gas cooled driving motor. · The flow of refrigerant sucked in from the evaporator is led over the engine and provides for a
particularly intensive cooling. Thus the engine can be kept on a relatively low temperature level specially during high load. · Oil pump independent of direction of rotation for reliable and safe oil supply. · One decompression valve each on the low and high pressure side, which vent into the atmosphere when inadmissibly high pressure levels are reached.
Transport eyelet
D Oil pump
US Terminal box
Fig. 1
Valve plate Name plate Oil sight glass
Cylinder cover Discharge
shut-off valve
Suction shut-off valve
Fig. 2 Dimension and connection values can be found in chapter 9
6 | AQ450435606290en-US0201
© Danfoss | Climate Solutions | 2023.06
2 | Product description
2.2 Name plate (example)
BOCK Bock GmbH, Benzstr. 7 72636 Frickenhausen, Germany
thermally protected system
1 Type : UL-HGX12e/40 S 3 CO2 LT 2 No : BC12345A001
6
267,03123 cfh
7 8
3
10,7/6,2A
9
4 5
111A 64A
372,28148 cfh
10 11
LP/HP = 1450/1451000p/1s0ig0 bar IP66
Oil:ÖBl:OBCOCKCSKlE8luu5bb5E5EE8855
12
Fig. 3
13
1 Type designation 2 Machine number
6 Voltage, circuit, frequency 7 Nominal rotation speed
} 50 Hz
3 maximum operating current 4 Starting current (rotor blocked) 5 LP: max. admissible operating
8 Displacement 9 Voltage, circuit, frequency 10 Nominal rotation speed
} 60 Hz
pressure (g) Low pressure side 11 Displacement
HP: max. admissible operating
12 Oil type filled at the factory
pressure (g) High pressure side 13 Terminal box protection type
D
Observe the limits of application
Electrical accessories can change
US
diagrams!
the IP protection class!
2.3 Type key (example)
UL -HG X 1 2 e / 40 S 3 CO2 LT
¹) HG ²) X ³) ML –
S –
Low Temperature
CO2 version HP code for motor size
Compressor version 3)
Swept volume
e-series
Number of cylinders
Size
Oil charge ²)
Series ¹)
Hermetic Gas-Cooled (suction gas-cooled)
Identification UL compressor
Ester oil charge
Deep freezing at low and medium evaporation temperatures
For frequency regulation and extended limits of application
© Danfoss | Climate Solutions | 2023.06
AQ450435606290en-US0201| 7
3 | Areas of application
3.1 Refrigerants · R744: CO2 (required CO2 quality 4.5 (< 5 ppm H2O))
3.2 Oil charge
The compressors are filled at the factory with the following oil type: Compressor version ML and S: BOCKlub E85
Property damage possible.
The oil level must be in the visible part of the sight glass; damage to the compressor is possible if overfilled or underfilled!
max.
Oil level min.
D US
~~ 21 fl.oz 0,6 Ltr. Fig. 4
8 | AQ450435606290en-US0201
© Danfoss | Climate Solutions | 2023.06
3 | Areas of application
3.3 Limits of application
Compressor operation is possible within the operating limits. These can be found in Bock compressor selection tool (VAP) under vap.bock.de. Observe the information given there. – Permissible ambient temperature -4°F … 140°F (-20 °C) – (+60 °C). – Max. permissible discharge end temperature 320°F (160 °C). – Min. discharge end temperature 122°F (50 °C). – Min. oil temperature 86°F (30 °C). – Max. permissible switching frequency 12x /h. – A minimum running time of 3 min. steady-state condition
(continuous operation) must be achieved. Avoid continuous operation in limit range.
Max. permissible operating pressure (LP/HP)1): 1450/1450 psig, 100/100 bar
1) LP = Low pressure HP = High pressure D
US
© Danfoss | Climate Solutions | 2023.06
AQ450435606290en-US0201| 9
4 | Compressor assembly
New compressors are factory-filled with inert gas. Leave this service charge in the compressor for as long as possible and prevent the ingress of air. Check the compressor for transport damage before starting any work.
4.1 Storage and transportation
?
Storage at -22°F … 158°F (-30 °C) – (+70 °C), maximum permissible relative humidity 10 % – 95 %, no condensation. Do not store in a corrosive, dusty, vaporous atmosphere or in a combustible environment.
Use transport eyelet. Do not lift manually! Use lifting gear!
4.2 Setting up D US
Attachments (e.g. pipe holders, additional units, fastening parts, etc.) directly to the compressor are not permissible!
Provide adequate clearance for maintenance work. Ensure adequate compressor ventilation.
Do not use in a corrosive, dusty, damp atmosphere or a combustible environment.
Setup on an even surface or frame with sufficient load-bearing capacity. Single compressor preferably on vibration damper. Compound connection basically rigid.
10 | AQ450435606290en-US0201
© Danfoss | Climate Solutions | 2023.06
4 | Compressor assembly
4.3 Pipe connections
Damage possible.
Superheating can damage the valve. Remove the pipe supports therefore from the valve for soldering and accordingly cool the valve body during and after soldering. Only solder using inert gas to inhibit oxidation products (scale).
Fig. 5: graduated internal diameter
Material soldering / welding connection: S235JR
The pipe connections have graduated inside diameters so that pipes with standard dimensions can be used. The connection diameters of the shut-off valves are rated for maximum compressor output. The actual required pipe cross section must be
matched to the output. The same applies for non-return valves.
4.4 Pipes
Pipes and system components must be clean and dry inside and free of scale, swarf and layers of
rust and phosphate. Only use hermetically sealed parts.
Lay pipes correctly. Suitable vibration compensators must be provided to prevent pipes being
D
cracked and broken by severe vibrations.
US
Ensure a proper oil return.
Keep pressure losses to an absolute minimum.
4.5 Flange shut-off valves (HP/LP)
Risk of injury.
The compressor must be depressurized through connections A1 and B1 before commencing any work and prior to connecting to the refrigerant system.
A1
B1
Fig. 6
© Danfoss | Climate Solutions | 2023.06
Fig. 7
AQ450435606290en-US0201| 11
4 | Compressor assembly
4.6 Laying suction and pressure lines
Property damage possible. Improperly installed pipes can cause cracks and tears, which can result in a loss of refrigerant.
Proper layout of the suction and pressure lines directly after the compressor is integral to the smooth running and vibration behavior of the system. A rule of thumb: Always lay the first pipe section starting from the shut-off valve downwards and parallel to the drive shaft.
D US
As short as possible
Rigid fixed point
Fig. 8
4.7 Operating the shut-off valves (example)
Before opening or closing the shut-off valve, release the valve spindle seal by approx. 1/4 of a turn counter-clockwise. After activating the shut-off valve, re-tighten the adjustable valve spindle seal clockwise.
Release
Tighten
Valve spindle seal Fig. 9
Fig. 10
12 | AQ450435606290en-US0201
© Danfoss | Climate Solutions | 2023.06
4 | Compressor assembly
4.8 Operating mode of the lockable service connections (example)
Service connection closed
Spindle
Connection blocked
Opening the shut-off valve: Spindle: turn to the left (counter-clockwise) as far as it will go. –> Shut-off valve completely opened / service connection closed.
Service connection opened
Pipe connection
Fig. 11
Compressor
Spindle
Connection open
Opening the service connection Spindle: Turn 1/2 – 1 turn to the right clockwise. –> Service connection opened / shut-off valve opened.
D
Pipe connection
US
Fig. 12
Compressor
After activating the spindle, generally fit the spindle protection cap again and tighten with 40 – 50 Nm. This serves as a second sealing feature during operation.
© Danfoss | Climate Solutions | 2023.06
AQ450435606290en-US0201| 13
4 | Compressor assembly
4.9 Oil return To ensure the oil return function will work reliably no matter what kind of system configuration you are using, Bock recommends incorporating oil separators or oil level monitoring equipment. The “O” connection is already available from the factory for the purpose of installing the additional oil level monitoring component. Oil should be returned from the oil separator to the compressor via the “D1″ connection provided for this purpose on the compressor.
4.10 Suction pipe filter For systems with long pipes and higher degree of contamination, a filter on the suction-side is recommended. The filter has to be be renewed depending on the degree of contamination (reduced pressure loss).
D US
14 | AQ450435606290en-US0201
© Danfoss | Climate Solutions | 2023.06
5 | Electrical connection
5 Electrical connection
Risk of electric shock! High voltage! Only carry out work when the electrical system is disconnected from the power supply!
When attaching accessories with an electrical cable, a minimum bending radius of 3x the cable diameter must be maintained for laying the cable.
Connect the compressor motor in accordance with the circuit diagram (see inside of terminal box).
Use suitable cable glands of the correct protection type (see name plate) for routing cables into the terminal box. Insert the strain reliefs and prevent chafe marks on the cables. Compare the voltage and frequency values with the data for the mains power supply.
Only connect the motor if these values are the same.
5.1 Information for contactor and motor contactor selection
D
All protection equipment, switching and monitoring devices must comply with the local safety reg- US ulations and established specifications (e.g. VDE) as well as the manufacturer’s specifications. Motor protection switches are required! Motor contactors, feed lines, fuses and motor protection switches must be rated according to the maximum operating current (see name plate). For motor protection, use a current-dependent, time-delayed overload protection device for monitoring all three phases. Adjust the overload protection device so that it must be actuated within 2 hours at 1.2 times the maximum working current.
© Danfoss | Climate Solutions | 2023.06
AQ450435606290en-US0201| 15
5| Electrical connection
5.2 Connection of the driving motor The compressor is designed with a motor for star-delta circuits.
Designation on the name plate
/ Y
D US
16 | AQ450435606290en-US0201
© Danfoss | Climate Solutions | 2023.06
5| Electrical connection
Star-delta start-up is only possible for (e.g. 280 V) power supply. Example:
Direct start
280 V
Star-delta start L1 L2 L3
460 V Y Direct start only
L1 L2 L3
L1 L2 L3 Insulator
L1 L2 L3
D
Insulators
US
INFO The supplied insulators must be mounted according to the illustrations as shown.
The connection examples shown refer to the standard version. In the case of special voltages, the instructions affixed to the terminal box apply.
© Danfoss | Climate Solutions | 2023.06
AQ450435606290en-US0201| 17
5.3 Circuit diagramm for direct start 280 V / 460 V Y
QA1
FC1.1
I> I> I>
1
3
5
QA2
2
4
6
FC2
SF1
QA2
FC1.1
L1 L2 L3 N PE
PE
D
US
1
2
3
4
5
6
7
M
8
-EC1 3/~Y
9
10
BT1
11
12
12 14 11 L N B1 B2
INT69G
CAonmspcrhelussßokratsetremninVael rbdoixchter
Fig. 13
BP1
High pressure safety monitor
BP2
Safety chain (high/low pressure monitoring)
BT1
Cold conductor (PTC sensor) motor winding
BT2
Thermal protection thermostat (PTC sensor)
BT3
Release switch (thermostat)
EB1
Oil sump heater
EC1
Compressor motor
18 | AQ450435606290en-US0201
© Danfoss | Climate Solutions | 2023.06
L1.1 L2.1 L3.1 L1.2
EB1 P>
BP1
BT2
BT2
QA2
P
BP2
BT3
N PE
D US
FC1.1 FC2 INT69 G QA1 QA2 SF1
Motor protection switch Control power circuit fuse Electronic trigger unit INT69 G Main switch Net switch Control voltage switch
© Danfoss | Climate Solutions | 2023.06
AQ450435606290en-US0201| 19
5| Electrical connection
5.4 Electronic trigger unit INT69 G
The compressor motor is fitted with cold conductor temperature sensors (PTC) connected to the electronic trigger unit INT69 G in the terminal box. In case of excess temperature in the motor winding, the INT69 G deactivates the motor contactor. Once cooled, it can be restarted only if the electronic lock of the output relay (terminals B1+B2) is released by interrupting the supply voltage. The hot gas side of the compressor can also be protected against overtemperature using thermal protection thermostats (accessory).
The unit trips when an overload or inadmissible operating conditions occur. Find and remedy the cause.
The relay switching output is executed as a floating changeover contact. This electrical circuit operates according to the quiescent current principle, i.e. the relay drops into a the idle position and deactivates the motor contactor even in case of a sensor break or open circuit.
5.5 Connection of the trigger unit INT69 G
D US 1
Connect the trigger unit INT69 G in accordance with the circuit dia-
2
3
4
5
gram. Protect the trigger unit with a delayed-action fuse (FC2) of
max. 4 A. In order to guarantee the protection function, install the trigger unit as the first element in the control power circuit.
or Protection MP10
Measure circuit BT1 and BT2 (PTC
R1
R2 sensor) must not
come into contact
with external
L
S
M
voltage.
1 N N 43 43 11 12 14 X2 1 2 3 4 5 6
This would destroy
+
Steuerstrom- BT1
–
kreis
+ the trigger unit BITN2T69 G and PTC
– sensors.
INT69 G
OG OG
LN
+
BT1
+
BT2
–
B1 B2
12 14 11
N L
CSotenutreorlstcriorcmu-it
kreis
Fig. 14 Terminal box
20 | AQ450435606290en-US0201
© Danfoss | Climate Solutions | 2023.06
5| Electrical connection
5.6 Function test of the trigger unit INT69 G
Before commissioning, after troubleshooting or making changes to the control power circuit, check the functionality of the trigger unit. Perform this check using a continuity tester or gauge.
Gauge state
Relay position
Relay position INT69 G
1. Deactivated state
11-12
2. INT69 G switch-on 3. Remove PTC connector 4. Insert PTC connector
11-14 11-12 11-12
B2 12 14 11 Fig. 15
5. Reset after mains on
11-14
5.7 Oil sump heater In order to avoid damage to the compressor, the compressor has to be equipped with an oil sump heater.
The oil sump heater must generally be connected and operated!
Operation: The oil sump heater operates when the compressor is at a standstill.
D
When the compressor starts up, the oil sump heating switches off.
US
Connection: The oil sump heater must be connected via an auxiliary contact (or parallel wired auxiliary contact) of the compressor contactor to a separate electric circuit.
Electrical data: 115 V – 1 – 60 Hz, 80 W.
5.8 Selection and operation of compressors with frequency converters For safe operation of the compressor, the frequency converter must be able to apply an overload of at least 160% of the compressor’s maximum current (I-max.) for at least 3 seconds.
When using frequency converters, the following things must also be observed: 1. The maximum permissible operating current of the compressor (I-max) (see type plate or
technical data) must not be exceeded. 2. If abnormal vibrations occur in the system, the affected frequency ranges in the frequency
converter must be blanked out accordingly. 3. The maximum output current of the frequency converter must be greater than the maximum
current of the compressor (I-max). 4. Carry out all designs and installations in accordance with the local safety regulations and
common rules (e.g. VDE) and regulations as well as in accordance with the specifications of the frequency converter manufacturer The permissible frequency range can be found in the technical data.
Rotational speed range
0 – f-min
Start-up time
< 1 s
Switch-off time
immediately
f-min/f-max see chapter: Technical data: permissible frequency range
f-min – f-max ca. 4 s
© Danfoss | Climate Solutions | 2023.06
AQ450435606290en-US0201| 21
6 | Commissioning
6.1 Preparations for start-up
In order to protect the compressor against inadmissible operating conditions, high-pressure and low-pressure pressostats controls are mandatory on the installation side.
The compressor has undergone trials in the factory and all functions have been tested. There are therefore no special running-in instructions. Check the compressor for transport damage!
When the compressor is not running, depending on ambient temperature and amount of refrigerant charge, it is possible that the pressure may rise and exceed permitted levels for the compressor. Adequate precautions must be taken to prevent this happening (e.g. using a cold storage medium, a receiver tank, a secondary refrigerant system, or pressure relief devices).
6.2 Pressure strength test
D
The compressor has been tested in the factory for pressure integrity. If however the entire system is
US
to be subjected to a pressure integrity test, this should be carried out in accordance with UL-/CSA-
Standards or a corresponding safety standard without the inclusion of the compressor.
6.3 Leak test
Risk of bursting! The compressor must only be pressurized using nitrogen (N2). Never pressurize with oxygen or other gases! The maximum permissible overpressure of the compressor must not be exceeded at any time during the testing process (see name plate data)! Do not mix any refrigerant with the nitrogen as this could cause the ignition limit to shift into the critical range.
Carry out the leak test on the refrigerating plant in accordance with UL-/CSA-Standards or a corresponding safety standard, while always observing the maximum permissible overpressure for the compressor.
Only dry test gases may be used for the leak test, e.g. nitrogen N2 min. 4.6 (= purity 99.996 % or higher).
22 | AQ450435606290en-US0201
© Danfoss | Climate Solutions | 2023.06
6 | Commissioning
6.4 Evacuation
Do not start the compressor if it is under vacuum. Do not apply
any voltage – even for test purposes (must only be operated with
refrigerant).
Under vacuum, the spark-over and creepage current distances of the terminal board connection bolts shorten; this can result in winding and terminal board damage.
First evacuate the system and then include the compressor in the evacuation process. Relieve the compressor pressure. Open the suction and pressure line shut-off valves. Turn on the oil sump heater. Evacuate the suction and discharge pressure sides using the vacuum pump. The vacuum has to be broken with nitrogen several times between the evacuation.
At the end of the evacuation process, the vacuum should be < 0.02 psig (1.5 mbar) when the pump is switched off. Repeat this process as often as is required.
6.5 Refrigerant charge
D
Wear personal protective clothing such as goggles and protective
US
gloves!
Make sure that the suction and pressure line shut-off valves are open.
Depending upon design of the CO2 refrigerant filling bottle (with/without tubing) CO2 can be filled in liquid after weight or gaseously.
Use only high-dried CO2 quality (see chapter 3.1)! Filling the liquid refrigerant: It is recommended that the system first be filled at standstill with gas on the high-pressure side up to a system pressure of at least 75 psig (5.2 bar) (if it is filled below 75 psig (5.2 bar) with liquid, there is a risk of dry ice formation). Further filling according to system. To eliminate the possibility of dry ice formation when the system is operating (during and after the filling process), the shut-off point of the low-pressure switch should be set to a value of at least 75 psig (5.2 bar).
Never exceed the max. permissible pressures while charging. Precautions must be taken in time.
A refrigerant supplement, which may become necessary after start-up, can be topped up in vapor form on the suction side.
Avoid overfilling the machine with refrigerant! Do not charge liquid refrigerant into the suction-side on the compressor. Do not mix additives with the oil and refrigerant.
© Danfoss | Climate Solutions | 2023.06
AQ450435606290en-US0201| 23
6 | Commissioning
6.6 Start-up
Ensure that both shut-off valves are open before starting the compressor!
Check that the safety and protection devices (pressure switch, motor protection, electrical contact protection measures, etc.) are functioning properly. Switch on the compressor and let it run for at least 10 minutes. The machine should reach a state of equilibrium. Check the oil level: The oil level must be visible in the sight glass. After a compressor is replaced, the oil level must be checked again. If the level is too high, oil must be drained off (danger of oil liquid shocks; reduced capacity of the refrigerating system).
If larger quantities of oil have to be topped up, there is a risk of oil impact effects. If this is the case, check the oil return!
6.7 Pressure switch
D
Suitably adjusted pressure switches according to UL 207 / EN 378 or national standards that switch
US
off the compressor before reaching the maximum permissible operating pressure must be installed in the system. The pressure reduction for the pressure switches can occur either at the suction and
pressure lines between the shut-off valve and compressor or at the non-lockable connections for the
shut-off valves (connections A and B, see Chapter 9).
24 | AQ450435606290en-US0201
© Danfoss | Climate Solutions | 2023.06
6 | Commissioning
6.8 Pressure relief valves The compressor is fitted with two pressure relief valves. One valve each on the suction and discharge side. If excessive pressures are reached, the valves open and prevent further pressure increase. Thereby CO2 is blown off to the ambient! In the event that a pressure relief valve activates repeatedly, check valve and replace if necessary as during blow-off extreme conditions can occure, which may result in a permanent leak. Always check system for refrigerant loss after activation of pressure relief valve! The pressure relief valves do not replace any pressure switches and the additional safety valves in the system. Pressure switches must always be installed in the system and designed or adjusted in accordance with EN 378-2 or appropriate safety standards. Failure to observe can result in risk of injury from CO2 streaming out of the two pressure relief valves!
D US
CO2 streaming out
Fig. 16
© Danfoss | Climate Solutions | 2023.06
AQ450435606290en-US0201| 25
6 | Commissioning
6.9 Avoiding slugging
Slugging can result in damage to the compressor and cause refrigerant to leak.
To prevent slugging:
The complete refrigeration plant must be properly designed. All components must be compatibly rated with each other with regard to output (particularly the evaporator and expansion valves). Suction gas superheating at the compressor input should be > 15 K (check the setting of the expansion valve). Regard oil temperature and pressure gas temperature. (The pressure gas temperature has to be high enough min. 122°F (50 °C), so the oil temperature is > 86°F (30 °C) ). The system must reach a state of equilibrium. Particularly in critical systems (e.g. several evaporator points), measures such as the use of liquid traps, solenoid valve in the liquid line, etc. are recommended.
There should be no movement of refrigerant in the compressor while the system is at a
standstill.
D
6.10 Filter dryer
US
Gaseous CO2 has a significantly lower solubility in water than other refrigerants. At low temperatures
it can therefore cause blocking of valves and filters due to ice or hydrate. For this reason we recom-
mend the use of an adequately sized filter drier and a sight glass with a moisture indicator.
7 | Maintenance
7.1 Preparation
Before starting any work on the compressor: Switch off the compressor and secure it to prevent a restart. Relieve compressor of system pressure. Prevent air from infiltrating the system!
After maintenance has been performed: Connect safety switch. Evacuate compressor. Release switch-on lock.
The decompression has to be carried out in a way that no dry ice respectively solid CO2 is produced which blocks the outlet and could hinder the streaming out of CO2. Otherwise, there is the danger that pressure can be built up again.
26 | AQ450435606290en-US0201
© Danfoss | Climate Solutions | 2023.06
7 | Maintenance
7.2 Work to be carried out
In order to guarantee optimum operational reliability and service life of the compressor, we recommend carrying out servicing and inspection work at regular intervals:
Oil change: – not mandatory for factory-produced series systems. – for field installations or when operating near the application limit: for the first time after 100
to 200 operating hours, then approx. every 3 years or 10,000 – 12,000 operating hours. Dispose of used oil according to the regulations; observe national regulations.
Annual checks: Oil level, leak tightness, running noises, pressures, temperatures, function of auxiliary devices such as oil sump heater, pressure switch.
7.3 Spare part recommendation Available spare parts and accessories can be found on our compressor selection tool under vap.bock.de as well as at bockshop.bock.de.
Only use genuine Bock spare parts!
7.4 Lubricants
For operation with CO2 the following oil types are necessary:
D
compressor version ML and S: BOCKlub E85
US
7.5 Decommissioning
Close the shut-off valves on the compressor. CO2 does not need to be recycled and can therefore be blown off into the environment. It is essential to ensure good ventilation or conduct the CO2 into the outdoors to avoid danger of suffocation. When releasing CO2, avoid a fast drop in pressure to prevent oil from exiting with it. If the compressor is unpressurized, remove the piping on the pressure- and suction-side (e.g. dismantling of the shut-off valve, etc.) and remove the compressor using an appropriate hoist. Dispose of the oil inside in accordance with the applicable national regulations.
When decommissioning the compressor (eg. for service or replacement of the compressor) larger amounts of CO2 in the oil can be set free. If the decompression of the compressor is not sufficient enough, closed shut-off valves may lead to intolerable excessive pressure. For this reason the suction side (LP) and the high pressure side (HP) of the compressor have to be secured by decompression valves.
© Danfoss | Climate Solutions | 2023.06
AQ450435606290en-US0201| 27
D
US
8 | Technical data
Oil charge
(sight glass center)
Oil charge
(ex works)
Suction line SV
Discharge line DV
Weight
permissible frequency range
Starting
current
(rotor locked)
Max. power consumption
Max. operating current
Voltage
Displacement
(1450 / 1740 rpm)
No. of cylinders
Type
28 | AQ450435606290en-US0201
Electrical data
3
Connections
UL-HGX12e/
30 – 70 265-290 V / 440-480 V Y – 3 – 60 Hz
© Danfoss | Climate Solutions | 2023.06
20 ML 0,7 CO2 LT 20 S 1 CO2 LT
50 / 60 Hz
1
cfh
V
61 / 73
2 / Y
A
2 kW (HP)
2 / Y
A
4,2 / 2,4 1.6 (2.2)
32 / 19
4,9 / 2,8 2.0 (2.7)
32 / 19
30 ML 1 CO2 LT 30 S 2 CO2 LT
2 100 / 120
9,0 / 5,2 2.6 (3.5)
111 / 64
9,9 / 5,7 3,1 (4.2)
111 / 64
40 ML 2 CO2 LT 40 S 3 CO2 LT
124 / 148
9,7 / 5,6 3,1 (4.2)
111 / 64
10,7 / 6,2 3.7 (5)
111 / 64
4
5
Hz
lb
mm (inch)
mm (inch)
Ltr. (fl.oz)
Ltr. (fl.oz)
190
190
209
12,8 (1/2) 209
16
1,3 1,1
(5/8) (46) (39)
209
209
AQ450435606290en-US0201| 29
© Danfoss | Climate Solutions | 2023.06
1 Tolerance (± 10 %) relative to the mean value of the voltage range. Other voltages and types of current on request.
2 – The specifications for max. power consumption apply for 60 Hz operation. – Take account of the max. operating current / max. power consumption for design of fuses, supply lines and safety devices. Fuse: Consumption category AC3
8 | Technical data
D US
3 All specifications are based on the average of the voltage range 4 Cutting ring connector for steel tubes 5 For solder connections
9 | Dimensions and connections
7
7
6
6
5
5
4
4
Anschlüsse /
An
+2 +20,08 +0,08Connections
Co
293 0 112,9534 0 11,54 0SV
Saugabsperrventil, Rohr (SLa/S Suction line valve, tubeSV (LS/Su
Centre of gravity 99 3,9 99 3,9 DV
Druckabsperrventil, Rohr Discharge line valve, tuDbeV
D(Lr/ D(iLs
338 0 13,31 0
7 6 5 4 A
Anschluss Saugseite, nicht aAbns Connection suction side,AnotCloo
+0,08
133 5,24
+0,08
13,31 0
7 7 6 6 X 5 X X2 5X2 4 4 A1
Anschluss Saugseite, abspeArrnb Connection suction sideA, 1lockCaob
5,24
A A +2 +0,08 B
Anschluss Druckseite, nicht aAbn Connection discharge siBde, nCoot
SI1 SI1+2 293+0,0081+12,54 0 +0,08 B1 X1 X1 A 293 A099113,,594 0293E 0 11,54E 0 D1
ACAnnossnccnShhellVcuutssiossACSnDÖaondrlurnsuisügccnccakhheksblacfeüüsrtihgspitoereseu,nersnarsBivg/bde1sevnp,otelmiACAolr,crnnobRÖ ConnectioSnuociltiroentulrinnefrovDma1lvoeiCl, stoue
133
99 3,9 99 3,9 E ACnosncnDhelVcutsiosDDnÖirosuldiclcrhpkuaracerbkgsmssepualernineroreEvmgeavenuategtlACivlre,neo
145 5,71 145154,5715,71
145 5,71
338 0 13,31133 05,24
+0,08
13,+301,080
+00,30388
+2 0
+2
OX,K O,K X2 O,K O,K F X A XX J/J1XJX* 2 J/J1* I
Ölablass Anschluss SaugseÖilta ACOnoilsndcnrAhaAe1licuntsiosCAnHnohesnocinßthegglcuaatsssiostetneSmmsapuFupIecegrtarsioaetACOnutiunoitrl
145 5,71
5198552962,3263,,,22312241855296 1326D5555,,,231D96901224012262F9+,,,F313203Q242Q11915,,D065094129+F3D200D,0Q1118191F,,F65Q94Q+00SS,0XAII8221 SXBIB2,,LSLXIS21XAIB21B,BI,I,LXB4X,4xLBBx,,LIJ15/OB1SJ5,1,I0I4KA1B,*05x,,9I5491x52144J902/Ox81S,J5519,IJ97KA1,*/O,501SJ8X3,515,IK2A1291*0492,859917,9,5883OE7,K,8 OE,K (UL-) T-Ve(UrsLio-)n mit AT-bVsepresrirovnenmtilteAnbusnpder(rUvLe-n)tHileGnXu1n2de(CUOL-2)HLGTX12e CO2 LT Maße und AnsMchalüßsesuenfdürAnschClüOss2e für
CO2
+2
338 0
13,31
133 5,24
+2
3+328 0
133 5,24
156 6,14 15826 36,,2124 293 11,54 99 3,9 99 3,19 242 9,53 (UL-) T-ve(rUsLio-n) withTs-hvuetr-soifofnvawlvitehssahnudt-o(Uff Lv-a)lHveGsXa1n2de (CUOL-2)HLGT X12e CO2 LT dimensions andimcoennnseiocntisonasndfocr onnecCtiOon2s for
CO2
/
/ *
Ölsumpfheizung Oil sump heater
no*unÖrlOyLlisilineuscfmuelumrpdufpehmdehfiaezinnaugtndegebrleinoviune(rlUryyLLiinfe-o)cfHrelu(rGUduXemLd1-f)a2HinnCGgdOXeb12leiv2iTe(CUr/yOLf-2o)HrT(GUXL1-)2HCGSSXJOQKLJOII1X121 12ACÖoSADSCSCACADDCD2iTnnicnncoeooreorollgsuuhhsssssncnncnnhCuccccaccruoonnnnn/tmakkDBhhhhJummmeeeeBEeFOJgeeId1llllg11pccccuuuuclppnpnealftttttssssa2hritritiirisoooohlloesesssasaaesSACACÖoCAACCACACÖOnnnnessnnssWiÖÖÖTizsasncnnnnnooooooollilttsotoofslauuuiillhthsssssosänsnnnnncnoostsiiieudbnlennllecacccccuhrrupnnnnnnnnnrsltmrmgmggrhhhhheuhmielmaseeeeeaeemueuvvsslllllvgmlcpsepcccccicuuuuucmgusapavvpnaehlsseftttttttsssssseeealflpshiiiiiillivpvcrhoooooorhosssss,nlnsesaapreerhennnnnneeSnhettrdtriÖDDÖÖuiiiHazuaLoHgllezgaeosdodothSSturrrNHlllXPtuutzauJeuPuOQsurdrKiuuiiiiseLeJonlslslIItünl1tl1iDDrugea21crhcaccverßscrctpeggcusmtnttakketruhhgiriogkoceoosssslrtemaavACÖoSADSCSCACADDCDarpfraukminoeeenüsteirrsfmsnnicnnrcoeooreoreollrnpiighhggsosn
98 7,8 198 7,8 X2 SCcohnrnaKedcetiroaSnnisgfochhrtlsugcslahssr,asDderXurc2vkaslevSCeictoe
+2 +0,08 (L/SWL)* =ACLnöostn-c/nSheclcuhtswiosenWisthsäaernmrmsec(aLshl/cl
82 3,22 822933,2211,54 5002903119,16,954 0 B1 B1 242 9,53 242 9,53 * Ölsumpfheizung nur Lieferumfang bei (UL-)HGX12 COAn2scThlu/ss Ölspiege D Oil sump heater only included in delivery for (UL-)HO GCXo1n2neCctioOn2oilTlevel
+2 +0S,0V8 +A21 SV A+01,08 DV DV Anschluss Öltemper
US
500 19,69 500 19,69 0 0 0 0 Maße und Anschlüsse für (UL-)CO2 T-Version mit Absperrventilen und (UL-)HGX12*eÖlCsuOm2pfhLeTizu/ng nur Lieferumf*aÖnglsbuemip(UfhLe-i)zHuGngXn1u2rCLOie2feTru/mfang bei (ULQ-)HCoGnnXe1cti2onCoiOl te2mpT 99 3,9 dimensions and connections for (UL-)CO2 T-version with shut-off valves and (UL-)HGOXil 1su2mepCheOa2terLoTnly included inOdilesliuvmerpy hfoera(tUerLo-)nHlyGiXnc1l2udCeOd2inTdeliverySIf1orDD(eruUccokLme-pn)rtHleassGstuionXng1vsav2elv
278 10,94
Druckentlastungsve
MdimaßeensuinodnsAannsdchcloünssneecDfMdütiiorimamn(ßUeseneLfsou-ni)rnoCsd(nUOisoAL2ann-nT)ssCdc-VOhacleo2ünrnssTdsnio-eevnccefütomriorsniin(toUnsAnLefbow-sc)riCptt(heUOiorsL2rnhv-T)uesC-tn-VOtwoiel2fefrisntTvihao-uvlnnvesedmrhs(iiuUtoaAntL-db-w)osH(ipftUGhfeLrXsv-rh)v1aHue2lGtnve-toeXiClfe1sfOn2v:2aeulnLvCedTOs(/2UanLLd-T)H(UGLX-)1H2Ge9XC91O22e3LC,T9O/2 LT SV A1 B1
B1 DV
99
3,9
B1
SI2 Decompression valv Schraderanschluss
X1 Connection for schr Schraderanschluss
X2 Connection for schr
(L/SW)* = Löt-/Schw
397 15,62397S1V5,6A21
SV A1
DV
DV
+ 2
513 0
205,123+00+,200820,2
+0,08 0
278 10,94 278 10,94 278 10,94
278 10,94
HalbhermHetaislbchermVeetrisdcichhetrerVHerGdic/ hSteemr Hi-hGe/rmSetmici-choemrmperetiscscoor mHpGressor HG
397 15,62TrantsraknristicsrcithiceaAl uvesrfüsihornungTr/antsraknristicsrcithiceaAl uvesrfüsihornung /
Subkritische Ausführung subcritical version
/Subkritische Ausführung subcritical version
/
397
+2 Typ /
type
+0,08 Typ /
type
Teile-Nr. part-no.
/
TtyyppeTp/ eairlte-n-Nor.. /
TtyyppeTp/eairlte-n-Nor.. /
Typ / type
Teile-Nr. / part-no.
TtyyppTpeea/ irlte-n-Nor.. /
Typ / type
Teile-Nr. / part-no.
Typ / type
Teile-Nr. part-no.
/
Teile-Nr. / part-no.
513 0 20,2 0 HGX12/20-4 ML(S)[SH] COH2 GTX1126/2402-84(1M6L4(2S9))[[S1H64] 3C0O] 2UTL-H1G64X2182(/12604M29L)[216C4O320]T UL-H1G64X4132/20 ML 2HCGOX21T2e/20-146M44L3(S) CO2 LHTG1X61423e7/2(106-443M8L) (SU)LC-HOG2XL1T2e1/26043M7L(106,473C8O) 2ULLT-HGX11624e5/220 ML 0,7 CO2 LT 16452
15,62 397 15,62 HGX12/30-4 ML(S)[SH] COH2 GTX1126/3403-14(1M6L4(3S2))[[S1H64] 3C3O] 2UTL-H1G64X3112(/12604S3(2S)[H1)6343C3O] 2UTL-H1G64X4142(/12604S45(S) HH) G3 XC1O22e/T30-146M44L4((S1)6C44O52) LHTG1X61423e9/3(106-444M0L) (SU)LC-HOG2XL1T2e1/26043S91(1C64O420)LTUL-HGX11624e5/320 S 1 CO2 LT HGX12/40-4 ML(S)[SH] COH2 GTX1126/4403-44(1M6L4(3S5))[[S1H64] 3C6O] 2UTL-H1G64X3142(/13604M35L)[316C4O326]T UL-H1G64X4162/30 ML 3HCGOX21T2e/40-146M44L6(S) CO2 LHTG1X61424e1/4(106-444M1L) (SU)LC-HOG2XL1T2e1/36044M1L(1164C4O12) LUTL-HGX11624e5/430 ML 1 CO2 LT
16453 16454
+ 2
513 0
+0,08 +2
20,2 0 513 0
UL-HGX12/30 S(SH) 4 CO2UTL-H1G64X4172(/13604S48(S) H) 4 CO2 T 16447(16448)
UL-HGX12e/30 S 2 CO2 LTUL-HGX11624e5/530 S 2 CO2 LT
16455
UL-HGX12/40 ML 4 CO2 T UL-H1G64X4192/40 ML 4 CO2 T 16449
20,2 +H00,a0l8bhermetischer Verdichter HG / Semi-hermetic compressor HG UL-HGX12/40 S(SH) 5 CO2UTL-H1G64X5102(/14604S51(S)H) 5 CO2 T 16450(16451)
UL-HGX12e/40 ML 2 CO2 LUTL-HGX11624e5/640 ML 2 CO2 LT UL-HGX12e/40 S 3 CO2 LTUL-HGX11624e5/740 S 3 CO2 LT
16456 16457
Transkritische Ausführung /
Subkritische Ausführung /
transcritical version
subcritical version
siVcZheuerDi(snpKrtseaaotrncerLrekdloluiieensnnfwiaeog,narndagnsanedsfsütlcfisrermhefuieduestriszmeitcs, hWsewiaVcZrierhreuednersprtsaatncekdlluennag,ndgaefsüliser fedsrieitchWewarierredn Transport).
Typ /
Teile-Nr. /
Typ /
Teile-Nr. / Typ /
Teile-Nr. / Typ /
Teile-Nr. /
HalbhermetischHeraVlbehredrimchetetisr cHhGer/VSeermdiic-hteerrmHeGtic/cSoemmpir-ehsesrmoreHticGcompressor HG type HGX12/20-4 ML(S)[SH] CO2 T HGX12/30-4 ML(S)[SH] CO2 T
part-no. 16428(16429)[16430] 16431(16432)[16433]
type UL-HGX12/20 ML 2 CO2 T UL-HGX12/20 S(SH) 3 CO2 T
part-no. 16443 16444(16445)
type HGX12e/20-4 HGX12e/30-4
ML(S) ML(S)
CO2 CO2
LTGp1u6aß4rt3t-n7o(ol1e.6r4a38n)zetUyLnp-eH/GGX1e2Gnee/u2r0ßaMtloLcle0a,rs7atCinnOzg2eLtnTol/epGra1are6tn-4nn5coe2e.rsa:l
LT- 16439(16440) UL-HGX12-e/20 S 1 CO2 LT
16453
casting
toZlerica Dra
Typ / type HGX12/20-4 ML(S)[SH] CO2 T HGX12/30-4 ML(S)[SH] CO2 T
TranHskGrXit1is2c/4h0e-4AMusLf(üSh)[SruHn]gC/O2 T transcritical version
16434(16T4r3a5n)s[1k6r4it3is6c] hUeLA-HuGsfXü1h2r/u30ngM/L 3 CO2 T transcritiUcaLl-HvGerXs1io2/n30 S(SH) 4 CO2 T
16446 SubkHriGtiXs1c2hee/4A0u-4sfMüLh(rSu)nCgO/2 16447(16448) subcritical version
LTNB1ae6ui4n4m1/(u1N6s4ot4Se1ur)bgskUUeurLLipbt–HHicsrGGrücithXXfitce11a22NB/Aeel Tua//ev33seuy00ifnrüpsmSMhi/eoL2runuN1CesnOCotgxOe2a/2rLmgTLTeinparütifo11t66n44/:55T45 ype
examinatio
1 Teile-Nr. / Typ /
part-no. type
Typ / type
16428(1642H9G)[1X61423/200] -4UML-LH(GS)X[S1H2/]2C0OM2LT2
CTp1O6ea24irlt2eT-n8-N(o1r.6. 4/Tp126ea94ir)lt4[e-1n3-6NUUo4r.LL3.–0/HH]GGTtUXXyy11LppTtH22-eyH//yG44/pGp00eXX/MS112(LS2e4H//22)C005O-M4C2LMOT22L(CTSO) 112C66OT4445290L(1T6Tp146eaTp154ir6ea1lt4e4-ir)ln3-t3eN-on7-rN.(o.1r./6. 4/ 38)TtHyyGTtUpypyLeXpp-/1eH2/Ge/X2102-4e/M20L(MAGSL)lelC0gw,O7e2iCmcLOhTe2tinL/Tp1T6eatWo4irlt3elTp-UUeen7-eaNLL1(iorir1g–l6rat.HHe6-.4hn-nGG4/5Not3XXz2:r.8.11e()22/AGkneeTtUgl//ey44l/yLg)p00wp-GeeHSM-/imGceL3hXn2Ce1teOCi2n/rO2eatW/2Lo2lT0LlteeToMirglLaeh0nr,taz7:11ne66C(44cknO55eg672/s)LGT- eTpnea1eirl6ter-4an-5Nol2r.t.o/ lera
Be 16431(1643H2G)[1X61423/30] -4UML-LH(GS)X[S1H2/]2C0OS2(STH) 136C4O312(1T6413624)4[146(413634]45U) LH-HGGXX1122e//2300-S4(SMHL)(S3)CCOO22TLT161464443(91(61464454)0)HGULX-1H2Ge/X3102-4e/M20L(SDS)1ICNCOO2I2SLLOTT 1267463981(1-6m64454K30-)DEUINL-HIGSXO122e/72068S-1mCKO2-ELT
16453
0.5 6 30 0.1520 6400 30 HGX12/40-4 ML(S)[SH] CO2 T 16434(1643H5G)[1X61423/460] -4UML-LH(GS)X[S1H2/]3C0OM2LT3 C1O6243T4(16413654)4[166436] ULH-HGGXX1122e//3400-M4LM3L(CSO) 2COT2 LT1614644641(16441)HGULX-1H2Ge/X4102-4e/M30L(MüSL)bC1eOCr2O/L2aTLbT1o6v4e411(166445441)übULe-rHG/ Xa1b2oe/v30eML 1 CO2 LT
16454
UL-HGX12/30 S(SH) 4 CO2 T 16447(16448U) L-HGX12/30 S(SH) 4 CO2 T 16447(16448)
UL-HGX12/40 ML 4 CO2 T 16449
UL-HGX12/40 ML 4 CO2 T 16449
UL-HGX12/40 S(SH) 5 CO2 T 16450(16451U) L-HGX12/40 S(SH) 5 CO2 T 16450(16451)
UL-HGX12e/30 S 2 CbOis2 L/Tup to 16455 6ULb-HisG3X/ 10u2pGe/3ut0o1ßSt2o20leCrOa2n46LzT0e0n /31G01e60n45e051ra2l c0as
UL-HGX12e/40 ML 2 CO2 LT UL-HGX12e/40 S 3 CO2 LT
116644±55670.1UULL–±HHGG0XX.11222B-ee//44a±00u0SMm.L33u±2Cs0OCtO2e±.12Lr0gTL.Te5±p0rü.±f211t066/44.55T±867y0p.e3e
Unbemaßte RadienU/nUbenmdimaßeNGtneeesiwRnioiac/ndhNeitdeo/nrWa/deUiiing: dh- itm: (ekngs)io- nOIDneIbddN
Gußtoleranzen / GenerAallgceamstienignGttouolßeletroraalnenzrcaeensz:/eGne/nGe
–
DIN ISO -2768-mK-E
Baumustergeprüft / Tyüpbeere/xaabmBoivaneuamtiouns0:t.e5rgeprü6f
Nein / No
bis / uNp etoin / No 6 30
oranensnsspTipnuo(ahrcrceeotkaprstatrhruiogooepsinpnpi)oedgl.inreeflorivcrehposrarnayesdfveoitteofitonrpanteainsonrsntssp,uo(rcreotarttrhiooesni)od.neliveprryevoef nptaiornts,
30 | AQ450435606290en-US0201 whaasrme.avtitdtutieersliuhewAuesinnbsordnllitfutllu,ärgtleWVbhRoTdcppoPrthütliorioardafohzeutoegeceaoeibnstneycueegrtnckhetithiiweemtundrhetxluhltenieiiismtctblpecnrentnauenyr,Sreeohiratrggenrhntnte-eptcmeessgg,uasdegtnGsdhrmfsodgruGnbüomleotsaiadetw.eeenIogerudonfenndrusssgdetuvOaabhtesidtncdeleuilcDi(TTieoausriotaninnefhivasKzaoatlncdftttrhwleieenemthamhtbovnafaudoDeserrirnewtioonloitcnnseatripaecoaioFd.rrrLpre,horeaMsschsfgsibkotnVeZlazsnirilthukpiiteeunldepzincosralumfetsdeplwossomi.htfhwadioptawsrmeeoe.iprauraovtitedoftueeatiteesirnrsslliuhlfd)vvenwAuesaiitrnAinnnt.esbtegsoteeerhdnelntlhiitdlfsutlrnntslurnrl,iiärgrtleseetss–cPcfrthü,-..ttlirrizmuthoohgeceaeibsuegZ000tnakhnuitiieueneexlultsditaabiuistcstpcnznmnayrSioshtrst,atgenrho-ie|||cmeog,stdessdhmsg.UHBunGmlisiaedVceZenIosu/endenrLehussgedutvabheRitnseetleirlesaurianißrupiVszraalcdtt(teilestaahratcbvfaugDeseetrivftonoocltcnestietoiao.rrrkd.horatlsibktlrnhdZBzussntehioueznaeumfnidentosm.hadcoatweegi,uriaoeofnohledsimdstlfdvvngtnnAiettttegateeeheteehillfnnptsrnsr3liiirsüeevlss–,r-..isteeerp-fZ000Nrrredyeasaaburirveoitt.cseuf|||hWintprn.eUHBwtsaair/oieeerLerSrnteRdnstni,eßrVesirfgeiovfetar.rndBsAzitaceenhlmtistctceph3hren-lNuruasnrt.sguirnIasaueSufnegfsgreioeenrnnoAozmmenmiscmcehhennlnu.usnsg
I aufgenommen aufgenommen.
7 7 packaging for safe transportation).
Weitergabe sowie Vervielfältigung dieses Dokuments, Verwertung und Mitteilung seines Inhalts sind ver-
6
6
rstellen, dass DdbeieortWLeniea, freseorawnetitmnuicshst saiucshderürsctkelilclehng, edsataststetd. ZieuwWidaerre-
Gewicht / Weight: (kg) –
Gewic±h0t /.1We±ig0h.t2:
Dimensions in mm [inch] Allgemeintoleranzen DIN ISO 2768-mK-E
/
UGnebneemraalßADttoelIlNlgeRerIaamSdnOeiceienn2st7o/ 6lUe8nr-admnimKz
11731 11643 11460
06.10177.2321 13.10156.2423 17.10124.2620
V. P0o6liz.0z7i .22 C. EVg. ePloelrizzi E. Bau1k3n.e0c5h.2t2 CE. .EBgaeulekrnecht E. Bau1k7n.e0c2h.2t2 J. KEe.uBearluekbneercht
Fig. 17 übCe. rE/gaebleorve 0.5 6 üb3e0r / a1b2ov0e 400
bis / up to
6 30 12b0is / 4up00to 100
C. Egeler
±0.1 ±0.2 ±0.3 ±0.5 ±±00
J. Keuerleber
© Danfoss | Climate Solutions | 2023.06 Änd.-Nr. / Mod-No. ÄDnadtu.-mNr/. D/ Matoed-BNeoa.rbD.a/tuEmdit/eDdaGteepBreüaftrb/ .A/pEpdr.iteMdaßG/UeDpnirbmüefetmn/saAioßpnpter.RMaadßieP/nDas/imsUuennndgsiim/oCnelnesUaironanbnecPedmarasasßdutieni:gR-/BaCOdliCee
5
5
4
4
9 | Dimensions and connections
SV Suction line DV Discharge line
see technical data, chapter 8
A
Connection suction side, not lockable
A1 Connection suction side, lockable
B
Connection discharge side, not lockable
B1 Connection discharge side, lockable
D1 Connection oil return from oil separator
E
Connection oil pressure gauge
F
Oil drain
1/8″ NPTF 7/16″ UNF 1/8″ NPTF 7/16″ UNF 1/4″ NPTF 1/8″ NPTF M12x1.5
I
Connection hot gas temperature sensor
J
Connection Oil sump heater
K
Sight glass
1/8″ NPTF 3/8″ NPTF 2 x 1 1/8″ – 18 UNEF
L
Connection thermal protection thermostat
O
Connection oil level regulator
Q
Connection oil temperature sensor
1/8″ NPTF
2 x 1 1/8″ – 18 UNEF
D
US
1/8” NPTF
SI1 Decompression valve HP
M22x1.5
SI2 Decompression valve LP
M22x1.5
© Danfoss | Climate Solutions | 2023.06
AQ450435606290en-US0201| 31
10| Declaration of incorporation
Declaration of incorporation for incomplete machinery in accordance with EC Machinery Directive 2006/42/EC, Annex II 1. B
Manufacturer:
Bock GmbH Benzstraße 7 72636 Frickenhausen, Germany
We, as manufacturer, declare in sole responsibility that the incomplete machinery
Name: Types:
Semi-hermetic compressor HG(X)12P/60-4 S (HC) …………………… HG(X)88e/3235-4(S) (HC) UL-HGX12P/60 S 0,7……………………… UL-HGX66e/2070 S 60 HGX12P/60 S 0,7 LG …………………….. HGX88e/3235 (ML/S) 95 LG HG(X)22(P)(e)/125-4 A …………………… HG(X)34(P)(e)/380-4 (S) A HGX34(P)(e)/255-2 (A) ………………….. HGX34(P)(e)/380-2 (A)(K) HA(X)12P/60-4 ……………………………… HA(X)6/1410-4 HAX22e/125 LT 2 LG ……………………. HAX44e/665 LT 14 LG HGX12e/20-4 (ML/S) CO2 (LT) ……….. HGX44e/565-4 S CO2 UL-HGX12e/20 (S/ML) 0,7 CO2 (LT)… UL-HGX44e/565 S 31 CO2 HGX12/20-4 (ML/S/SH) CO2T………….. HGX46/440-4 (ML/S/SH) CO2 T UL-HGX12/20 ML(P) 2 CO2T…………. UL-HGX46/440 ML(P) 53 CO2T HGZ(X)7/1620-4 ……………………………. HGZ(X)7/2110-4 HGZ(X)66e/1340 LT 22…………………… HGZ(X)66e/2070 LT 35
HRX40-2 CO2 T H………………………….. HRX60-2 CO2 T H
Name:
Open type compressor
D
Types:
F(X)2 …………………………………… F(X)88/3235 (NH3) FK(X)1………………………………….. FK(X)3
US
FK(X)20/120 (K/N/TK)…………….. FK(X)50/980 (K/N/TK)
Serial number:
BC00000A001 BN99999Z999
complies with the following provisions of the above-mentioned Directive:
According to Annex I, points 1.1.2, 1.1.3, 1.1.5, 1.3.2, 1.3.3, 1.3.7, 1.5.1, 1.5.2, 1.5.13 and 1.7.1 to 1.7.4 (excepted 1.7.4 f) are fulfilled.
Applied harmonised standards, in particular: EN ISO 12100 :2010
EN 12693
:2008
Safety of machinery — General principles for design — Risk assessment and risk reduction Refrigerating systems and heat pumps — Safety and environmental requirements — Positive displacement refrigerant compressors
Remarks:
We also declare that the special technical documentation for this incomplete machine has been created in accordance with Annex VII, Part B and we obligate to provide these upon reasoned request from the individual national authorities by data transfer.
Commissioning is prohibited until it has been confirmed that the machinery into which the incomplete machine above is to be incorporated complies with the EC Machinery Directive and an EC Declaration of Conformity, Annex II. 1. A exists.
Authorized person for compiling and handing over technical documentation:
Bock GmbH Alexander Layh Benzstraße 7 72636 Frickenhausen, Germany
Frickenhausen, 04th of January 2021
i. A. Alexander Layh, Global Head of R&D
32 | AQ450435606290en-US0201
© Danfoss | Climate Solutions | 2023.06
10| Declaration of incorporation
Declaration of incorporation of partly completed machinery in accordance with UK Statutory Instrument Supply of Machinery (Safety) Regulations 2008, Annex II 1. B
Manufacturer:
Bock GmbH Benzstraße 7 72636 Frickenhausen, Germany
We, as manufacturer, declare in sole responsibility that the partly completed machinery
Name: Types:
Semi-hermetic compressor HG(X)12P/60-4 S (HC) …………………… HG(X)88e/3235-4(S) (HC) UL-HGX12P/60 S 0,7……………………… UL-HGX66e/2070 S 60 HGX12P/60 S 0,7 LG …………………….. HGX88e/3235 (ML/S) 95 LG HG(X)22(P)(e)/125-4 A …………………… HG(X)34(P)(e)/380-4 (S) A HGX34(P)(e)/255-2 (A) ………………….. HGX34(P)(e)/380-2 (A)(K) HA(X)22e/125-4 ……………………………..HA(X)6/1410-4 HAX22e/125 LT 2 LG ……………………. HAX44e/665 LT 14 LG HGX12e/20-4 (ML/S) CO2 (LT) ……….. HGX44e/565-4 S CO2 UL-HGX12e/20 (S/ML) 0,7 CO2 (LT)… UL-HGX44e/565 S 31 CO2 HGX12/20-4 (ML/S/SH) CO2T………….. HGX46/440-4 (ML/S/SH) CO2 T UL-HGX12/20 ML(P) 2 CO2T…………… UL-HGX46/440 ML(P) 53 CO2T HGZ(X)7/1620-4 ……………………………. HGZ(X)7/2110-4 HGZ(X)66e/1340 LT 22…………………… HGZ(X)66e/2070 LT 35
HRX40-2 CO2 T H………………………….. HR(Z)X60-2 CO2 T (H)(V)
Name:
Open type compressor
Types:
F(X)2 …………………………………………… F(X)88/3235 (NH3) FK(X)1………………………………………….. FK(X)3
D
FK(X)20/120 (K/N/TK)…………………….. FK(X)50/980 (K/N/TK)
US
Serial number:
BC00000A001 BN99999Z999
complies with the following provisions of the above-mentioned Statutory instrument:
According to Schedule 2, part1, points 1.1.2, 1.1.3, 1.1.5, 1.3.2, 1.3.3, 1.3.7, 1.5.1, 1.5.2, 1.5.13 and 1.7.1 to 1.7.4 (excepted 1.7.4 f) are fulfilled.
Designated standards: EN ISO 12100 :2010
EN 12693
:2008
Safety of machinery — General principles for design — Risk assessment and risk reduction Refrigerating systems and heat pumps — Safety and environmental requirements — Positive displacement refrigerant compressors
Remarks:
We also declare that the special technical documentation for this partly completed machine has been created in accordance with Annex II, 1. B and we obligate to provide these upon reasoned request from the individual national authorities by data transfer.
Commissioning is prohibited until it has been confirmed that the machinery into which the partly completed machine above is to be incorporated complies with the UK Statutory Instrument Supply machinery (Safety) regulations 2008 and an EC Declaration of Conformity, Annex II, 1. A exists.
Authorized person for compiling and handing over technical documentation:
Bock GmbH Alexander Layh Benzstraße 7 72636 Frickenhausen, Germany
Frickenhausen, 14th of October 2022
i. A. Alexander Layh, Global Head of R&D
© Danfoss | Climate Solutions | 2023.06
AQ450435606290en-US0201| 33
11 | UL-Certificate of Compliance
Dear customer, the Certificate of Compliance can be downloaded by the following QR-Code:
https://vap.bock.de/stationaryapplication/Data/ DocumentationFiles/COC CO2 trans.pdf
D US
34 | AQ450435606290en-US0201
© Danfoss | Climate Solutions | 2023.06
D US
© Danfoss | Climate Solutions | 2023.06
AQ450435606290en-US0201| 35
D US
36 | AQ450435606290en-US0201
© Danfoss | Climate Solutions | 2023.06