Sauermann Cp 110 Pressure Transmitter User Guide

Sauermann Cp 110 Pressure Transmitter User Guide

sauermann CP 110 Pressure Transmitter

CP 110
Quick Start Guide

Quick Start Guide

Differential pressure transmitter
sauermann CP 110 Pressure Transmitter - icon1 Ranges from -500/+500 Pa to -10 000/+10 000 Pa (according to model)
sauermann CP 110 Pressure Transmitter - icon2Configurable intermediary ranges

Features

  • 0-10 V or 4-20 mA output, active, power supply 24 Vac/Vdc (3-4 wires) or 4-20 mA output, passive loop, power supply from 16 to 30 Vdc (2 wires)
  • ABS V0 housing, IP65, with or without display
  • “¼ turn” system mounting with wall-mount plate
  • Housing with simplified mounting system
  • Solenoid valve for auto-calibration (only on CP 111 model)

General features

Output / SupplyActive sensor 0-10 V or 4-20 mA (alim. 24 Vac/Vdc ±10%), 3-4 wires Passive loop 4-20 mA (power supply 16/30 Vdc), 2 wires Common mode voltage <30 VAC Maximum load: 500 Ω (4-20 mA) / minimum load: 1 K Ω (0-10 V)
ConsumptionCP 111: 3 VA (0-10 V) or 3 VA (4-20 mA)
CP112, CP113, CP 114, CP 115: 2 VA (0-10 V) or 0.6 VA (4-20 mA)
European directives2014/30/EU EMC; 2014/35/EU Low Voltage; 2011/65/EU RoHS II; 2012/19/EU WEEE
Electrical connectionScrew terminal block for cables from 0.05 to 2.5 mm2
or from 30 to 14 AWG Carried out according to the code of good practice
PC CommunicationUSB-mini DIN cable
EnvironnementAir and neutral gases
Response time1/e (63%) 0.3 s
Zero settingManual autozero with push-button; self-calibration by a solenoid valve (CP 111 only)
Type of fluidAir and neutral gases
Conditions of use
(°C/%RH/m)
From 0 to +50 °C. In non-condensing condition. From 0 to 2000 m
Storage temperatureFrom -10 to +70 °C

*All the accuracies indicated in this technical datasheet were stated in laboratory conditions, and can be guaranteed for measurements carried out in the same conditions, or carried out with calibration compensation.

Technical specifications

CP 111CP 112CP 113CP 114CP 115
Measuring ranges-100/+100 Pa-1000/+1000 Pa-10 000 /+10 000 Pa-500/+500 mbar-2000/+2000 mbar
Measurement
units
Pa, mmH2 O,
inWG, mmHG,
daPa, kPa, hPa, mbar
Pa, mmH2 O,
inWG, mmHG,
daPa, kPa, hPa,
mbar
Pa, mmH2O,
inWG, mmHG,
daPa, kPa, hPa,
mbar
mbar, inWG,
mmHG, PSI,
mmH2 O, daPa,
hPa, kPa
mbar, inWG,
mmHG, PSI,
mmH2 O, daPa,
hPa, kPa
Accuracy*±1% of reading
±2 Pa
±1.5% of reading
±3 Pa
±1.5% of reading
±30 Pa
±1.5% of reading
±3 mbar
±1.5% of reading
±3 mbar
Resolution1 Pa;
0.1 mmH2 O;
0.01 mbar;
0.01 inWG;
0.01 mmHG;
0.1 daPa;
0.001 kPa;
0.01 hPa
1 Pa;
0.1 mmH2 O;
0.01 mbar;
0.01 inWG;
0.01 mmHG;
0.1 daPa;
0.001 kPa;
0.01 hPa
1 Pa;
0.1 mmH2O;
0.01 mbar;
0.01 inWG;
0.01 mmHG;
0.1 daPa;
0.01 kPa;
0.01 hPa
1 mbar;
0.1 inWG;
1 mmHG;
1 mmH2 O;
1 hPa;
10 daPa;
0.1 kPa;
0.1 PSI
1 bar;
0.1 inWG;
1 mmHG;
1 mmH2 O;
1 hPa;
10 daPa;
0.1 kPa;
0.1 PSI
Overpressure tolerated21 000 Pa21 000 Pa69 000 Pa1400 mbar4100 mbar

Features of the housing

MaterialABS V0 as per UL94
ProtectionIP65
DisplayLCD 10 digits.
Dimensions: 50 x 17 mm
Height of digits: values: 10 mm; units: 5 mm
ConnectionsRibbed, Ø 6.2 mm
Cable glandFor cables Ø 8 mm maximum
Weight143 g

sauermann CP 110 Pressure Transmitter - fig1

Symbols used
warning For your safety and in order to avoid any damage of the device, please follow the procedure described in this document and read carefully the notes preceded by the following symbol:

Note 12 The following symbol will also be used in this document, please read carefully the information notes indicated after this symbol:

Connections

sauermann CP 110 Pressure Transmitter - fig2

sauermann CP 110 Pressure Transmitter - fig3

1. Solenoid valve (CP 111 only)
2. Left DIP switch
3. Right DIP switch
4. Pressure connections
5. Safety pressure connections
6. Autozero
7. LCC-S software connection
8. Output terminal block
9. Power supply terminal block
10. Cable gland

Electrical connections as per NFC15-100 standard

warning This connection must be made by a qualified and trained technician. To make the connection, the transmitter must NOT BE ENERGIZED.

For CP 111/112/113/114/115 – AO models and
CP 111/112/113/114/115 – AN models with 0-10 V or
4-20 mA output – active, 4 wires:
warning To make a 3-wire connection, BEFORE POWERING UP THE TRANSMITTER, please connect the output ground to the input ground. See drawing below.
sauermann CP 110 Pressure Transmitter - fig4

For CP 111/112/113/114/115 – PO models and CP 111/112/113/114/115 – PN models with 4-20 mA output – passive

sauermann CP 110 Pressure Transmitter - fig5

Settings and use of the transmitter

Alimentation
16-30 Vdc + – Vdc IP + … 5 6 7 A autonome de + Auto-calibration CP 111 pressure transmitter has a temperature compensation of the gain from 0 to 50°C and an auto-calibration process that guarantees overtime excellent stability and perfect reliability of the measurement on low and high ranges. Auto-calibration principle: the microprocessor of the transmitter drives a solenoid valve that compensates for the possible drifts on the sensitive element over time. The compensation is

warning To configure the transmitter, it must not be energized. Then, you can make the settings required, with the DIP switches (as shown on the drawing below). When the transmitter is configured, you can power it up. performed by the permanent adjustment of the zero. So the measurement of the differential pressure is then independent of the environmental conditions of the transmitter. Advantage: no drift Frequency of auto-calibration: resettable or from 1 to 60 minutes.

Autozero
To perform an autozero, unplug the 2 pressure connections tubes and press the “Autozero” key.

sauermann CP 110 Pressure Transmitter - fig6

On the CP 111 transmitter, it is not necessary to unplug the 2 pressure connection tubes. When an autozero has been performed, the “On” green light turns off then turns on, and on transmitters equipped with a display, “autos” is displayed.

Configuration
To configure the transmitter, unscrew the4 screws from the housing then open it. DIP switches allowing the different settings are then accessible.

sauermann CP 110 Pressure Transmitter - fig7

Measuring range settings – left DIP switch
To set a measuring range, but the 1, 2, and 3 on-off switches as indicated in the table below

CP 111, CP 112, CP 113

sauermann CP 110 Pressure Transmitter - fig8
Combination 1Combination 2Combination 3Combination 4Combination 5
Type of transmitteCP111CP112CP113CP111CP112CP113CP111CP112CP113CP112CP111CP113CP111CP112CP113
Pa201001000302502500405005000507507500100100010000
mmH2210100325250450500575750101001000
mbar0.21100.32.5500.45500.57.575110100
inWG0.080.440.121100.162200.23300.4440
mmHg0.20.880.222200.34400.46600.8880
daPa210100325250450500575750101001000
kPa0.020.110.030.252.50.040.550.050.757.50.1110
hPa0.21100.32.5250.45500.57.575110100
  • Measuring ranges of the CP 111 transmitter on the ±100 Pa range according to the measurement unit
  • Measuring ranges of the CP 112 transmitter on the ±1000 Pa range according to the measurement unit
  • Measuring ranges of the CP 113 transmitter on the ±10 000 Pa range according to the measurement unit
    Example:
  • From 0 to 750 mmH2 O, the measuring range is 750 mmH2 O.
  • From -500 Pa to +500 Pa, measuring range is 1000 Pa

CP 114, CP 115

sauermann CP 110 Pressure Transmitter - fig8
Combination 1Combination 2Combination 3Combination 4Combination 5
Type of transmitterCP114CP115CP114CP115CP114CP115CP114CP115CP114CP115
mbar1005002007503001 0004001 5005002 000
inWG4020080300120400160600200800
kPa10502075301004015050200
PSI2104156208301040
mmHg804001606002408003201 2004001 600
mmH21 0005 0002 0007 5003 00010 0004 00015 0005 00020 000
daPa1527.5310415520
hPa1005002007503001 0004001 5005002 000
  • Measuring ranges of the CP 114 transmitter on the ±500 mbar range according to the measurement unit.
  • Measuring ranges of the CP 115 transmitter on the ±2000 mbar range according to the measurement unit.
    Example:
  • From 0 to 750 mmH2 O, the measuring range is 750 mmH2 O.
  • From -500 mbar to +500 bar, the measuring range is 1000 bar.

Standard range / central zero setting – left DIP switch

warning Please follow carefully the combinations besides the DIP switch. If the combination is wrongly done, the following message will appear on the display of the transmitter “CONF ERROR”. In that case, you will have to unplug the transmitter, place the DIP switches correctly, and then power the transmitter up.

sauermann CP 110 Pressure Transmitter - fig9

Output setting – right DIP switch
(CP 111/112/113/114/115 – AO and CP 111/112/113 – AN models) To set the type of analog output, please put the on-off switch of the output as shown beside.

sauermann CP 110 Pressure Transmitter - fig10

Units setting – right DIP switch
To set a measurement unit, but the on-off switches 2, 3, and 4 of the units as shown in the table below.

sauermann CP 110 Pressure Transmitter - fig11

Configuration via LCC-S software (option)
An easy and friendly configuration with the software! You can configure your own intermediary ranges.

warning The minimum difference between the high range and the low range is 20.
For example, it is possible to set the instrument from -20 to 0 Pa, from 0 to +20 Pa, or from -10 to +10 Pa… To access the configuration via software: set the DIP switches as
shown beside.
Note: the on-off switch 1 of the right DIP switch can be in any position (selection of the analog output 0-10 V or 4-20 mA). Connect the cable of the LCC-S to the connection of the transmitter.

sauermann CP 110 Pressure Transmitter - fig12

warningThe configuration of the parameters can be done either with the DIP switch or via software (you cannot combine both solutions).

Mounting

To mount the transmitter, mount the ABS plate on the wall (drilling: Ø 6 mm, screws and pins are supplied). Insert the transmitter on the fixing plate (see A on the drawing beside). Rotate the housing in a clockwise direction until you hear a “click” which confirms that the transmitter is correctly installed.

sauermann CP 110 Pressure Transmitter - fig13

warningOnce the transmitter is installed and powered up, please make an autozero to guarantee the correct working of the transmitter in any position.

Accessories

Please refer to the datasheet to get more information about available accessories.

Maintenance: please avoid any aggressive solvent. Please protect the transmitter and its probes from any cleaning product containing formalin, that may be used for cleaning rooms or ducts.Precautions for use: please always use the device in accordance with its intended use and within parameters described in the technical features in order not to compromise the protection ensured by the
device.

Download the LCC-S software user manualsauermann CP 110 Pressure Transmitter - qr1

https://sauermanngroup.com/en-INT/measuring-instruments/transmitters/software/lcc-s

sauermann CP 110 Pressure Transmitter - qr2

https://sauermanngroup.com/en-INT/measuring-instruments/transmitters/pressure-transmitters

sauermann CP 110 Pressure Transmitter - icon3Customer service portal
Utilisez notre Portail service clients pour nous contacter
Use our Customer service portal to contact us
https://sauermann-en.custhelp.com
www.sauermanngroup.com
CE and Dustbin

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals