Nvent Csbma050050 Csbma Structural Attachment Fitting Instruction Manual

CSBMA050050 CSBMA Structural Attachment Fitting

Product Information:

  • Product Name: CSBMA050050(XX) and CSBMA050075(XX)
  • Part Number: CSBMA050050(XX) and CSBMA050075(XX)
  • Attachment Hole: 1/2 inch (13 mm) and 3/4 inch (19 mm)
  • Finish Specifier: (XX)
  • Load Ratings:
    • UL Loads (Listed for Structural Attachment):
      • Parallel to Structure, Perpendicular to Beam: 680 lb (3,025
        N)
      • Perpendicular to Structure, Perpendicular to Beam: 1,100 lb
        (4,893 N)
      • Parallel to Structure, Parallel to Beam: 1,300 lb (5,783
        N)
    • FM Horizontal Load Ratings:
      • Installation Angle 30 – 44: 3,290 lb (14,630 N)
      • Installation Angle 45 – 59: 4,520 lb (20,100 N)
      • Installation Angle 60 – 74: 5,540 lb (24,640 N)
      • Installation Angle 75 – 90: 6,200 lb (27,570 N)

Product Usage Instructions:

  1. Ensure that the Sway Brace assemblies are installed in
    accordance with NFPA-13 and the manufacturer’s installation
    instructions.
  2. Use the required type, number, and size of fasteners for the
    structure attachment fitting in accordance with NFPA-13.
  3. Only use SAE grade 5 or higher strength fasteners when
    assembling other structural fittings or braces to CSBMA.
  4. Combine CSBMA with CSBUNIV050(XX) and CSBU1 for proper
    installation.
  5. CSBMA050050(XX) and CSBMA050075(XX) do not include Structure
    Attachment Fittings.
  6. For concrete installation, use a cast-in-place anchor, wedge,
    pre-set, or a concrete anchor screw.

WARNING:

  1. nVent products must be installed and used only as indicated in
    nVent product instruction sheets and training materials.
    Instruction sheets are available at www.nVent.com and from your
    nVent customer service representative.
  2. nVent products must never be used for a purpose other than the
    purpose for which they were designed or in a manner that exceeds
    specified load ratings.
  3. Follow all instructions completely to ensure proper and safe
    installation and performance.
  4. Improper installation, misuse, misapplication, or failure to
    follow nVent’s instructions and warnings may cause product
    malfunction, property damage, serious bodily injury, and/or death,
    and void your warranty.
  5. Products manufactured using spring steel components should only
    be used in a non-corrosive indoor environment.
  6. All pipe supports, hangers, intermediate components, and
    structural attachments must ONLY be used as described herein and
    are NEVER to be used for any other purposes.

Technical Support: www.nVent.com

INSTRUCTION SHEET

*Part Number
CSBMA050050(XX) CSBMA050075(XX)

Attachment Hole

Inch

mm

1/2

13

3/4

19

*(XX) = Finish Specifier

Parallel to Structure, Perpendicular to Beam

Sway Brace assemblies are intended to be installed in accordance with NFPA-13 and the manufacturer’s installation instructions. The required type, number, and size of fasteners used for the structure attachment fitting shall be in accordance with NFPA-13. Only SAE grade 5 or higher strength fasteners are to be used when assembling other structural fittings or braces to CSBMA. CSBMA is a Structural Attachment Fitting. It is intended to be combined with the CSBUNIV050(XX)and CSBU1.
Perpendicular to Structure, Perpendicular to Beam

LOAD
Parallel to Structure, Parallel to Beam

Installation Angle from Vertical

LOAD

Installation Angle from Vertical

Section View

0.50 [12.7]

LOAD Installation Angle
WARNING: 1. nVent products shall be installed and used only as indicated in nVent product instruction sheets and training materials. Instruction sheets are available at
www.nVent.com and from your nVent customer service representative. 2. nVent products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings. 3. All instructions must be completely followed to ensure proper and safe installation and performance. 4. Improper installation, misuse, misapplication or other failure to completely follow nVent’s instructions and warnings may cause product malfunction, property
damage, serious bodily injury and/or death, and void your warranty. 5. Products that are manufactured using spring steel components shall be used only in a non-corrosive indoor environment. 6. All pipe supports, hangers, intermediate components and structural attachments must ONLY be used as described herein and are NEVER to be used for any
other purpose. NOTE: All load ratings are for static conditions and do not account for dynamic loading such as wind, water or seismic loads, unless otherwise noted. The customer is responsible for: a. Conformance to all governing codes. b. The integrity of structures to which the products are attached, including their capability of safely accepting the loads imposed, as evaluated by a qualified engineer. c. Using appropriate industry standard hardware as noted above. SAFETY INSTRUCTIONS: All governing codes and regulations and those required by the job site must be observed. Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.

nVent, nVent CADDY, nVent ERICO Cadweld, nVent ERICO Critec, nVent ERICO, nVent ERIFLEX, and nVent LENTON are owned by nVent or its global affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without prior notice.

TECHNICAL SUPPORT: www.nVent.com

CFS382_H

1 OF 3

© 2009-2020 nVent All Rights Reserved

INSTRUCTION SHEET

Part Number

UL Loads (Listed for Structural Attachment)

Structure

Parallel to Structure Perpendicular to Structure

Attachment Fitting Perpendicular to Beam Perpendicular to Beam

Parallel to Structure Parallel to Beam

CSBMA050050(XX) CSBMA050075(XX)

CSBUNIV050(XX) CSBU1
CSBURC12 CSBNPC12 CSBUNIV050(XX)
CSBU1 CSBURC12 CSBNPC12

680 lb (3,025 N)
1,100 lb (4,893 N) 1,300 lb (5,783 N)
680 lb (3,025 N)
1,100 lb (4,893 N) 1,300 lb (5,783 N)

1. Structure Attachment Fittings are not included with CSBMA050050(XX) and CSBMA050075(XX)

Part Number
CSBMA050050(XX) CSBMA050075(XX)

30 – 44 3,290 lb (14,630 N)

FM Horizontal Load Ratings

Installation Angle

45 – 59

60 – 74

4,520 lb (20,100 N)

5,540 lb (24,640 N)

75 – 90 6,200 lb (27,570 N)

Concrete anchor could be cast in place, wedge, pre-set or a concrete anchor screw.

nVent, nVent CADDY, nVent ERICO Cadweld, nVent ERICO Critec, nVent ERICO, nVent ERIFLEX, and nVent LENTON are owned by nVent or its global affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without prior notice.

TECHNICAL SUPPORT: www.nVent.com

CFS382_H

2 OF 3

© 2009-2020 nVent All Rights Reserved

INSTRUCTION SHEET

Through bolt shown. A lag screw may also be used.

Concrete anchor could be cast in place, wedge, pre-set or a concrete anchor screw.

nVent, nVent CADDY, nVent ERICO Cadweld, nVent ERICO Critec, nVent ERICO, nVent ERIFLEX, and nVent LENTON are owned by nVent or its global affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without prior notice.

TECHNICAL SUPPORT: www.nVent.com

CFS382_H

3 OF 3

© 2009-2020 nVent All Rights Reserved