Siemens Trx-2 Addressable Interface Modules Instruction Manual

Siemens Trx-2 Addressable Interface Modules Instruction Manual

SIEMENS logoSIEMENS TRX 2 Addressable Interface Modules - logo 2Addressable Interface Modules
Models TRX-2, TRX-2R, TRX-2D
Installation/Wiring Instructions

INTRODUCTION

The Models TRX-2 and TRX-2R are addressable interface modules that can monitor and supervise a single normally open or normally closed switch. The Model TRX-2D (dual TRX) is an addressable interface module occupying two address spaces. It can monitor and supervise two switches, either of which may be normally open or normally closed. For example, Model TRX-2D can be used to monitor and supervise a tamper switch and a waterflow switch from one TRX.
Models TRX-2 and TRX-2D are used where no relay control is required. Model TRX-2R (relay TRX) is used where relay control of external equipment is required. This module (an upgraded version of the TRX-1) has a latching type, single pole, double throw, relay contact rated:
2A at 125 VAC inductive, or 2A at 30 VDC resistive

MECHANICAL REQUIREMENTS

Models TRX-2/2R/2D are all provided with an extra terminal (terminal 8) for direct connection to Earth Ground. See WIRING INFORMATION for details.
All Model TRXs mount directly to a 3½ inch deep, double gang switchbox – no other box can be used. See MOUNTING for details.

OPERATION

Each TRX-2 has a programmable dipswitch with switches marked 1 through 9, as shown in FIGURE 1. Switches 1-5 are used to select the unique address code for each device (See Device Address Programming below). Switches 6-9 are used to identify the type of supervised switch monitored (See Device Identification Programming below).
Device Address Programming

  1. Position the TRX addressable interface module as shown in FIGURE 1 and locate the programmable dipswitch.
  2. When using the Model TRX-2 or TRX-2R: Refer to TABLE 1 to obtain the unique address code that must be set on dipswitch switches 1-5 for that device.
  3. When using the Model TRX-2D: Refer to TABLE 1 to obtain the unique even address code that must be set on dipswitch

SIEMENS TRX 2 Addressable Interface Modules - FGURE 1 MODEL TRX-2 2R 2D

SIEMENS TRX 2 Addressable Interface Modules - logo 3A Division of CERBERUS Technologies, Inc.
8 Ridgedale Avenue, Cedar Knolls, New Jersey 07927

TABLE 1
DEVICE ADDRESS CODES

AddressDipswitch Settings
12345
*10XXXX
2X0XXX
300XXX
4XX0XX
50X0XX
6X00XX
7000XX
8XXX0X
90XX0X
10X0X0X
1100X0X
12XX00X
130X00X
14X000X
150000X
16XXXX0
170XXX0
18X0XX0
1900XX0
20XX0X0
210X0X0
22X00X0
23000X0
24XXX00
250XX00
26X0X00
2700X00
28XX000
290X000
*30X0000

X = Closed; 0 = Open
• Addresses 1 and 30 cannot be used with Model TRX-2D.
switches 1-5 for that device. (Only even numbered address codes can be selected for TRX-2D.) When the desired ad­ dress code is selected, the next higher address code (an odd number) will also automatically be selected, thereby setting up dual, sequential address slots.
a. Addresses 1 and 30 cannot be used with the TRX-2D.
b. Supervised switch SA, connected to terminals 3 and 4, has its status reported by the odd numbered address.
c. Supervised switch SB, connected to terminals 5 and 6, has its status reported by the even numbered address.
Device Identification Programming

  1. Position the addressable interface module as shown in FIGURE 1 and locate the programmable dipswitch.
  2. When using Model TRX-2 or Model TRX-2R, refer to TABLE 2 to select the identification code on switches 6-9 for the type of supervised switch being used. A TRX-2/2R cannot be used to replace a TRX-1 configured as a status switch.
    Type of DeviceDipswitch SettingsTRX-1
    Replacement 
    6789
    Alarm/Trouble Causing No Alarm/Trouble Causing Status and/or Remote Relay
    Remote Relay
    X000Yes
    Yes
    No
    Yes
    0000
    000X
    00X0
  3. When using Model TRX-2D, refer to TABLE 3 to select the identification code for the types of supervised switches being monitored.

TABLE 2
TRX-2/-2R DEVICE IDENTIFICATIONSIEMENS TRX 2 Addressable Interface Modules - FACEPLATEFIGURE2
MODEL TRX-2/2R/2D FACEPLATE

TABLE3
TRX-2D DEVICE IDENTIFICATION CODE

Type of DeviceDipswitch SettingsType of Supv Switch*
6789S BS A
Trouble Causing/Status
Alarm Causing/Status
Alarm/Trouble Causing
Dual Trouble Causing
Dual Alarm Causing
Dual Status
XXX0Trouble Causing
Alarm Causing
Alarm Causing
Trouble Causing
Alarm Causing
Status
Status
Status
Trouble Causing
Trouble Causing
Alarm Causing
Status
0XX0
XX00
0X00
X000
0000

X = Closed; O = Open
Status is intended for contact monitoring application where programmed for other than fire alarm or trouble, such as supervisory service.

  • All supervised switches may be normally open or normally closed types. Only one normally closed switch may be connected per circuit.

WIRING INFORMATION

  1. Position the addressable interface module as shown in FIGURE 1.
  2. Refer to the wiring information on the faceplate (See FIGURE 2). Each module has an X marked to indicate the type of model and another X marked to indicate the wiring connec­tions to be made to that module.
  3. Refer to the appropriate wiring diagram (FIGURE 3, 4, or 5) and wire the addressable interface module accordingly. model and another X marked to indicate the wiring connec­tions to be made to that module.
  4. Refer to the appropriate wiring diagram (FIGURE 3, 4, or 5) and wire the addressable interface module accordingly.

SIEMENS TRX 2 Addressable Interface Modules - MODEL TRX 2 WIRINGFIGURE3
MODEL TRX-2 WIRING SIEMENS TRX 2 Addressable Interface Modules - MODEL TRX-2R WIRINGFIGURE4
MODEL TRX-2R WIRING SIEMENS TRX 2 Addressable Interface Modules - MODEL TRX-2D WIRINGFIGURE 5
MODEL TRX-2D WIRING

NOTES

  1. All supervised switches must be held closed and/or open for at least 1 O seconds in order to guarantee detection.
  2. End of line device: 27K, 1/4W resistor.
  3. The supervised switches have the following ratings:
    Voltage maximum14 VDC
    Current maximum3mA during polling
    Contact resistance10 ohms
    Maximum cable length200 feet (18 AWG)

    Maximum capacitance:
    CLine to shield = .04uF
    CLine to line = .02uF

  4. Supervised Switch SA is supervised on odd numbered addresses only. Supervised Switch SB is supervised on even numbered addresses only.
  5. Relay contacts are rated:
    2A, 125 VAC inductive, or 2A, 30 VDC resistive
    The relay is shown in standby condition.
  6. Earth Ground is the INX wiring shield when using shielded cable, or the conduit when not using shielded cable.
  7. A TRX-2/2R cannot be used to replace a TRX-1 configured as a status switch.

MOUNTING
Addressable Interface Model TRX-2, TRX-2D, or TRX-2R mounts directly into a 3½ inch deep, double gang switchbox (user supplied) only. Each module is secured to the switchbox with a standard blank, double gang swashplate (also user supplied). Refer to FIGURE 6 for details.

SIEMENS TRX 2 Addressable Interface Modules - MOUNTING THE TRX-2 2R 2DFIGURE 6
MOUNTING THE TRX-2/2R/2D
PIN 315-086678C
firealarmresources.com

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals