Ismacontrolli Sfar-s-8ao 8 Analog Outputs Expansion Module User Manual

Ismacontrolli Sfar-s-8ao 8 Analog Outputs Expansion Module User Manual

iSMACONTROLLI-LOGO

iSMACONTROLLI SfAR-S-8AO 8 Analog Outputs Expansion Module

iSMACONTROLLI-SfAR-S-8AO-8-Analog-Outputs-Expansion-Module-PRO

Introduction

Thank you for choosing our product. This manual will help you with proper handling and operating of the device. The information included in this manual have been prepared with utmost care by our professionals and serve as a description of the product without incurring any liability for the purposes of commercial law. This information does not discharge you from the liability of your own judgement and verification. We reserve the right to change product specifications without notice. Please read the instructions carefully and follow the recommendations concluded therein.

WARNING! Failure to follow instructions can result in equipment damage or impede the use of the hardware or software.

Revision History

Rev.DateDescription
3.225 May 2022Rebranded

Safety Rules

  • Improper wiring of the product can damage it and lead to other hazards. Make sure that the product has been correctly wired before turning the power on.
  • Before wiring or removing/mounting the product, make sure to turn the power off.
  • Failure to do so might cause an electric shock.
  • Do not touch electrically charged parts such as power terminals. Doing so might cause an electric shock.
  • Do not disassemble the product. Doing so might cause an electric shock or faulty operation.
  • Use the product only within the operating ranges recommended in the specification (temperature, humidity, voltage, shock, mounting direction, atmosphere, etc.). Failure to do so might cause a fire or faulty operation.
  • Firmly tighten the wires to the terminal. Failure to do so might cause a fire.
  • Avoid installing the product in close proximity to high-power electrical devices and cables, inductive loads, and switching devices. Proximity of such objects may cause an uncontrolled interference, resulting in an instable operation of the product.
  • Proper arrangement of the power and signal cabling affects the operation of the entire control system. Avoid laying the power and signal wiring in parallel cable trays. It can cause interferences in monitored and control signals.
  • It is recommended to power controllers/modules with AC/DC power suppliers. They provide better and more stable insulation for devices compared to AC/AC transformer systems, which transmit disturbances and transient phenomena like surges and bursts to devices. They also isolate products from inductive phenomena from other transformers and loads.
  • Power supply systems for the product should be protected by external devices limiting overvoltage and effects of lightning discharges.
  • Avoid powering the product and its controlled/monitored devices, especially high power and inductive loads, from a single power source. Powering devices from a single power source causes a risk of introducing disturbances from the loads to the control devices.
  • If an AC/AC transformer is used to supply control devices, it is strongly recommended to use a maximum 100 VA Class 2 transformer to avoid unwanted inductive effects, which are dangerous for devices.
  • Long monitoring and control lines may cause loops in connection with the shared power supply, causing disturbances in the operation of devices, including external communication. It is recommended to use galvanic separators.
  • To protect signal and communication lines against external electromagnetic interferences, use properly grounded shielded cables and ferrite beads.
  • Switching the digital output relays of large (exceeding specification) inductive loads can cause interference pulses to the electronics installed inside the product. Therefore, it is recommended to use external relays/contactors, etc. to switch such loads. The use of controllers with triac outputs also limits similar overvoltage phenomena.
  • Many cases of disturbances and overvoltage in control systems are generated by switched, inductive loads supplied by alternating mains voltage (AC 120/230 V). If they do not have appropriate built-in noise reduction circuits, it is recommended to use external circuits such as snubbers, varistors, or protection diodes to limit these effects.

Module Features

Purpose and Description of the Module
The SfAR-S-8AO module has a set of 8 analog outputs that can work as current outputs (0-20 mA or 4-20 mA) or as voltage outputs (0-10 V). Setting the output current or voltage mode is done via RS485 (Modbus protocol), so the module can be easily integrated with popular PLCs, HMI, or PC equipped with the appropriate adapter. The module is connected to the RS485 bus with a twisted-pair wire. Communication is via Modbus RTU or Modbus ASCII. The use of 32-bit ARM core processor provides fast processing and quick communication. The baud rate is configurable from 2400 to 115200. The module is designed for mounting on a DIN rail in accordance with DIN EN 5002. The module is equipped with a set of LEDs to indicate the status of inputs and outputs which is useful for diagnostic purposes and helping to find errors. Module configuration is done via USB by using a dedicated computer program. It also allows for changing the parameters using the Modbus protocol or set the Modbus address using the DIP switches under the front panel.

Technical Specification

Power SupplyVoltage10-38 V DC; 10-28 V AC
Power consumption (with active Modbus transmission, all outputs on)1.25 W at 24 V DC
1.5 VA at 24 V AC
IsolationIsolation between power supply and I/O1000 V DC
OutputsNo. of outputs8
Voltage output0 V do 10 V (resolution 1.5 mV)
Max. load current 0-10 V 5 mA
Accuracy ±2%
Current output0 mA – 20 mA (resolution 5 μA)
4 mA – 20 mA (value in ‰ – 1000 steps) (resolution 16 μA)
Max. resistance 500 ohm
Accuracy ±1%
Output resolution12-bit
DAC processing time16 ms/channel
TemperatureWork-10°C to +50°C (14°F to 122°F)
Storage-40°C to +85°C (-40°F to 185°F)
ConnectorsPower supply2 pins
Communication3 pins
Outputs2 x 10 pins
Quick connectorIDC10
Configurationmini USB
SizeHeight119.1 mm (4.689 in)
Length110.9 mm (4.366 in)
Width22.7 mm (0.894 in)
InterfaceRS485Up to 128 devices

Dimensions
The appearance and dimensions of the module are shown below. The module is mounted directly to the rail in the DIN industry standard. Power connectors, communication and IOs are at the bottom and top of the module. USB connector configuration and indicators located on the front of the module.iSMACONTROLLI-SfAR-S-8AO-8-Analog-Outputs-Expansion-Module-1

Communication

Grounding and Shielding
In most cases, I/O modules will be installed in an enclosure along with the other devices, which generate electromagnetic radiation. Relays, contactors, transformers, motor invertors, etc., are examples of such devices. Radiation can induce electrical noise into both power and signal lines, as well as direct radiation into the module. Whether or not the SfAR modules are immune to such effects, the interferences must be suppressed at their source if possible to ensure the proper functioning of the entire system. Appropriate grounding, shielding and other protective steps should be taken at the installation stage to prevent these effects. It is recommended to at least follow the rules below:

  • line power cables must be routed with spatial separation from signal and data transmission cables;
  • analog and digital signal cables should also be separated;
  • it is recommended to use shielded cables for analog signals, cable shields should not be interrupted by intermediate terminals;
  • the shielding should be earthed directly after the cable enters the cabinet.

It is recommended to install interference suppressors when switching inductive loads (e.g., coils of contactors, relays, solenoid valves). RC snubbers or varistors are suitable for AC voltage and freewheeling diodes for DC voltage loads. The suppressing elements must be connected as close to the coil as possible.

Network Termination
Transmission line effects often present problems for data communication networks. These problems include reflections and signal attenuation. To eliminate the presence of reflections of signal from the end of the cable, the cable must be terminated at both ends with a resistor across the line adequate to its characteristic impedance. Both ends must  be terminated since the propagation is bidirectional. In case of an RS485 twisted paircable, this termination is typically 120 Ω.

Setting Module Address in RS485 Modbus Network
The following table shows how to set switch to determine the address of the module. The module address is set with the switches in the range of 0 to 31. Addresses from 32 to 255 can be set via RS485 or USB.

AddrSW1SW2SW3SW4SW5
0OFFOFFOFFOFFOFF
1ONOFFOFFOFFOFF
2OFFONOFFOFFOFF
3ONONOFFOFFOFF
4OFFOFFONOFFOFF
AddrSW1SW2SW3SW4SW5
5ONOFFONOFFOFF
6OFFONONOFFOFF
7ONONONOFFOFF
8OFFOFFOFFONOFF
9ONOFFOFFONOFF
10OFFONOFFONOFF
11ONONOFFONOFF
12OFFOFFONONOFF
13ONOFFONONOFF
14OFFONONONOFF
15ONONONONOFF
16OFFOFFOFFOFFON
17ONOFFOFFOFFON
18OFFONOFFOFFON
19ONONOFFOFFON
20OFFOFFONOFFON
21ONOFFONOFFON
22OFFONONOFFON
23ONONONOFFON
24OFFOFFOFFONON
25ONOFFOFFONON
26OFFONOFFONON
27ONONOFFONON
28OFFOFFONONON
29ONOFFONONON
30OFFONONONON
AddrSW1SW2SW3SW4SW5
31ONONONONON

Types of Modbus Functions
There are 4 types of Modbus functions supported by the SfAR modules.

TypeBeginning AddressVariableAccessModbus Command
100001Digital OutputsBit Read/write1, 5, 15
210001Digital InputsBit Read2
330001Input RegistersRegistered Read3
440001Output RegistersRegistered Read/write4, 6, 16

Communication Settings
The data stored in the module’s memory is given in the 16-bit registers. The access to registers is via Modbus RTU or Modbus ASCII.

Default Settings
The default configuration can be restored with the DIP switch, SW6.

Baud Rate19200
ParityNo
Data Bits8
Stop Bits1
Reply Delay [ms]0
Modbus TypeRTU

Restoring Default Configuration
To restore the default configuration, follow the steps below:

  • turn the power off;
  • turn the switch SW6 on;
  • turn the power on;
  • when power and communication LED is lit, turn the switch SW6 off.

WARNING! After restoring the default configuration, all values stored in the registers will be cleared as well.

Configuration Registers

Modbus AddressDecimal AddressHex AddressNameValues
4000320x02Baud Rate0 – 2400

1 – 4800

2 – 9600

3 – 19200

4 – 38400

5 – 57600

6 – 115200

other – value * 10

4000540x04Parity0  – none

1  – odd

2  – even

3  – always 0

4  – always 1

4000430x03Stop Bits1 – one stop bit 2 – two stop bits
4000430x03Data Bits7  – 7 data bits

8  – 8 data bits

4000650x05Response DelayTime in ms
4000760x06Modbus Mode0  – RTU

1  – ASCII

Watchdog
This 16-bits register specifies the time in milliseconds to watchdog reset. If module does not receive any valid message within that time, all Digital and Analog Outputs will be set to the default state. This feature is useful if there is an interruption in data transmission and for security reasons. Output states must be set to the appropriate state in order to reassure the safety of persons or property. The default value is 0 milliseconds which means the watchdog function is disabled.

Indicators

iSMACONTROLLI-SfAR-S-8AO-8-Analog-Outputs-Expansion-Module-2

IndicatorDescription
Power SupplyThe LED indicates that the module is correctly powered
CommunicationThe LED lights up when the unit received the correct packet and sends the answer
Outputs StateThe LED indicates that the output is on

Connections

Block Diagram

iSMACONTROLLI-SfAR-S-8AO-8-Analog-Outputs-Expansion-Module-3

Power Supply Connection 

  • DC Power Connection:iSMACONTROLLI-SfAR-S-8AO-8-Analog-Outputs-Expansion-Module-4
  • AC Power Connection:iSMACONTROLLI-SfAR-S-8AO-8-Analog-Outputs-Expansion-Module-5

Connection of Analog Outputs

  • Connection of Current Output:iSMACONTROLLI-SfAR-S-8AO-8-Analog-Outputs-Expansion-Module-6
  • Connection of Voltage Output:iSMACONTROLLI-SfAR-S-8AO-8-Analog-Outputs-Expansion-Module-7

Quick Connector
The Quick Connector is a unique feature of modules that allows for quickly connecting a group of devices with a flat ribbon cable. Thanks to this solution, it is enough to connect power an RS485 communication to one of the devices in the group, and the others will be powered and communicated with ribbon cable. The Quick Connector is sufficient to connect up to 10 devices next to each other. It is important that the various types of modules in the SfAR-S family can be connected with the ribbon cable.iSMACONTROLLI-SfAR-S-8AO-8-Analog-Outputs-Expansion-Module-8

Setting Output Mode

To change the output mode from current to voltage, it is required to set appropriate values of Modbus registers (40069-40076) and change the position of a jumper inside the module, according to the following picture.iSMACONTROLLI-SfAR-S-8AO-8-Analog-Outputs-Expansion-Module-9

Opening the Case

iSMACONTROLLI-SfAR-S-8AO-8-Analog-Outputs-Expansion-Module-10

  • Remove the catch by pressing it and moving it towards the center of the case. Mind the spring located under the catch.
  • Separate parts of the case by gently tilting catches located as shown in the picture using a thin tool.

