Siemens Pxc5.e003 System Controller Instruction Manual

PXC5.E003 System Controller

Product Information: DesigoTM System Controller PXC5.E003

The DesigoTM System Controller PXC5.E003 is a programmable
system controller for integration of BACnet/MSTP, Modbus, and KNX
PL-Link devices. It has a communication BACnet/IP (BTL certified)
and a 2-port Ethernet switch for low-cost cabling. The system
controller integrates Modbus data points via RTU and / or TCP,
BACnet MS/TP devices, and KNX PL-Link bus to connect sensors and
operator units (including bus power). This system controller
operates on AC 24 V and can be mounted on standard rails or on the
wall using plug-in screw terminal blocks.

Functions:

  • Freely programmable system controller.
  • System functions (alarming, scheduling, trending, access
    protection with individually definable user profiles and
    categories).
  • System controller for system networks with PXC3, PXC4, PXC5,
    PXC7 and DXR controllers over BACnet/IP, BACnet/SC, or BACnet
    MS/TP.
  • Integrates third-party devices and systems.
  • The following functions are available with KNX PL-Link bus:
    interface, generic object viewer for local data points and assigned
    devices via embedded web interface.
  • Engineering and commissioning with the ABT Site Tool using
    graphical function charts.
  • BTL tested BACnet communication on IP (BACnet/IP and BACnet/SC)
    or MS/TP, in compliance with the BACnet standard including B-BC
    profile (Rev. 1.15).
  • Wireless connection for engineering and commissioning.
  • Cloud connectivity for remote access.
  • Integration of Modbus data points via RTU and / or TCP.

Type Summary:

TypeOrder NumberNumber of integration data points (Modbus TCP and/or RTU)Number of BACnet/MSTP devices per RS485 interfaceNumber of BACnet/SC devices as a BACnet/SC hubNumber of KNX PL-Link devicesNumber of configurable RS485 interfaces either for integration
of Modbus RTU or BACnet MS/TP
PXC5.E003S55375-C1031) up to 500up to 60 2)up to 100up to 64 21) For details on engineering, see PXC4, PXC5 & PXC7
Planning overview, A6V13054435. 2) Depending on the behavior of the
third-party MS/TP devices

Equipment Combinations:

DescriptionType
Wall-mounted temperature sensorQMX3.P30
Wall-mounted temperature and humidity sensorQMX3.P40
Wall-mounted temperature, humidity, and CO2 sensorQMX3.P70
Wall-mounted temperature sensor and room operator unitQMX3.P34
Wall-mounted temperature and humidity sensor and room operator
unit
QMX3.P44
Wall-mounted temperature, humidity, and CO2 sensor and room
operator unit
QMX3.P74

Desigo Control Point:

Desigo Control Point is a BACnet touch panel with an integrated
web server available in three sizes: 7.0, 10.1, and 15.6. It also
offers touch panel clients with data storage in web server
PXG3.Wx00-1 available in the same three sizes. Additionally, it has
a BACnet/IP web server with standard functionality and an extended
functionality.

DescriptionType
BACnet touch panel with integrated web serverPXM30.E
BACnet touch panel with integrated web serverPXM40.E
BACnet touch panel with integrated web serverPXM50.E
Touch panel clients with data storage in web serverPXM30-1
Touch panel clients with data storage in web serverPXM40-1
Touch panel clients with data storage in web serverPXM50-1
BACnet/IP web server with standard functionalityPXG3.W100-2
BACnet/IP web server with extended functionalityPXG3.W200-2

Technical and Mechanical Design:

The DesigoTM System Controller PXC5.E003 has a compact build
that allows for mounting the devices on a standard rail or a
wall.

Product Usage Instructions:

Follow the below instructions to use DesigoTM System Controller
PXC5.E003:

  1. Connect the BACnet/MSTP, Modbus, and KNX PL-Link devices to the
    system controller using plug-in screw terminal blocks.
  2. For engineering and commissioning, use the ABT Site Tool with
    wireless connection or WLAN interface.
  3. To integrate third-party devices and systems, refer to the
    planning overview A6V13054435 and data sheets.
  4. To access system functions (alarming, scheduling, trending,
    access protection), create individually definable user profiles and
    categories.
  5. The DesigoTM System Controller PXC5.E003 can be mounted on
    standard rails or on the wall.
  6. For cloud connectivity for remote access, connect the system
    controller to the internet.
  7. For integration of Modbus data points via RTU and / or TCP,
    refer to the technical and mechanical design.

DesigoTM
System controller
PXC5.E003

System controller for integration of BACnet/MSTP, Modbus, and KNX PL-Link devices
System controller to integrate BACnet MS/TP, Modbus, and KNX PL-Link devices Communication BACnet/IP (BTL certified) 2-port Ethernet switch for low-cost cabling Integration of Modbus data points via RTU and / or TCP Integration of BACnet MS/TP devices KNX PL-Link bus to connect sensors and operator units (including bus power) WLAN interface for engineering and commissioning Operating voltage AC 24 V Mounted on standard rails or on the wall Plug-in screw terminal blocks

A6V11646020_en–_h 2022-08-30

Smart Infrastructure

Functions

Freely programmable system controller. System functions (alarming, scheduling, trending, access protection with individually
definable user profiles and categories) System controller for system networks with PXC3, PXC4, PXC5, PXC7 and DXR
controllers over BACnet/IP, BACnet/SC, or BACnet MS/TP Integrates third-party devices and systems The following functions are available with KNX PL-Link bus:
­ Communication with room operator units and sensors.
­ Plug-and-play connection of Siemens field devices with KNX PL-Link. Generic object viewer for data points of several assigned devices via embedded web
interface Generic object viewer for local data points and assigned devices via embedded web
interface Engineering and commissioning with the ABT Site Tool using graphical function charts BTL tested BACnet communication on IP (BACnet/IP and BACnet/SC) or MS/TP, in
compliance with the BACnet standard including B-BC profile (Rev. 1.15) Wireless connection for engineering and commissioning Cloud connectivity for remote access Integration of Modbus data points via RTU and / or TCP

Type summary

Type Order number Number of integration data points (Modbus TCP and/or RTU) Number of BACnet/MSTP devices per RS485 interface Number of BACnet/SC devices as a BACnet/SC hub Number of KNX PL-Link devices Number of configurable RS485 interfaces either for integration of Modbus RTU or BACnet MS/TP

PXC5.E003 S55375-C103 1) up to 500
up to 60 2) up to 100 up to 64 2

1) For details on engineering, see PXC4, PXC5 & PXC7 Planning overview, A6V13054435. 2) Depending on the behavior of the third-party MS/TP devices

Equipment combinations

KNX PL-Link devices

Description

Type

Wall-mounted temperature sensor

QMX3.P30

Wall-mounted temperature and humidity sensor

QMX3.P40

Wall-mounted temperature, humidity, and CO2 sensor Wall-mounted temperature sensor and room operator unit

QMX3.P70 QMX3.P34

Wall-mounted temperature and humidity sensor and room operator QMX3.P44 unit

Wall-mounted temperature, humidity, and CO2 sensor and room operator unit

QMX3.P74

Data sheet CM2N1602

For details, see planning overview A6V13054435 and data sheets.

2 Siemens Schweiz AG Smart Infrastructure

A6V11646020_en–_h 2022-08-30

Desigo Control Point
Description BACnet touch panels with integrated web server 7.0 ” 10.1 ” 15.6 ” Touch panels clients with data storage in web server PXG3.Wx00-1 7.0 ” 10.1 ” 15.6 ” BACnet/IP web server with standard functionality BACnet/IP web server with extended functionality

Type
PXM30.E PXM40.E PXM50.E
PXM30-1 PXM40-1 PXM50-1 PXG3.W100-2 PXG3.W200-2

Data sheet A6V11664137
A6V11664139
A6V12304192

Technical and mechanical design The compact build allows for mounting the devices on a standard rail or a wall.

5

6

7

8

4 Service button (network login and WLAN on/off)

5 2-port Ethernet switch with 2 LEDs per port for display purposes

6 Plug-in terminal block with screw terminals

KNX PL-Link

1

7 Plug-in terminal block with screw terminals

2

Power supply

3
4
Date/Series S/N
WLAN Default

8 Plug-in terminal blocks with screw terminals Digital input, for future use
9 Plug-in terminal block with screw terminals M-bus, for future use
10 Plug-in terminal block with screw terminals COM1 / COM2 (MS/TP or Modbus)

