Skinner Em Emergency Pipe Repair Clamp Instruction Manual

Skinner Em Emergency Pipe Repair Clamp Instruction Manual

Skinner-EM-Emergency-Pipe-Repair-Clamp-LOGO

Skinner EM Emergency Pipe Repair Clamp

Skinner-EM-Emergency-Pipe-Repair-Clamp-PRODUCT

INSTALLATION PROCEDURE

EMERGENCY CLAMPS:
The Skinner Emergency Clamps are designed for use on Steel, Ductile and Cast Iron pipes to repair pit holes, splits, and corrosion leaks. This clamp can be used on pipes for Gas, Water, Oil, or Ammonia. Sizes and pressure ratings are as follows:

SizeBolt TorqueMax. Working

Pressure

0.50”10 ft/lb600 psi
0.75”10 ft/lb600 psi
1.00”18 ft/lb600 psi
1.25”18 ft/lb600 psi
1.50”18 ft/lb600 psi
2.00”40 ft/lb600 psi
2.50”40 ft/lb600 psi
SizeBolt TorqueMax. Working

Pressure

3.00”40 ft/lb500 psi
3.50”40 ft/lb500 psi
4.00”50 ft/lb500 psi
5.00”50 ft/lb450 psi
6.00”50 ft/lb400 psi
8.00”60 ft/lb300 psi
10” & 12”60 ft/lb200 psi

Installation Procedure:

Step #1Thoroughly clean the damaged area with a wire brush. Remove all pipe scale, rust, and foreign material. This will

help insure a “bubble tight” seal.

Step #2Place the clamp around the pipe so that the leak is completely covered by the clamp gasket.
Step #3Tighten the bolts evenly to the recommended torque shown above.
Step #4Pressure test the complete installation for leaks.
Step #5Check for leaks before leaving repair site.

GASKET Material: Buna-N (Nitrile Rubber) rated at 250 F Max to -20 F Min Temp.

IMPORTANT: DO NOT EXCEED TEMPERATURE OR PRESSURE RATINGS!

  • The Skinner Company
  • 1519 Evans Pond Road
  • Greenwood, South Carolina 29649
  • USA
  • 877-923-7700 (Ph)
  • 864-953-9724 (Fx)
  • www.skinnerco.com