DIP Switch

iSMACONTROLLI-SfAR-S-8AO-8-Analog-Outputs-Expansion-Module-11

SwitchFunctionDescription
1Module address +1Setting module address from 0 to 31
2Module address +2
3Module address +4
4Module address +8
5Module address +16
6Restoring default settingsRestoring default settings

Module Registers

Registered Access

ModbusDecHexRegister NameAccessDescription
3000100x00Version/TypeReadVersion and type of the device
3000210x01SwitchesReadSwitches state
4000320x02Baud RateRead/writeRS485 baud rate
4000430x03Stop Bits & Data BitsRead/writeNo. of stop bits & data bits
4000540x04ParityRead/writeParity bit
4000650x05Response DelayRead/writeResponse delay in ms
4000760x06Modbus ModeRead/writeModbus Mode (ASCII or RTU)
4000980x08WatchdogRead/writeWatchdog
40033320x20Received Packets LSR (Least Significant Register)Read/writeNo. of received packets
40034330x21Received Packets MSR (Most Significant Register)Read/write
40035340x22Incorrect Packets LSRRead/writeNo. of received packets with error
40036350x23Incorrect Packets MSRRead/write
40037360x24Sent Packets LSRRead/writeNo. of sent packets
40038370x25Sent Packets MSRRead/write
30051500x32OutputsReadBit is set if value ≠ 0
40053520x34Analog output 1Read/writeValue of Analog Output:

in mV for voltage output (max 10240)

 

in μA for current output 0 – 20 mA (max 20480)

in ‰ for current output

4-20 mA (max 1000)

40054530x35Analog Output 2Read/write
40055540x36Analog Output 3Read/write
40056550x37Analog Output 4Read/write
40057560x38Analog Output 5Read/write
40058570x39Analog Output 6Read/write
40059580x3AAnalog Output 7Read/write
40060590x3BAnalog Output 8Read/write
ModbusDecHexRegister NameAccessDescription
40061600x3CDefault Output 1 ValueRead/writeDefault value of output set when power is on or when watchdog reset occurs
40062610x3DDefault Output 2 ValueRead/write
40063620x3EDefault Output 3 ValueRead/write
40064630x3FDefault Output 4 ValueRead/write
40065640x40Default Output 5 ValueRead/write
40066650x41Default Output 6 ValueRead/write
40067660x42Default Output 7 ValueRead/write
40068670x43Default Output 8 ValueRead/write
40069680x44Output 1 SettingRead/writeSetting of output mode:

0 – output disabled 1 – voltage output

2  – current output 0-20 mA

3  – current output 4-20 mA

Caution! For the change to take effect, you must also set the jumper inside the module.

40070690x45Output 2 SettingRead/write
40071700x46Output 3 SettingRead/write
40072710x47Output 4 SettingRead/write
40073720x48Output 5 SettingRead/write
40074730x49Output 6 SettingRead/write
40075740x4AOutput 7 SettingRead/write
40076750x4BOutput 8 SettingRead/write

Bit Access

Modbus AddressDec AddressHex AddressRegister NameAccessDescription
8018000x320Output 1ReadIf voltage or current is greater than 0 then according bit is set.
8028010x321Output 2Read
8038020x322Output 3Read
8048030x323Output 4Read
8058040x324Output 5Read
8068050x325Output 6Read
8078060x326Output 7Read
8088070x327Output 8Read

Configuration Software
The SfAR Configurator is the type of software, which is designed to set the communication module registers over Modbus network as well as to read and write the current value of other registers of the module. It is a convenient way to test the system as well as to observe real-time changes in the registers. Communication with the module is via the USB cable. The module does not require any drivers.

iSMACONTROLLI-SfAR-S-8AO-8-Analog-Outputs-Expansion-Module-12

The SfAR Configurator is a universal software, where it is possible to configure all available modules.

iSMACONTROLLI-SfAR-S-8AO-8-Analog-Outputs-Expansion-Module-13

www.ismacontrolli.com

DMP274en | 3rd Issue rev. 2 | 05/2022

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals