ZP-05 Isolated HART Intelligent Temperature Transmitter
ZP-05 Isolated HART Intelligent Temperature Transmitter (Round
Card) Operating Manual
Product Introduction
The ZP-05 Isolated HART Intelligent Temperature Transmitter
(Round Card) is a device used for the signal input of Resistance
Temperature Detector (RTD) and Thermocouple (TC) and 4-20mA analog
output of the two-wire system. It can be installed in the sensor
(Form B) through the HART protocol configuration.
Appearance Structure Diagram

Installation Schematic Diagram

Configuration Schematic Diagram

Wiring Diagram

Technical Parameters
| Input | Input signal | Cold-junction compensation | Temperature scope | Compensation precision |
|---|---|---|---|---|
| Resistance temperature detector (RTD), thermocouple (TC) | -20 – 60 temperature scope |
| Output | Output signal | Load resistance | Output current of upper and lower limit overflow alarm |
|---|---|---|---|
| 4-20mA, overlaid HART protocol | RL(Ue-12)/0.021 | IH=21mA, IL=3.8mA |
| Power supply | Supply voltage |
|---|---|
| DC12-40V |
| Other parameters | Temperature drift | Response time | Used environmental temperature | Storage temperature | Insulation strength (between input and output) | Insulation resistance (between input and output) | Aseismicity | Installation angle | Installation area | Electromagnetic compatibility |
|---|---|---|---|---|---|---|---|---|---|---|
| 0.0075%FS/°C | Reach to 90% of the final value for 700ms | -40 – 80°C | -40 – 100°C | 1500Vrms (1 min, without spark) | 100M (under the 500 VDC) | 4g/2 – 150Hz | Unlimited | B-type top cassette installation | Conform to GB/T18268 industrial equipment application requirements (IEC 61326-1) |
Product Usage Instructions
- Install the ZP-05 Isolated HART Intelligent Temperature
Transmitter (Round Card) in the sensor (Form B) through the HART
protocol configuration. - Connect the input signal of Resistance Temperature Detector
(RTD) or Thermocouple (TC) to the device. - Connect the 4-20mA analog output of the two-wire system to the
device. - Connect the power supply of DC12-40V to the device.
- Configure the device based on the Configuration Schematic
Diagram provided in the user manual. - The device is now ready to use.
ZP-05 Isolated HART Intelligent Temperature Transmitter (Round Card) Operating Manual
Product Introduction ZP-05 isolated HART intelligent temperature transmitter (round card) is usedfor
the signal input of resistance temperature detector (RTD) and thermocouple (TC) and 4 – 20mA analog output of the two-wire system, and can be installed in the sensor(Form B) through the HART protocol configuration. 1. Appearance Structure Diagram
2. Installation Schematic Diagram
1
3. Configuration Schematic Diagram
4. Wiring Diagram
5. Technical Parameters
Input Input signal Cold-junction compensation
Resistance temperature detector (RTD), thermocouple (TC) -20 -60
2
temperature scope
Compensation precision
±1
Output
Output signal
4-20mA, overlaid HART protocol
Load resistance
RL(Ue-12)/0.021
Output current of upper and lower IH=21mA, IL=3.8mA
limit overflow alarm
Power supply
Supply voltage
DC12-40V
Other parameters
Temperature drift
0.0075%FS/
Response time
Reach to 90% of the final value for700ms
Used environmental temperature -40 – 80
Storage temperature
-40 – 100
Insulation strength (between input 1500Vrms (1 min, without spark)
and output)
Insulation resistance (between
100M(under the 500 VDC)
input and output)
Aseismicity
4g/2 – 150Hz
Installation angle
Unlimited
Installation area
B-type top cassette installation
Electromagnetic compatibility
Conform to GB/T18268 industrial equipment application
requirements (IEC 61326-1)
Input type and transmission accuracy:
Model
Type
Resistance temperature
detector
Pt100 Cu50
Measurement
Minimum
Conversion accuracy
scope
measurement scope
(larger value)
-200850
20
±0.1%range Or±0.2
-50150
20
±0.1%range Or±0.2
3
(RTD)
B
Thermocouple
E
(TC)
J
K
N
R
S
T
1001820 -1001000 -1001200 -1801372 -1801300 -501768 -501768 -200400
500 50 50 50 50 500 500 50
±0.1%range Or±1.5 ±0.1%range Or±0.5 ±0.1%range Or±0.5 ±0.1%range Or±0.5 ±0.1%range Or±0.5 ±0.1%range Or±1.5 ±0.1%range Or±1.5 ±0.1%range Or±0.5
Notes: 1. The above accuracy data was obtained by testing at an ambient temperature of 20 °C ± 2 °C. 2. The output precision “%” is relative to the set range. 3. The cold end compensation error needs to be added to the thermocouple measurement, and the internal cold end compensation error is ±1°C.
4