11 DIP switches for bus termination and polarization COM1 / COM2

15

16 11 10 12 11 10 13 9 14 12 Slider for mounting on standard mounting rails

13 Eyelets for cable ties

1 Plastic housing

14 Holes for wall mounting

2 Front cover

15 Date / Series and Serial number

3 LEDs for communication and state

16 QR code for default WLAN access Description see Technical data

Siemens Schweiz AG Smart Infrastructure

3 A6V11646020_en–_h
2022-08-30

LED displays
Activity

LED
Ethernet 1/2

Color Green

Yellow

RUN

Green

Red

Blue

BAT

Red

COM… Yellow

KNX

Yellow

SVC

Red

Activity
Continuously ON Continuously OFF Flashing
Continuously ON Continuously OFF
Continuously ON Continuously OFF Flashing
Continuously OFF Continuously ON Rapid flashing
Continuously ON Continuously OFF
Continuously OFF Continuously ON
Flashing Continuously OFF
Flashing Continuously OFF
Continuously OFF Flashing
Flashing per wink command

Function
Link active No connection Network traffic
Link 100 Mbps Link 10 Mbps
Device operational Device not operational Start-up or program halted
OK HW or SW fault Firmware or application missing/corrupted
Connection to the cloud OK No connection to the cloud
Optional battery OK Optional battery empty – replace
Communication No communication to subsystem
Communication No communication to subsystem
OK Device is not configured
Identification of the device after receipt of wink command

5 Hz

5 Hz

WLAN

Blue

Service button

2s

1s

2s

1s

Steady OFF Steady ON Flashing
Press 0.2 … 1 s Press 1 … 3 s
As per description

WLAN inactive WLAN active and at least one WLAN client connected WLAN active and no WLAN client connected
Identification in the network Enable/disable WLAN WLAN is disabled automatically after 10 min if no client is connected
Do the following to reset the device to factory state:
1. Power off the device.
2. Power on the device.
3. Wait until all LEDs light up and turn off again, then press the Service button.
4. Keep the Service button pressed until all LEDs light up, then release the button. All LEDs go off, the device restarts.
5. Wait until the device has fully started ­ unconfigured (green RUN LED and red SVC LED are flashing)

4 Siemens Schweiz AG Smart Infrastructure

A6V11646020_en–_h 2022-08-30

Product documentation Related documents such as the environmental declarations, CE declarations, etc., can be downloaded from the following Internet address: www.siemens.com/bt/download
Notes Safety
CAUTION
National safety regulations Failure to comply with national safety regulations may result in personal injury and property damage. Observe national provisions and comply with the appropriate safety regulations.

Mounting position and ambient temperature The devices can be snapped onto standard rails or screwed onto a flat surface. Plug-in screw terminals connect power and interfaces.

Ambient temperature -5…50 °C (23…122 °F) Wall, horizontal
­ From left to right ­ From right to left

Ambient temperature -5…45 °C (23…113 °F) Overhead Wall, vertically
­ From top to bottom
­ From bottom to top On a horizontal surface

Installation

WARNING
Electric shock Incorrect installation of the device may lead to electric shock injuries when touching the device!
Install the device in a lockable cabinet or use terminal covers. Do not install the device in locations where children are likely to be present. Conductors with a cross-section of 0.5 mm2 (AWG24) or greater shall comply with the
requirements of IEC 60332-1-2 and IEC 60332-1-3 or IEC TS 60695-11-21.

Disposal

The device is considered an electronic device for disposal in accordance with European Directive and may not be disposed of as domestic waste.
Use only designated channels for disposing the devices.
Comply with all local and currently applicable laws and regulations.
Dispose of empty batteries at designated collection points.

Siemens Schweiz AG Smart Infrastructure

5 A6V11646020_en–_h
2022-08-30

Technical data Power supply

Operating voltage (24 V~, , )

Functional ground (US) Functional earth
Screw terminals for wire cross sections up to Internal fusing External supply line fusing (EU)

AC 24 V -15 / +20 % (PELV) AC 24 V Class 2 (US) 48…63 Hz
The terminal for the functional ground must be connected on the installation side with the building grounding system (PE).
Max. 2.5 mm2 (14 AWG)
3.15 A irreversible / non-replaceable
Non-renewable fuse max. 10 A slow-blow or circuit breaker max. 13 A Tripping characteristic B, C, D per EN 60898 or Power supply with current limitation of max. 10 A

Power consumption (for transformer planning)

Full load Base load (without loading by KNX PL-Link and M-Bus) KNX PL-Link supply M-Bus supply, for future use

19 VA / 0.8 A 12 VA / 0.5 A 4 VA / 0.17 A 3 VA / 0.13 A

Function data

Hardware information Processor Storage

NXP i.MX8 DualX, 1 GHz
1 GByte RAM 8 GByte eMMC

Interfaces

Data backup in the event of power failure
Energy reserve (Supercap) to support real-time clock (7 days). Energy reserve to support real-time clock can be extended using optional battery CR2032: depending on the life time of battery and use, typical 10 years. (Battery safety requirement and specification for CR2032 according to IEC 60086-4 or UL1642. Battery must be rated for ambient temperature 70 °C (158 °F)) Low power of battery will be indicated by LED and a system alarm will be generated
Data available if stored to flash memory. Occurs every 5 minutes. The interval of 5 minutes is only valid for change log but not for trending. In case of a power failure, trend log data can be lost up to 30 minutes.

Ethernet interface Plug Interface type Bit rate Protocol
Cabling (in-house cabling only), cable type
Cable length

2 x RJ45, shielded
10Base-T / 100Base-TX, IEEE 802.3 compatible
10/100 Mbps, autosensing
BACnet/IP on UDP/IP, BACnet/SC on TCP/IP, and HTTPS on TCP/IP
10 Mbps: Min. CAT3, shielded cable is recommended 100 Mbps: Min. CAT5, shielded cable is recommended
Max. 100 m (330 ft)

6 Siemens Schweiz AG Smart Infrastructure

A6V11646020_en–_h 2022-08-30

Screw terminals, plug-in Cu-wire or Cu-strand with wire end sleeve
Cu-strand without wire end sleeve
Stripping length Screwdriver Max. tightening torque

1 x 0.6 mm to 2.5 mm2 (22 to 14 AWG) or 2 x 0.6 mm to 1.0 mm2 (22 to 18 AWG) 1 x 0.6 mm to 2.5 mm2 (22 to 14 AWG) or 2 x 0.6 mm to 1.5 mm2 (22 to 16 AWG) 6…7.5 mm (0.24…0.29 in) Slot screws, screwdriver size 1 with shaft ø = 3 mm 0.6 Nm (0.44 lb ft)

The two COM interfaces can be used either for Modbus or for MS/TP, according to configuration.

Modbus RTU interface Interface type Baud rate
Internal bus termination Internal bus polarization
Cabling (in-house cabling only) Cable length
Protection

EIA-485, electrically isolated
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 76800, 115200 (depending on the configuration)
120 Ohm, switchable with DIP switch
270 Ohm pull-up/pull-down resistances, switchable with DIP switch
3-wire cable, shielded cable recommended (shield must be connected to building earth in the mounting panel) Max. 1000 m (3300 ft)
Short-circuit proof Protection against faulty wiring with AC 24 V

BACnet MS/TP interface Interface type Baud rate
Internal bus termination Internal bus polarization
Cabling (in-house cabling only) Distance between 2 devices Length of the MS/TP line Protection

EIA-485, electrically isolated
9600, 19200, 38400, 76800, 115200 (depending on the configuration)
120 Ohm, switchable with DIP switch
270 Ohm pull-up/pull-down resistances, switchable with DIP switch
3-wire cable, shielded Max. 500 m (1650 ft) Max. 1000 m (3300 ft)
Short-circuit proof Protection against faulty wiring with AC 24 V

Siemens Schweiz AG Smart Infrastructure

7 A6V11646020_en–_h
2022-08-30

Conformity

WLAN interface

Interface type

Wireless access point

Supported standards Frequency band WLAN channels Maximum radio-frequency power

IEEE 802.11b/g/n 2.4…2.462 GHz 1…11 16.4 dBm

Distance (unobstructed field)

Min. 5 m (16 ft)

Device pairing

Activation / Deactivation with service button
Automatic switch off after 10 minutes if no WLAN-client is connected.
Optionally, for cyber security reasons, the WLAN can be permanently disabled via configuration.

Default SSID and WLAN password: Scan the QR code. It will show something like WIFI:S:PXC5.E003_0000550;T:WPA;P:1400052738;; Then SSID = PXC5.E003_0000550 and password = 1400052738
Determine manually: Use the information from the Date/Series/SN block It will show something like:
Date/Series: 20190423A0000550 S/N: 1400052738
SSID = <ASN>_<Running number after the series letter> and password = <S/N>

KNX PL-Link interface Type
Cabling (in-house cabling only) Cable length Internal bus power

KNX TP1 PL-Link, galvanic isolation Baud rate: 9.6 kbps
2-wire cable, 0.75 mm2 / AWG20 or 1 mm2 / AWG18 With internal supply: Max. 80 m (262 ft) With external supply: Max. 1000 m (3300 ft)
Max. 50 mA When using external bus power for KNX PL-Link, switch off the internal bus power via the ABT Site Tool.

Ambient conditions and protection classification

Classification as per EN 60730 Automatic action Control function Degree of pollution Overvoltage category

Type 1 Class A 2 I

Protection against electric shock

Protection class III

Degree of protection of housing to EN 60529 Front parts in DIN cut-out Terminal part

IP30 IP20

Climatic ambient conditions
Storage / Transport (packaged for transport) as per IEC EN 6072132

Operation as per IEC/EN 60721-3-3

Class 1K22 / 2K12 Temperature -25…70 °C (-13…158 °F) Air humidity 5…95 % (non-condensing)
Class 3K23 Temperature -5…50 °C (23…122 °F) (for details see chapter Mounting) Air humidity 5…95 % (non-condensing)

Mechanical ambient conditions Transport per IEC/EN 60721-3-2 Operation as per IEC/EN 60721-3-3

Class 2M4 Class 3M11

8 Siemens Schweiz AG Smart Infrastructure

A6V11646020_en–_h 2022-08-30

Standards, directives and approvals Product standards Product family standard Electromagnetic compatibility (EMC)
EU conformity (CE) EAC compliance RCM conformity UL/cUL approbation (US / Canada) CSA certification
FCC BACnet. Environmental compatibility 1)

IEC/EN 60730-1, IEC/EN 62368-1
IEC/EN 63044-x
For residential, commercial, and industrial environments
See CE declaration 1)
Eurasian compliance
See RCM declaration 1)
UL916; http://ul.com/database
C22.2, http://csagroup.org/services-industries/productlisting
CFR 47 Part 15C
B-BC
The product environmental declaration 1) contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal).

1) Documents can be downloaded at http://siemens.com/bt/download.

FCC Statement
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. this device must accept any interference received, including interference that may cause undesired operation
FCC Caution: Changes or modifications not expressly approved by Siemens Switzerland Ltd. could void user authority to operate the equipment. United States representative https://new.siemens.com/us/en/products/buildingtechnologies/home.html

Industry Canada statement This device complies with ISED’s license-exempt RSSs. Operation is subject to the following two conditions:
1. This device may not cause interference, and
2. This device must accept any interference received, including interference that may cause undesired operation.

Siemens Schweiz AG Smart Infrastructure

9 A6V11646020_en–_h
2022-08-30

Housing

Radiofrequency radiation exposure statement
This equipment complies with FCC and IC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with a minimum distance of 20 cm between the radiator and your body.
This transmitter must not be co-located or operated in conjunction with any other antenna or transmitter.

Color top/bottom Dimensions Weight without/with packaging

RAL 7035 (light grey) / RAL 7016 (anthracite grey) per DIN 43880, see dimensions 351 g / 391 g

10 Siemens Schweiz AG Smart Infrastructure

A6V11646020_en–_h 2022-08-30

Connection terminals

34

567

10 11

65 66 67

68 69 70

71 72

Warranty

Terminal 1, 2
3, 4 5, 6 7
10, 11 Term Polar 65, 66, 67 68, 69, 70 71, 72

Symbol
KNX ~ ,
D, On, off On, off COM1 COM2 MBUS

Description 2 x RJ45 interface for Ethernet with switch
KNX PL-Link Operating voltage AC 24 V Functional ground must be connected on the installation side with the building grounding system (PE). Digital input (for future use) Switch for bus termination Switch for polarization Interface EIA-485 (Modbus RTU and MS/TP)
M-bus interface (for future use)

The application-specific technical data is guaranteed only in combination with the Siemens products listed in the ‘Device combinations’ section. If third-party products are used, any guarantee provided by Siemens will be invalidated.

Siemens Schweiz AG Smart Infrastructure

11 A6V11646020_en–_h
2022-08-30

21.5 (0.85″) 11 (0.43″)

45 (1.77″)

124 (4.88″) 117 (4.61″)

Dimensions

All dimensions in mm and inches

110 (4.33″) 35.5 (1.40″)

129 (5.08″) 144 (5.67″)

4 (0.16″)
26.5 (1.04″) 45 (1.77″) 49 (1.91″) 65.5 (2.58″) 70.5 (2.78″)

4.1 (0.16″)

21.5 (0.85″) 11 (0.43″)

Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies

Document ID Edition

A6V11646020_en–_h 2022-08-30

© Siemens Switzerland Ltd, 2020 Technical specifications and availability subject to change without notice.

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals