Eaton Il159026en Cx Plus Controller Instructions

Eaton Il159026en Cx Plus Controller Instructions

EATON IL159026EN CX Plus Controller

EATON IL159026EN CX Plus

EATON IL159026EN CX Plus PRODUCT

Replacement instructions for CX with CX Plus controller

WARNING
ENSURE THAT THE UPSTREAM AND INTEGRAL (IF INCLUDED) DISCONNECT / OVERCURRENT PROTECTION DEVICE HAS BEEN TURNED OFF AND LOCKED OUT. ALSO ENSURE THE CT WIRES THAT ARE TERMINATED ON TERMINALS TB1–1 AND TB1–2 ARE SHORTED. WAIT AT LEAST 5 MINUTES AFTER DISCONNECTION OF POWER SUPPLY BEFORE OPENING THE ENCLOSURE FOR SERVICE.

CX controller removal

  1. For catalog option W remove all caulking around the CX controller.
  2. Remove all wires terminated into the BLR-CX controller, ensuring the wire markers do not become removed.
  3. Open the enclosure door and lift up/pull the slide tabs toward you to loosen the controller from its enclosure.
  4. The controller can now be removed by gently pushing the controller away from the enclosure door.

Re energizing the unit

  1. Once all wiring connections are completed, check all wiring is secured and tight.
  2. Remove the CT shorting link at TB1 terminals 1 and 2.
  3. Energize the upstream and/or integral disconnect/overcurrent protection device.
  4. The CX Plus controller is shown below

EATON IL159026EN CX Plus PRODUCT

 

CX Plus controller installation

  1. Place the BLR-CX Plus controller into the slot from the BLR-CX.
  2. Secure the controller in place using the tab slide-in mechanism (similar to the BLR-CX).
  3. For catalog option “W”, caulk around the CX Plus controller (between the facia and the door cutout).
  4. Reconnect all the following wires for UM1, UM2 A through 12, k and 1.
    1. Note: Output stages 13 and 14 will not have any wires connected to them.
  5. Remove and discard shorting wires from UM1 and UM2 to Lb (or La) and N.
  6. If this is an AutoVAR Filter, remove the RTF wire from Lb (CX) and connect it to UM2 (CX Plus).
  7.  For catalog option A, remove the wires from M/MS (CX) and terminate it onto the M/MS terminals of the CX Plus. Wire extension or rewiring from TB may be necessary for this change.

Digital display

EATON IL159026EN CX Plus 1

Screen legend

  • INFO Capacitor Database.
  • AUTO Automatic Mode.
  • MANUAL Manual Mode.
  • SETUP Setup Mode.
  • ALARM Blinking during alarm.
  • NT Second target-pf is active.
  • EXPORT Export of active energy.
  • 1-12 Capacitor stage number indication.
  • The CX Plus controller is operated by using four keys

Operational keys

EATON IL159026EN CX Plus 2

 

  • Press the up or down keys to scroll through submenus.
  • Pressing the right key enter allows selection, entering the Edit Mode, or accepts the edited values.
  • In the Edit Mode, the left key escape or right key scroll left and right to allow setting of the appropriate digit.
  • Outside of Edit Mode, the left key exits to the next higher level.
  • Press and hold the left key for approximately 3 seconds to silence any alarms.
  • Upon power on the controller displays the existing power factor value X.XX  and enters the Automatic Control Mode.
    • The I at the end indicates an inductive power factor and would be appropriate for most installations.
    • A c at the end indicates capacitive power factor and suggests reactive power export and may not be appropriate.
  • Set up the basic parameters in the controller.
  • From the main screen, press the down key to step through the INFO and SETUP modes.
  • When SETUP is shown, press the right key to enter the Menu 100.
  • Press the right key and program and/or verify the following values.
  • Un :Nominal voltage (factory programmed; customer may verify
  • Ct : CT ratio factory set to 600, which corresponds to 3000:5 current transformer ratio. Changing the CT ratio will change the capacitor step sizes in 402 and those values will have to be reprogrammed.
  • Pt :PT ratio factory programmed.
  • Ai :Start of automatic initialization factory programmed PFC P control ON/OFF/HOLD factory programmed CP1 Target PF customer to program.
  • St : Switching time delay factory programmed; customer may verify.
  • Out Output type of each stage Auto/Alarm/Fixed Off/Fixed Onfactory programmed; customer may verify.
  • Once the Menu 100 is programmed, press the left key three times to return to the main screen that displays the existing PF.
  • From the main screen, press the left key to enter the Measurement Mode to verify the measured values. See the menu map for a list of designated parameters.
  • Press the left key to return to the main screen that displays the existing PF.
  • To verify the capacitor bank is working, activate the controller in Manual Control Mode and cycle through all the available steps. Note: The steps will switch on only after the factory-set capacitor stage discharge time has elapsed.
  • After each manual operation of the stage, the PF should change in the right direction for example 0.70 i >> 0.78 i >> 0.85 i.
  • If the PF changes in the right direction, the capacitor bank has been correctly commissioned.
  • To switch the controller in Manual and Control Mode, press the down key to step through the INFO.
  • Press and hold the right key for approximately 3 seconds until 1 displays, indicating the stage number 1 is available for control.
  • The controller freezes the stages in their existing state ON, OFF, or HOLD.
  • Therefore, it is important to ensure that at the end of this step the controller is returned to the Automatic Control Mode by pressing the left key to return to the main screen that displays the existing PF.
  • After activating all available steps, one should make note of the displayed PF values, as that reading should be greater than or equal to the target PF desired.
  • If the displayed PF with the electrical system fully loaded and all steps energized is less than the target PF then the selected capacitor bank is not sized adequately to raise the PF to the desired value.
  • The customer should either upgrade the capacity of the capacitor bank or the target PF value should be decreased to prevent PF alarms.

Replacement instructions for CX with CX Plus controller

Default settings

EATON IL159026EN CX Plus 3

 

200

Setup measuring system

201

Nominal voltage phase phase

208 V / 240 V /480 V / 600 V

202

CT-ratio:  600 (corresponds to 3000:5 CT ratio

203

VT ratio

1.7(240 V unit)

3.7(480 V unit)

4.7(600 V unit)

204

Tolerance nominal voltage: 20%

205Voltage measuringY = L–L
206Phase-offset90
207Start automatic initializingN
208Synchronization to frequency60 (60 Hz unit)
209Temperature offset0 °C
300Setup control system
301Switching threshold55%
302Target-PF 10.95i
303Target-PF 20.95i
304Target-PF 2 at KW-exportN
305Switching time delay60 s
306Switching time delay for fine control10 s
307Fine control activeN for units with equal stage sizes

Y for units with multiple stage sizes

308Automatic Stage detectionN
309Block defective CapacitorsN
310Start/Stop/Hold PF-controlOn
311Control algorithm1
312Reactive-power offset0
313Asymmetrical switching time delay1
314Switch-off capacitors in leading conditionN
315Distribute sw. operationsN
316Detect faulty stagesY
400Setup capacitor database
401Discharge time60 s
402Capacitor size: step 1 max. 12Varies (see equipment drawings for step size, typically 25, 50, or 100 kvar capacitive

 

 

400Setup capacitor database continued
403Type of exit: step 1 max. 12Auto for each step
installed in unit
Fixed Off for unused
controller outputs
404Switching operations: step 1 max. 120
405Operations hours counter: step 1 max 120 h
406Fan relay as stage outputN
500Setup alarm system
501Reset alarms manuallyN
502THD U threshold6%
503Disconnect capacitors when THD >N
504THD alarm delay120 s
505Stop control if I=0N
506Service alarmN
507Max. operations per step262 k
508Max. operation hours of BLR-ACX-V65.5 k
509Max. operation hours per step65.5 k
510THD-I threshold20%
511Digital input logicY
512Temp. threshold level 1

(fan control, type of exit: AL)

40 °C
513Temp. threshold level 2, disconnect capacitors55 °C
514Control alarm (target cannot be reached)Y
515Faulty stages alarmY
516Stage power loss alarmY
517Flashing displayN
518Digital input functionCP2
519I Low alarm suppr.Y
520Switch off active stages if digital input alarmN
521I Low alarmY
522I High alarm delay10 s
523Switch off interval60 s
600Reset
601Reset to default valuesN
602Reset capacitor database to defaultN
603Reset operation hoursN
604Reset average PFN
605Reset max. temperatureN
606Reset alarmN
607Info firmware
608Change password242
609Restart first setupN
700

Modbus

Baud rate

 

19.2 k

Parity and stop bitsEVEN
Slave address1
800System
801Backlight during commissioning modeN
802Backlight delay time0.25 h

 

EATON IL159026EN CX Plus 5

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals