Ismacontrolli Sfar-1m-2di1ao Expansion Module 2 Digital Inputs 1 Analog Output User Manual

Ismacontrolli Sfar-1m-2di1ao Expansion Module 2 Digital Inputs 1 Analog Output User Manual

iSMACONTROLLI SfAR-1M-2DI1AO Expansion Module 2 Digital Inputs 1 Analog Output 

iSMACONTROLLI SfAR-1M-2DI1AO Expansion Module 2 Digital Inputs 1 Analog Output

Introduction

Thank you for choosing our product.

This manual will help you with proper handling and operating of the device.
The information included in this manual have been prepared with utmost care by our professionals and serve as a description of the product without incurring any liability for the purposes of commercial law. This information does not discharge you from the liability of your own judgement and verification.
We reserve the right to change product specifications without notice.
Please read the instructions carefully and follow the recommendations concluded therein.

WARNING! 

Failure to follow instructions can result in equipment damage or impede the use of the hardware or software.

Revision History
Rev.DateDescription
3.125 May 2022Rebranded

Safety Rules

  • Improper wiring of the product can damage it and lead to other hazards. Make sure that the product has been correctly wired before turning the power on.
  • Before wiring or removing/mounting the product, make sure to turn the power off. Failure to do so might cause an electric shock.
  • Do not touch electrically charged parts such as power terminals. Doing so might cause an electric shock.
  • Do not disassemble the product. Doing so might cause an electric shock or faulty
    operation.
  • Use the product only within the operating ranges recommended in the specification
    (temperature, humidity, voltage, shock, mounting direction, atmosphere, etc.). Failure to do so might cause a fire or faulty operation.
  • Firmly tighten the wires to the terminal. Failure to do so might cause a fire.
  • Avoid installing the product in close proximity to high-power electrical devices and
    cables, inductive loads, and switching devices. Proximity of such objects may cause an uncontrolled interference, resulting in an instable operation of the product.
  • Proper arrangement of the power and signal cabling affects the operation of the entire control system. Avoid laying the power and signal wiring in parallel cable trays. It can cause interferences in monitored and control signals.
  • It is recommended to power controllers/modules with AC/DC power suppliers. They provide better and more stable insulation for devices compared to AC/AC transformer systems, which transmit disturbances and transient phenomena like surges and bursts to devices. They also isolate products from inductive phenomena from other transformers and loads.
  • Power supply systems for the product should be protected by external devices limiting overvoltage and effects of lightning discharges.
  • Avoid powering the product and its controlled/monitored devices, especially high
    power and inductive loads, from a single power source. Powering devices from a single power source causes a risk of introducing disturbances from the loads to the control devices.
  • If an AC/AC transformer is used to supply control devices, it is strongly recommended to use a maximum 100 VA Class 2 transformer to avoid unwanted inductive effects, which are dangerous for devices.
  • Long monitoring and control lines may cause loops in connection with the shared power supply, causing disturbances in the operation of devices, including external
    communication. It is recommended to use galvanic separators.
  • To protect signal and communication lines against external electromagnetic interferences, use properly grounded shielded cables and ferrite beads.
  • Switching the digital output relays of large (exceeding specification) inductive loads can cause interference pulses to the electronics installed inside the product. Therefore, it is recommended to use external relays/contactors, etc. to switch such loads. The use of controllers with triac outputs also limits similar overvoltage phenomena.
  • Many cases of disturbances and overvoltage in control systems are generated by switched, inductive loads supplied by alternating mains voltage (AC 120/230 V). If they do not have appropriate built-in noise reduction circuits, it is recommended to use external circuits such as snubbers, varistors, or protection diodes to limit these effects.

Module Features

Purpose and Description of the Module

The SfAR-1M-2DI1AO module has 1 current analog output (0-20 mA or 4-20 mA) and 1 voltage analog output (0-10 V). Both outputs can be used at the same time. The module is equipped in two digital inputs. In addition, terminals IN1 and IN2 can be used to connect one encoder. Setting the output current or voltage value is done via RS485 (Modbus protocol), so the module can be easily integrated with popular PLCs, HMI, or PC equipped with an appropriate adapter.

This module is connected to the RS485 bus with a twisted-pair wire. Communication is via Modbus RTU or Modbus ASCII. The use of 32-bit ARM core processor provides fast processing and quick communication. The baud rate is configurable from 2400 to 115200.

The module is designed for mounting on a DIN rail in accordance with DIN EN 5002.
The module is equipped with a set of LEDs to indicate the status of inputs and outputs, which is useful for diagnostic purposes and helping to find errors.
Module configuration is done via USB by using a dedicated computer program. It also allows for changing the parameters using the Modbus protocol.

Technical Specification
Power SupplyVoltage10-38 V DC; 10-28 V AC
Power consumption (with active Modbus transmission and high state on all inputs)1 W at 24 V DC
2 VA at 24 V AC
IsolationIsolation between power supply and I/O1000 V DC
Analog OutputsNo. of outputs1
Voltage output0 V – 10 V (resolution 1.5 mV)
Max. load current 0-10 V 5 mA
Accuracy ± 2%
Current output0 mA – 20 mA (resolution 5 μA)
4 mA – 20 mA (value in ‰ – 1000 steps) (resolution 16 μA)
Max. resistance 500 ohm
Accuracy ±1%
Output resolution12 bits
DAC time processing16 ms/channel
Digital InputsNo. of inputs2
Voltage range0-36 V
Low state “0”0-3 V
High state “1”6-36 V
Input impedance4 kΩ
Isolation1500 Vrms
Input TypePNP or NPN
CountersNo. of counters2
Resolution32-bit
Frequency1 kHz (max.)
Impulse width500 μs (min.)
TemperatureWork-20 °C to +65°C
Storage-40 °C to +85°C
ConnectorsPower supply3 pin
Communication3 pin
Inputs2 x 3 pin
Configurationmini USB
SizeHeight90 mm
Length56.4 mm
Width17.5 mm
InterfaceRS485Up to 128 devices
Dimensions

The appearance and dimensions of the module are shown below. The module is mounted directly to the rail in the DIN industry standard. Power connectors, communication and IOs are at the bottom and top of the module. USB connector configuration and indicators located on the front of the module.

  • Figure 1. Dimensions
    Dimensions

Communication

Grounding and Shielding

In most cases, I/O modules will be installed in an enclosure along with the other devices, which generate electromagnetic radiation. Relays, contactors, transformers, motor invertors, etc., are examples of such devices. Radiation can induce electrical noise into both power and signal lines, as well as direct radiation into the module. Whether or not the SfAR modules are immune to such effects, the interferences must be suppressed at
their source if possible to ensure the proper functioning of the entire system. Appropriate grounding, shielding and other protective steps should be taken at the installation stage to prevent these effects. It is recommended to at least follow the rules below:

  • line power cables must be routed with spatial separation from signal and data transmission cables;
  • analog and digital signal cables should also be separated;
  • it is recommended to use shielded cables for analog signals, cable shields should not be interrupted by intermediate terminals;
  • the shielding should be earthed directly after the cable enters the cabinet.

It is recommended to install interference suppressors when switching inductive loads (e.g., coils of contactors, relays, solenoid valves). RC snubbers or varistors are suitable for AC voltage and freewheeling diodes for DC voltage loads. The suppressing elements must be connected as close to the coil as possible.

Network Termination

Transmission line effects often present problems for data communication networks. These problems include reflections and signal attenuation. To eliminate the presence of reflections of signal from the end of the cable, the cable must be terminated at both ends
with a resistor across the line adequate to its characteristic impedance. Both ends must be terminated since the propagation is bidirectional. In case of an RS485 twisted pair cable, this termination is typically 120 Ω.

Types of Modbus Functions

There are 4 types of Modbus functions supported by the SfAR modules.

Table 3. Types of Modbus functions supported by the module 

TypeBeginning AddressVariableAccessModbus Command
100001Digital OutputsBit Read/write1, 5, 15
210001Digital InputsBit Read2
330001Input RegistersRegistered Read3
440001Output RegistersRegistered Read/write4, 6, 16
Communication Settings

The data stored in the module’s memory is given in the 16-bit registers. The access to registers is via Modbus RTU or Modbus ASCII.

Default Settings

Table 4. Default settings 

Parameter NameValue
Address1
Baud rate19200
ParityNo
Data bits8
Stop bits1
Reply delay [ms]0
Modbus typeRTU

Configuration Registers

Table 5. Configuration registers

Modbus AddressDecimal AddressHex AddressNameValues
4000320x02Baud Rate0 – 2400
1 – 4800
2 – 9600
3 – 19200
4 – 38400
5 – 57600
6 – 115200
other – value * 10
4000540x04Parity0 – none
1 – odd
2 – even
3 – always 0
4 – always 1
4000430x03Stop Bits1 – one stop bit 2 – two stop bits
4000430x03Data Bits7 – 7 data bits

8 – 8 data bits

4000650x05Response DelayTime in ms
4000760x06Modbus Mode0 – RTU

1 – ASCII

Watchdog

This 16-bits register specifies the time in milliseconds to watchdog reset. If the module does not receive any valid message within that time, all digital and analog outputs will be set to the default state.
This feature is useful if there is an interruption in data transmission and for security reasons. Output states must be set to the appropriate state in order to reassure the safety of persons or property.
The default value is 0 milliseconds, which means the watchdog function is disabled.

Indicators

Figure 2. Indicators 

Indicators

Table 6. Description of indicators

IndicatorDescription
ONThe LED indicates that the module is correctly powered
TXThe LED lights up when the unit received the correct packet and sends the answer
DI1, DI2The LED indicates that on the input is high state
DO1, DO2The LED indicates that the output is on

Connections

Block Diagram

Figure 3. Block diagram 

Block Diagram

Power Supply Connection

DC Power Connection

  • Figure 4. DC power connection
    DC Power Connection

AC Power Connection 

  • Figure 5. AC power connection
    AC Power Connection 
Communication Bus Connection
  • Figure 6. Communication bus connection
    Communication Bus Connection
Connection of Outputs

Connection of Voltage Output 

  • Figure 7. Connection of voltage output
    Connection of Voltage Output 

Connection of Current Output 

  • Figure 8. Connection of current output
    Connection of Current Output 

Connection of Digital Inputs

  • Figure 9. Connection of digital inputs
    Connection of Digital Inputs

Modules Registers

Registered Access

Table 7. Registered access 

Modbus AddressDecimal AddressHex AddressRegister NameAccessDescription
3000100x00Version/TypeReadVersion and type of the device
3000210x01AddressReadModule address
4000320x02Baud RateRead/writeRS485 baud rate
4000430x03Stop Bits & Data BitsRead/writeNo. of stop bits & data bits
4000540x04ParityRead/writeParity bit
4000650x05Response DelayRead/writeResponse delay in ms
4000760x06Modbus ModeRead/writeModbus mode (ASCII or RTU)
4000980x08WatchdogRead/writeWatchdog
40013120x0CDefault Output StateRead/writeDefault output state (after power on or watchdog reset)
40033320x20Received Packets LSR (Least Significant Register)Read/writeNo. of received packets
40034330x21Received Packets MSR (Most Significant Register)Read/write
40035340x22Incorrect Packets LSRRead/writeNo. of received packets with error
40036350x23Incorrect Packets MSRRead/write
40037360x24Sent Packets LSRRead/writeNo. of sent packets
40038370x25Sent Packets MSRRead/write
30051500x32InputsReadInputs state
40052510x33OutputsRead/writeOutput state
40053520x34Counter 1 LSRRead/write32-bit counter 1
40054530x35Counter 1 MSRRead/write
40055540x36Counter 2 LSRRead/write32-bit counter 2
Modbus AddressDecimal AddressHex AddressRegister NameAccessDescription
40056550x37Counter 2 MSRRead/write 
40061600x3CCCounter 1 LSRRead/write32-bit value of captured counter 1
40062610x3DCCounter 1 MSRRead/write
40063620x3ECCounter 2 LSRRead/write32-bit value of captured counter 2
40064630x3FCCounter 2 MSRRead/write
40069680x44Counter Config 1Read/writeCounter configuration
+1 – time measurement (if 0 counting impulses)
+2 – autocatch counter
every 1 sec +4 – catch value when input low +8 – reset counter after catch +16 – reset counter if input low
+32 – encoder
40070690x45Counter Config 2Read/write
40073720x48CatchRead/writeCatch counter
40074730x49StatusRead/writeCaptured counter
Bit Access

Table 8. Bit access

Modbus AddressDecimal AddressHex AddressRegister NameAccessDescription
1931920x0C0Default state of output 1Read/writeDefault state of output 1
1941930x0C1Default state of output 2Read/writeDefault state of output 2
108018000x320Input 1ReadInput 1 state
108028010x321Input 2ReadInput 2 state
8178160x330Output 1Read/writeOutput 1 state
8188170x331Output 2Read/writeOutput 2 state
115311520x480Capture 1Read/writeCapture counter 1
115411530x481Capture 2Read/writeCapture counter 2
116911680x490Captured 1Read/writeCaptured value of counter 1
117011690x491Captured 2Read/writeCaptured value of counter 2

Configuration Software

The SfAR Configurator is the type of software, which is designed to set the communication module registers over Modbus network as well as to read and write the current value of other registers of the module. It is a convenient way to test the system as well as to observe real-time changes in the registers.
Communication with the module is via the USB cable. The module does not require any drivers.

Figure 10. PC connection 

PC connection 

The SfAR Configurator is a universal software, where it is possible to configure all available modules.

Figure 11. The SfAR Configurator

The SfAR Configurator

Customer Support

www.ismacontrolli.com
DMP266en | 3rd
Issue rev. 1 | 05/2022

iSMACONTROLLI  Logo

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals