Circutor Cem M-eth Communication Module For Cem Meters Instruction Manual

Circutor Cem M-eth Communication Module For Cem Meters Instruction Manual

Circutor logo

Circutor CEM M-ETH Communication Module for CEM Meters

Circutor CEM M-ETH Communication Module for CEM Meters featured

SAFETY PRECAUTIONS

Follow the warnings described in this manual with the symbols shown below.

DANGER
Warns of a risk, which could result in personal injury or material damage.
ATTENTION
Indicates that special attention should be paid to a specific point.

If you must handle the unit for its installation, start-up or maintenance, the following should be taken into consideration:

Incorrect handling or installation of the unit may result in injury to personnel as well as damage to the unit. In particular, handling with voltages applied may result in electric shock, which may cause death or serious injury to personnel. Defective installation or maintenance may also lead to the risk of fire. Read the manual carefully prior to connecting the unit. Follow all installation and maintenance in-structions throughout the unit’s working life. Pay special attention to the installation standards of the National Electrical Code.

Refer to the instruction manual before using the unit
In this manual, if the instructions marked with this symbol are not respected or carried out correctly, it can result in injury or damage to the unit and /or installations.

DISCLAIMER

CIRCUTOR SA reserves the right to make modifications to the device or the unit specifications set out in this instruction manual without prior notice.
CIRCUTOR SA on its web site, supplies its customers with the latest versions of the device specifica-tions and the most updated manuals.
CIRCUTOR, recommends using the original cables and accessories that are supplied with the device.

DateRevisionDescription
11/14M060B01-03-14AInitial Version
04/21M060B01-03-21ACircutor logo change
  1. VERIFICATION UPON RECEPTION
    Check the following points upon receiving the unit:
    a) The unit meets the specifications described in your order.
    b) The unit has not suffered any damage during transport.
    c) Perform an external visual inspection of the unit prior to switching it on.
    d) Check that it has been delivered with the following:
    – An installation guide,.
    If any problem is noticed upon reception, immediately contact the transport com-pany and/or CIRCUTOR’s after-sales service.
  2. PRODUCT DESCRIPTION

    The CEM M-ETH optical-electric interface converts the optical service port of any unit of the CEM range into an Ethernet port with MODBUS/TCP protocol.
    Circutor CEM M-ETH Communication Module for CEM Meters featured

The unit features: 
– 3 indicator LEDs: POWER, LINK and LINK/ACT.
The unit is installed on 2-step DIN rails, on the left of any unit of the CEM range.

UNIT INSTALLATION

PRELIMINARY RECOMMENDATIONS

In order to use the unit safely, it is critical that the individuals who handle it follow the safety measures set out in the standards of the country where it is being used, use the necessary personal protective equipment and pay attention to the various warnings indicated in this instruction manual.

The CEM M-ETH unit must be installed by authorised and qualified staff.
The power supply plug must be disconnected before handling, altering the connections or replacing the unit. It is dangerous to handle the unit while it is powered.
Also, it is critical to keep the cables in perfect condition in order to avoid accidents, personal injury and damage to installations.
The manufacturer of the unit is not responsible for any damage resulting from failure by the user or installer to observe the warnings and/or recommendations set out in this manual, nor for damage resulting from the use of non-original products or accessories or those made by other manufacturers.
If an anomaly or malfunction is detected in the unit, do not use the unit to take any measurements.
Inspect the work area before taking any measurements. Do not take measurements in dangerous ar-eas or where there is a risk of explosion.

Disconnect the unit from the power supply (unit and measuring system power supply) before maintaining, repairing or handling the unit’s connections.
Please contact the after-sales service if you suspect that there is an operational fault in the unit.

INSTALLATION

On the side of the unit are all of the indications adjusted to the CEI 62052-11 standard. The unit is installed on a DIN rail. Before connecting the unit, you must couple it to a CEM energy meter as shown in Figure 1 and Figure 2.

Circutor CEM M-ETH Communication Module for CEM Meters fig1

Terminals, opening covers or removing elements can expose parts that are hazardous to the touch while the unit is powered. Do not use the unit until it is fully installed.
The unit must be connected to a power circuit that is protected with gL fuses (IEC 269) or M fuses, with a rating of 0.5 to 2 A. It must be fitted with a circuit breaker switch or equivalent device for disconnect-ing the unit from the power supply mains.
The RCCB or equivalent device must be in the immediate vicinity of the unit and must be easily acces-sible.
The power circuit is connected with a cable with a section measuring up to 2.5 mm2.

The unit’s operating temperature is between -25ºC and +70ºC; always use connection cables that can withstand these temperatures.

UNIT TERMINALS

Table 2:List of CEM M-ETH terminals

 

Unit terminals

1: Auxiliary power supply.
2: Auxiliary power supply.
3: Ethernet.

Circutor CEM M-ETH Communication Module for CEM Meters fig2

CONNECTION DIAGRAM

The connection between the CEM M-ETH and the Ethernet network must be made with a twisted pair cable (100Base-TX: 100Mbit/s on two pairs of wires of Category 5 or higher). The segment length of the 100Base-T, 10BaseT and 1000Base-T cables is limited to 100 m.

Circutor CEM M-ETH Communication Module for CEM Meters fig3

OPERATION

The CEM M-ETH is designed to be used as a Ethernet port for any device in the CEM family, using the mechanical coupling next to the optical port.

OPERATING PRINCIPLE

The CEM M-ETH is an optional accessory for electrical energy meters from the CEM range that are mounted on DIN rails.
The CEM M-ETH provides CEM units with Ethernet communications with the MODBUS/TCP protocol.
Once the unit is coupled to the CEM energy meter (See “3.2.- INSTALLATION”) the LINK LED turns green to let the user know that the link has been made correctly.
From this point onward, the new CEM energy meter + CEM M-ETH assembly functions as a single device.
Circutor CEM M-ETH Communication Module for CEM Meters fig4

  • POWER LED: Indicates that the unit is connected to a power supply.
  • LINK LED: Indicates the status of the link with the CEM unit. (Table 3)

Table 3:LINK LED, colour codes

LINK LED
ColourStatus
Flashing redUnit not linked
Steady greenUnit linked

LED LINK/ACT, indicates the state of the Ethernet connection, Table 4.

Table 4: LED LINK/ACT

LED LINK/ ACT
ColourStatus
OnEthernet link
OffNo Ethernet link
FlashingActivity on this port

OPTICAL COMMUNICATIONS PORT

The unit has an optical serial communications port on its right side, in accordance with the UNE EN 62056-21:2003 standard, in order to communicate with other devices in the CEM family.

RS-485 COMMUNICATIONS

The MODBUS/TPC protocol is the MODBUS RTU protocol with a TCP interface that runs on Ethernet.
MODBUS/TCP uses TCP/IP and Ethernet to manage the data of MODBUS messages between compatible devices.
The MODBUS/TCP protocol embeds a standard MODBUS data frame in a TCP frame without the Modbus checksum, as shown in the diagram in the figure.

Circutor CEM M-ETH Communication Module for CEM Meters fig5

Table 5 shows the format of the MODBUS/TCP frame.

Table 5: MODBUS/TCP frame format

NameLengthFunction
Transaction identifier2For message synchronisation between the server and client.
Protocol identifier2Value 0 for MODBUS/TCP
Field length2Number of bytes remaining in the frame
Unit identifier1Peripheral number
Function code1Modbus function number
Data bytesnResponse or command data

The MODBUS functions implemented in the unit are:

Functions 03 and 04. Reading of logs. Function 10. Writing of multiple logs.

VARIABLES MODBUS
All MODBUS map addresses are hexadecimal.

Configuration variables
The Read and Write functions are implemented for these variables.

Table 6:Modbus configuration variables CEM M-RS485. 

DescriptionAddressSizeValid data rangeDefault value
Impulse output type0x008016 bits0: Active energy, 1: Reactive energy0
Impulse output weight0x008116 bitsWh/impulse 0 … 99999
Cost per kWh0x00B032 bits0.0000…. 9999.9999 with 4 decimal places of

resolution

KgCO20x00B232 bits0.0000…. 9.0000 with 4 decimal places of

resolution

Note: Some MODBUS variables may not be available depending on the CEM energy meter coupled to the CEM M-ETH. See “4.4.2.7.- Available addresses by unit”

Energy
The Read function is implemented for these variables.

DescriptionAddressSizeUnits
Total values
Imported active energy0x000032 bitsWh
Exported active energy0x000232 bitsWh
Q1 reactive energy0x000432 bitsvarh
Q2 reactive energy0x000632 bitsvarh
Q3 reactive energy0x000832 bitsvarh
Q4 reactive energy0x000A32 bitsvarh
Partial values
Partial imported active energy0x003032 bitsWh
Partial exported active energy0x003232 bitsWh
Q1 partial reactive energy0x003432 bitsvarh
Q2 partial reactive energy0x003632 bitsvarh
Q3 partial reactive energy0x003832 bitsvarh
Q4 partial reactive energy0x003A32 bitsvarh

Note: Some MODBUS variables may not be available depending on the CEM energy meter coupled to the CEM M-ETH. See “4.4.2.7.- Available addresses by unit”

Operating time, cost and KgCO2 atmospheric emissions
The Read function is implemented for these variables.
Table 8: Modbus variables: Operating time, costs and KgCO2

DescriptionAddressSizeUnits
Cost of the partial consumption0x00C032 bits
KgCO2 atmospheric emissions of the partial consumption0x00C232 bits
Hours of partial operation0x00C432 bits( 1 decimal place)
Hours of total operation0x00C632 bits( 1 decimal place)

Note: Some MODBUS variables may not be available depending on the CEM energy meter coupled to the CEM M-ETH. See “4.4.2.7.- Available addresses by unit”

Instantaneous values
The Read function is implemented for these variables.
Table 9: Modbus variables: Instantaneous values.

DescriptionAddressSizeUnits
Phase 1 voltage0x073232 bitsV (1 primary decimal place)
Phase 2 voltage0x073432 bitsV (1 primary decimal place)
Phase 3 voltage0x073632 bitsV (1 primary decimal place)
Phase 1 current0x073832 bitsA (2 primary decimal places)
Phase 2 current0x073A32 bitsA (2 primary decimal places)
Phase 3 current0x073C32 bitsA (2 primary decimal places)
Phase 1 cos φ0x073E32 bits2 decimal places

Table 9 (Continuation): Modbus variables: Instantaneous values

DescriptionAddressSizeUnits
Phase 2 cos φ0x074032 bits2 decimal places
Phase 3 cos φ0x074232 bits2 decimal places
Phase 1 active power0x074632 bitsW
Phase 2 active power0x074832 bitsW
Phase 3 active power0x074A32 bitsW
Total active power0x074C32 bitsW
Phase 1 reactive power0x074E32 bitsvar
Phase 2 reactive power0x075032 bitsvar
Phase 3 reactive power0x075232 bitsvar
Total reactive power0x075432 bitsvar
Phase 1 apparent power0x075632 bitsVA
Phase 2 apparent power0x075832 bitsVA
Phase 3 apparent power0x075A32 bitsVA
Total apparent power0x075C32 bitsVA

Note: Some MODBUS variables may not be available depending on the CEM energy meter coupled to the CEM M-ETH. See “4.4.2.7.- Available addresses by unit”

Other parameters
The Read function is implemented for these variables.
Table 10: Modbus variables: Other parameters.

DescriptionAddressSizeUnits
Energy meter model1)0xF0106×16 bits12 bytes in ASCII format
Serial no0x271032 bits
Transformation ratios
Voltage primary0x044C32 bitsV (1 decimal place)
Voltage secondary0x044E32 bitsV (1 decimal place)
Current primary0x045032 bitsA (1 decimal place)
Current secondary0x045232 bitsA (1 decimal place)
Energy meter firmware version
Higher firmware version0x005016 bits
Lower firmware version0x005116 bits
Revised firmware version0x005216 bits
Communications module firmware version
Higher firmware version0x057816 bits
Lower firmware version0x057916 bits
Revised firmware version0x057A16 bits

Note: Some MODBUS variables may not be available depending on the CEM energy meter coupled to the CEM M-ETH. See “4.4.2.7.- Available addresses by unit”
(1) Energy meter model description table, Table 11.

Options C10C20C30bytes in ASCII format
Connection mode2 wiresü  2
4 wires üü4
 

Accuracy

Class B active / Does not measure reactive energyüüü10
Class B active / Class 2.0 reactiveüüü12
 

 

 

 

Measurement voltage

1×230ü  E
1×127ü  B
3×127/220 … 3×230/400 V ü U
3×127/220 V üüN
3×230/400 V üüQ
3×57/100 … 3×230/400 V  üV
3×57/100 V  üL
3×63.5/110 V  üM
 

 

 

Current measurement

Shunt 10(60) Aü  S4
Shunt 5(65) Aü  S7
Direct 10(60)A ü D4
Direct 5(65)A ü D7
Transformer 5(10) A  üT5
Transformer 5(6) A  üT6
 

Frequency

50HzüüüA
60 HzüüüB
Automatic (50/60Hz)üüüC
CommunicationsWithout communicationsüüü0
Side optical service portüüü1
ExpansionWithout inputs/outputsüüü0
Input/Output (Optocoupler)üüü1
ModelBox for assembly on DIN railüüüE
 

Number of quadrants

2 quadrantsüüü0
4 quadrantsüüü1
Storage in both directionsüüü2
Additional featuresNo special featuresüüü0

Partial energy reset
The 0x05 function is implemented for this variable.

DescriptionAddressActivation
Partial energy reset0x08000xFF00

Table 13: Modbus variables: Available addresses by unit.

AddressC10C20C30Description
0x03E8üüüModbus Address
0x03E9üüüTransmission speed
0x03EAüüüCommunications configuration
0x0080üüüImpulse output type
0x0081üüüImpulse output weight
0x00B0üüüCost per kWh
0x00B2üüüKgCO2
0x0000üüüImported active energy
0x0002üüüExported active energy
0x0004üüüQ1 reactive energy
0x0006üüüQ2 reactive energy
0x0008üüüQ3 reactive energy
0x000AüüüQ4 Reactive energy
0x0030üüüPartial imported active energy
0x0032üüüPartial exported active energy
0x0034üüüQ1 partial reactive energy
0x0036üüüQ2 partial reactive energy
0x0038üüüQ3 partial reactive energy
0x003AüüüQ4 partial reactive energy
0x00C0üüüCost of the partial consumption
0x00C2üüüKgCO2 atmospheric emissions of the partial consumption
0x00C4üüüPartial operating time
0x00C6üüüTotal operating time
0x0732üüüPhase 1 voltage
0x0734 üüPhase 2 voltage
0x0736 üüPhase 3 voltage
0x0738üüüPhase 1 current
0x073A üüPhase 2 current
0x073C üüPhase 3 current
0x073EüüüPhase 1 cos φ
0x0740 üüPhase 2 cos φ
0x0742 üüPhase 3 cos φ
0x0746üüüPhase 1 active power
0x0748 üüPhase 2 active power
0x074A üüPhase 3 active power
0x074CüüüTotal active power
0x074EüüüPhase 1 reactive power
0x0750 üüPhase 2 reactive power
0x0752 üüPhase 3 reactive power
0x0754üüüTotal reactive power
0x0756üüüPhase 1 apparent power
0x0758 üüPhase 2 apparent power
0x075A üüPhase 3 apparent power
AddressC10C20C30Description
0x075CüüüTotal apparent power
0xF010üüüEnergy meter model
0x2710üüüSerial no.
0x044C  üVoltage primary
0x044E  üVoltage secondary
0x0450  üCurrent primary
0x0452  üCurrent secondary
0x0050üüüHigher firmware version
0x0051üüüLower firmware version
0x0052üüüRevised firmware version

TECHNICAL FEATURES

Power supply
Rated voltage230 V~ ± 20%
Maximum power consumption4 VA
Frequency50/60 Hz with no differentiation
Insulation
AC voltage4kV RMS 50Hz during 1 minute
Overimpulse
12/50ms 0source impedance6 kV at 60º and 240º, with positive and negative polarization
Memory
Setup, events, load curveNon-volatile EEPROM memory
User interface
LED3 LEDs (POWER – LINK – LINL/ACT)
Communication
Communications protocolModbus/TCP

 

Environmental features
Operating temperature-25ºC… +70ºC
Storage temperature-35ºC… +80ºC
Relative humidity (non-condensing)5 … 95%
Maximum altitude2,000 m
Mechanical features
Dimensions (mm)Figure 7
EnclosureABS + V0 polycarbonate
Weight115 gr
Protection degreeIP 51 installed

IP 40 in the terminal area

 

Standards
Safety requirements for electrical units for measurement, control and laborato- ry use� Part 1: General requirements�EN 61010-1: 2010
Electromagnetic compatibility (CEM) Part 6-2: Generic standards Immunity for industrial environmentsEN 61000-6-2: 2005
Electromagnetic  compatibility  (CEM)� Part  6-3: Generic  standards� Emission standard for residential, commercial and light industry environments�EN 61000-6-3: 2007

Circutor CEM M-ETH Communication Module for CEM Meters fig6

MAINTENANCE AND TECHNICAL SERVICE

The unit does not need any type of maintenance.
In the case of any query in relation to device operation or malfunction, please contact the CIRCUTOR, SA Technical Support Service.
Technical Assistance Service
Vial Sant Jordi, s/n, 08232 – Viladecavalls (Barcelona)
Tel: 902 449 459 ( España) / +34 937 452 919 (outside of Spain)
email: [email protected]

GUARANTEE

CIRCUTOR guarantees its products against any manufacturing defect for two years after the delivery of the units.
CIRCUTOR will repair or replace any defective factory product returned during the guarantee period.

  • No returns will be accepted and no unit will be repaired or replaced if it is not accom-panied by a report indicating the defect detected or the reason for the return.
  • The guarantee will be void if the units has been improperly used or the storage, instal-lation and maintenance instructions listed in this manual have not been followed. “Im-proper usage” is defined as any operating or storage condition contrary to the national electrical code or that surpasses the limits indicated in the technical and environmental features of this manual.
  • CIRCUTOR accepts no liability due to the possible damage to the unit or other parts of the installation, nor will it cover any possible sanctions derived from a possible failure, improper installation or “improper usage” of the unit. Consequently, this guarantee does not apply to failures occurring in the following cases:
    • Overvoltages and/or electrical disturbances in the supply;
    • Water, if the product does not have the appropriate IP classification;
    • Poor ventilation and/or excessive temperatures;
    • Improper installation and/or lack of maintenance;
    • Buyer repairs or modifications without the manufacturer’s authorisation.

 

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals