Blue Jay Zp-05 Isolated Hart Intelligent Temperature Transmitter Instruction Manual

ZP-05 Isolated HART Intelligent Temperature Transmitter

ZP-05 Isolated HART Intelligent Temperature Transmitter (Round
Card) Operating Manual

Product Introduction

The ZP-05 Isolated HART Intelligent Temperature Transmitter
(Round Card) is a device used for the signal input of Resistance
Temperature Detector (RTD) and Thermocouple (TC) and 4-20mA analog
output of the two-wire system. It can be installed in the sensor
(Form B) through the HART protocol configuration.

Appearance Structure Diagram

Appearance Diagram

Installation Schematic Diagram

Installation Diagram

Configuration Schematic Diagram

Configuration Diagram

Wiring Diagram

Wiring Diagram

Technical Parameters

InputInput signalCold-junction compensationTemperature scopeCompensation precision
Resistance temperature detector (RTD), thermocouple (TC)-20 – 60 temperature scope
OutputOutput signalLoad resistanceOutput current of upper and lower limit overflow alarm
4-20mA, overlaid HART protocolRL(Ue-12)/0.021IH=21mA, IL=3.8mA
Power supplySupply voltage
DC12-40V
Other parametersTemperature driftResponse timeUsed environmental temperatureStorage temperatureInsulation strength (between input and output)Insulation resistance (between input and output)AseismicityInstallation angleInstallation areaElectromagnetic compatibility
0.0075%FS/°CReach to 90% of the final value for 700ms-40 – 80°C-40 – 100°C1500Vrms (1 min, without spark)100M (under the 500 VDC)4g/2 – 150HzUnlimitedB-type top cassette installationConform to GB/T18268 industrial equipment application
requirements (IEC 61326-1)

Product Usage Instructions

  1. Install the ZP-05 Isolated HART Intelligent Temperature
    Transmitter (Round Card) in the sensor (Form B) through the HART
    protocol configuration.
  2. Connect the input signal of Resistance Temperature Detector
    (RTD) or Thermocouple (TC) to the device.
  3. Connect the 4-20mA analog output of the two-wire system to the
    device.
  4. Connect the power supply of DC12-40V to the device.
  5. Configure the device based on the Configuration Schematic
    Diagram provided in the user manual.
  6. The device is now ready to use.

ZP-05 Isolated HART Intelligent Temperature Transmitter (Round Card) Operating Manual
Product Introduction ZP-05 isolated HART intelligent temperature transmitter (round card) is usedfor
the signal input of resistance temperature detector (RTD) and thermocouple (TC) and 4 – 20mA analog output of the two-wire system, and can be installed in the sensor(Form B) through the HART protocol configuration. 1. Appearance Structure Diagram
2. Installation Schematic Diagram
1

3. Configuration Schematic Diagram

4. Wiring Diagram

5. Technical Parameters
Input Input signal Cold-junction compensation

Resistance temperature detector (RTD), thermocouple (TC) -20 -60
2

temperature scope

Compensation precision

±1

Output

Output signal

4-20mA, overlaid HART protocol

Load resistance

RL(Ue-12)/0.021

Output current of upper and lower IH=21mA, IL=3.8mA

limit overflow alarm

Power supply

Supply voltage

DC12-40V

Other parameters

Temperature drift

0.0075%FS/

Response time

Reach to 90% of the final value for700ms

Used environmental temperature -40 – 80

Storage temperature

-40 – 100

Insulation strength (between input 1500Vrms (1 min, without spark)

and output)

Insulation resistance (between

100M(under the 500 VDC)

input and output)

Aseismicity

4g/2 – 150Hz

Installation angle

Unlimited

Installation area

B-type top cassette installation

Electromagnetic compatibility

Conform to GB/T18268 industrial equipment application

requirements (IEC 61326-1)

Input type and transmission accuracy:

Model

Type

Resistance temperature
detector

Pt100 Cu50

Measurement

Minimum

Conversion accuracy

scope

measurement scope

(larger value)

-200850

20

±0.1%range Or±0.2

-50150

20

±0.1%range Or±0.2

3

(RTD)

B

Thermocouple

E

(TC)

J

K

N

R

S

T

1001820 -1001000 -1001200 -1801372 -1801300 -501768 -501768 -200400

500 50 50 50 50 500 500 50

±0.1%range Or±1.5 ±0.1%range Or±0.5 ±0.1%range Or±0.5 ±0.1%range Or±0.5 ±0.1%range Or±0.5 ±0.1%range Or±1.5 ±0.1%range Or±1.5 ±0.1%range Or±0.5

Notes: 1. The above accuracy data was obtained by testing at an ambient temperature of 20 °C ± 2 °C. 2. The output precision “%” is relative to the set range. 3. The cold end compensation error needs to be added to the thermocouple measurement, and the internal cold end compensation error is ±1°C.