Modine Csd Ceiling Cassette Ductless Mini-split And Chilled Water Instruction Manual

CSD Ceiling Cassette Ductless Mini-Split and Chilled Water

Product Information

The Ceiling Cassette is a versatile cooling and heating unit
that can effectively create independent temperature zones in
different areas. It offers thermostatic control of operations,
allowing conditions to be adjusted according to specific
requirements or activities. Optional fresh air intakes are
available for ventilation purposes. The Cassette is available in
three models: DX cooling, heat pump, or chilled water cooling.
Heating options include electric heat or hot water, depending on
the model. The design of the Cassette incorporates noise reduction
techniques such as low blower speeds, rigid panel and cabinet
construction, and sound-absorbent cabinet insulation. It is
available with electromechanical or micro-processor based controls,
including an infrared transmitter for maintaining room conditions
at a user-defined setpoint. The Cassette can also be connected to a
Building Management System using Carel microprocessor controls and
network cards.

Product Usage Instructions

To use the Ceiling Cassette, follow these steps:

  1. Identify the model of your Ceiling Cassette using the model
    nomenclature provided in the user manual.
  2. Determine the unit configuration (UC) of your Cassette: SD for
    DX cooling, SH for HP heating & cooling, or CW for chilled
    water.
  3. Check the nominal capacity (MBH) of your Cassette based on the
    desired cooling or heating power: 08 = 8,000 Btu/Hr, 12 = 12,000
    Btu/Hr, 18 = 18,000 Btu/Hr, 20 = 20,000 Btu/Hr, 24 = 24,000 Btu/Hr,
    30 = 30,000 Btu/Hr, 33 = 33,000 Btu/Hr, 36 = 36,000 Btu/Hr, or 42 =
    42,000 Btu/Hr.
  4. Confirm the supply voltage (SV) required for your Cassette: A =
    115/60/1, B = 208/60/1, C = 230/60/1, H = 277/60/1, J = 110/50/1,
    or K = 220/50/1.
  5. Refer to the control code (CC) to determine the specific
    control options available for your Cassette.
  6. Install the Cassette according to the provided installation
    instructions, ensuring proper electrical and water connections if
    applicable.
  7. Set the desired temperature and operating mode using the
    controls on the Cassette or through a connected Building Management
    System.
  8. Monitor the performance of the Cassette and adjust settings as
    needed to maintain the desired temperature and comfort level.

Note: As Modine Manufacturing Company may make design and
specification changes without notice, always refer to the latest
user manual or product documentation for accurate information and
instructions.

Technical Manual
Ceiling Cassette
Ductless Mini-Split and Chilled Water
Models CSD, CSH and CCW
by
AIR 8-105.11 · June, 2023 8-105.11 · June, 2023

OVERVIEW / TABLE OF CONTENTS

Ceiling Cassette

Overview
The ceiling mounted Cassette units effectively make each area served an independent controlled temperature zone. Through thermostatic control of operations, conditions can be varied to suit diverse requirements or activities. Optional fresh air intakes are available to provide outside air for ventilation into the space.
Cassettes are available in a choice of three models: DX cooling, heat pump, or chilled water cooling. Optional heating can be provided as electric heat or hot water, depending on the model. This versatility eliminates compromising architecture or design. Important cost savings are often realized during building modernizations, as existing piping and/or wiring can frequently be reused.
Design techniques are incorporated in every Airedale by Modine Cassette to reduce noise levels to a minimum. These techniques include low blower speeds, rigid panel and cabinet construction, and sound-absorbent cabinet insulation.
For individual comfort, Cassettes are available with electromechanical or micro-processor based controls. The microprocessor controller includes an infrared transmitter which enables room conditions to be maintained at a user defined setpoint. The Cassettes are also available with Carel microprocessor controls and network cards to allow units to be connected to a Building Management System.

Table of Contents
Model Identification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-5 Accessories – Field Installed. . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-10 Unit Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-15 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16-17

The Modine Breeze® AccuSpec is the fastest way to generate performance data based on actual job conditions. The Breeze® AccuSpec program is a web-based sizing and selection program. The program provides a series of step-by-step questions that allow for the easy configuration of Airedale by Modine products. After a model has been configured, the program can generate Submittal Schedules, Submittal Data (including performance and dimensional drawings), and Specifications.

As Modine Manufacturing Company has a continuous product improvement program, it reserves the right to change design and specifications without notice.

2

AIR 8-105.11

MODEL IDENTIFICATION

Model Nomenclature

1

2,3

4,5

6

7

PT

UC

MBH

SV

G

1 ­ Product Type (PT) C ­ Ceiling Cassette

2,3 ­ Unit Configuration (UC) SD ­ DX Cooling
SH ­ HP Heating and Cooling
CW ­ Chilled Water

4,5 ­ Nominal Capacity (MBH) 08 ­ 8,000 Btu/Hr 12 ­ 12,000 Btu/Hr 18 ­ 18,000 Btu/Hr 20 ­ 20,000 Btu/HR 24 ­ 24,000 Btu/Hr 30 ­ 30,000 Btu/Hr 33 ­ 33,000 Btu/Hr 36 ­ 36,000 Btu/Hr 42 ­ 42,000 Btu/Hr

6 ­ Supply Voltage (SV) A ­ 115V/60Hz/1ph B ­ 208V/60Hz/1ph C ­ 230V/60Hz/1ph H ­ 277V/60Hz/1ph J ­ 110V/50Hz/1ph K ­ 220V/50Hz/1ph

7 ­ Generation (G) A ­ Current Design

Ceiling Cassette

8

9

10

11

12

13

C

HO

FL

FP

PO

CC

8 ­ Control Code (C) C ­ Modine Controls System E ­ Electro-Mechanical Controls M ­ Microprocessor Controls (Infrared Remote Control)

9 ­ Heating Option (HO) N ­ None A ­ Electric Heat B ­ Hot Water Heating Coil ­ 4-pipe C ­ Hot Water Heating ­ 2 Pipe (Uses CW Coil)

10 ­ Filters (FL) A ­ 60-80% Arrestance (Standard) B ­ MERV 10

11 ­ Heat Freeze Protection (FP) N ­ None F ­ Hot Water Coil Freeze Protection

12 ­ Power Option (PO) N ­ None D ­ Cassette Power Disconnect Switch

13 ­ Control Communication Option (CC) N ­ None B ­ BACnet IP Compatible Network Card M ­ BACnet MS/TP Compatible Network Card

AIR 8-105.11

3

STANDARD FEATURES

Ceiling Cassette

General Description ­ Ceiling Cassette Unit
Digit 2,3: Unit Configuration (UC)
SD = DX Cooling All direct expansion units include a factory installed thermal expansion valve and utilize large surface area evaporator coils ideally positioned to optimize heat transfer and airflow. Each evaporator is manufactured from refrigeration quality copper tubes with mechanically bonded aluminum fins.
SH = HP Heating & Cooling All direct expansion units include a factory installed thermal expansion valve and utilize large surface area evaporator coils ideally positioned to optimize heat transfer and airflow. Each evaporator is manufactured from refrigeration quality copper tubes with mechanically bonded aluminum fins.
CW = Chilled Water All chilled water units utilize large surface area coils positioned to optimize heat transfer and airflow. Each coil is manufactured from refrigeration quality copper tubes with mechanically bonded aluminum fins and are circuited from headers to ensure low water pressure drops.
Digit 4,5: Nominal Capacity (MBH)
08 = 8,000 Btu/Hr 12 = 12,000 Btu/Hr 18 = 18,000 Btu/Hr 20 = 20,000 Btu/Hr 24 = 24,000 Btu/Hr 30 = 30,000 Btu/Hr 33 = 33,000 Btu/Hr 36 = 36,000 Btu/Hr 42 = 42,000 Btu/Hr
Digit 6: Supply Voltage (SV)
A = 115/60/1 B = 208/60/1 C = 230/60/1 H = 277/60/1 J = 110/50/1 K = 220/50/1
Digit 8: Control Code (CC)
C = Modine Controls System The unit shall be fitted with a programmable microprocessor controller designed to operate the unit according to preengineered control strategies. The Carel controller requires a wall sensor, wall stat or network interface card.

M = Microprocessor Controls A custom designed microprocessor is fitted to the cassette to enable room conditions to be maintained at a user defined setpoint. Communication to the controller is by a hand held infrared transmitter.
The microprocessor monitors indoor coil temperature and return air temperature. The receiver contains a self diagnostic feature. When a low indoor coil temperature is detected the cooling action is stopped. If a sensor fails then an alarm is displayed on the fascia-mounted receiver.
The infrared transmitter is used to switch the unit ON/OFF, change temperature settings, fan speed, operating mode, and to toggle the motorized air sweep (where fitted). The microprocessor also has a built-in clock with a timer. The timer can be activated to provide ON/OFF unit operation. Note this is not a night set back or occupied/unoccupied control function.
Figure 4.1 – Microprocessor Remote

E = Electro-Mechanical Controls The unit shall be factory wired with an electro-mechanical control system that includes the necessary relays and safety switches for proper unit operation. Terminal strip provide at the unit for the wiring of a 24V wall mounted thermostat required for unit operation.
The unit shall include terminals for remote start/stop of the unit. The unit is enabled when contact between the terminals is closed.

4

AIR 8-105.11

STANDARD FEATURES

Ceiling Cassette

Digit 9: Heating Option (HO)
N = None
A = Electric Heat Electric heating elements will be factory fitted to the unit. Elements are manufactured for maximum surface area and lower working temperature for improved reliability. Thermal cut out protection switches are fitted to the electric heat circuit to protect against overheating.
B = Hot Water Heating Coil – 4 Pipe A hot water heating coil will be factory fitted (depending on unit size) in addition to the standard DX or chilled water coil to provide heating. The coil is manufactured from refrigeration quality copper tubes with mechanically bonded aluminum fins.
C = Hot Water Heating – 2 Pipe (Uses CW Coil) A common chilled water/hot water coil for 2 pipe systems will provide cooling or heating, depending on mode of operation. The coil is manufactured from refrigeration quality copper tubes with mechanically bonded aluminum fins.
Digit 10: Filtration (F)
A = 60-80% Arrestance (Standard) Wire framed filters are fitted. These are reusable and may be vacuum cleaned.
B = MERV 10 MERV 10, 1″ thick, radial pleated disposable cotton and synthetic blend filters. Minimum Efficiency Reporting Value of MERV 10 per ASHRAE standard 52.2.
Digit 11: Heat Freeze Protection (FP)
N = None
F = Hot Water Coil Freeze Protection The unit shall be fitted with a freeze protection sensor to prevent freezing of the hot water coil assembly. When the sensor detects a conditions that can result in a freeze condition, it will open the flow control valve and prevent the unit fan(s) from running.

STANDARD FEATURES
Construction Cases are manufactured from lightweight galvanized sheet steel with integral fan mounting rails for added strength. Fire resistant foam insulation is fitted internally to provide both thermal and acoustic insulation.
Fan Backward curved centrifugal fans are statically and dynamically balanced for quiet operation. Fan impellers are made from either aluminum or fire retardant plastic for lightweight and corrosion resistant operation. Fans are driven by an enclosed multi-speed external rotor motor allowing good heat dissipation and an increased motor efficiency. Fans come complete with thermal overload protection and sealed-for-life lubricated bearings.
Condensate Pump A condensate pump and check valve are fitted to carry condensate water out of the unit and stop water from flowing back into the condensate tray. The pump is fixed to a mounting bracket which can be withdrawn from the side of the chassis and incorporates an inspection hole to allow a visual check of the pump during operation. A float switch is fitted to stop the cooling action should the pump become blocked or fail.
Air Vanes Air outlet vanes are designed to prevent condensation from forming. Vanes are manually adjustable on model sizes 08 and 12. The vanes on all other model sizes are driven by an electric motor. Motorized air vanes can be set to auto sweep or can be stopped in a fixed position. Polystyrene blanking pieces are supplied with Cassette packing so that up to two fascia discharge slots can be blanked off.
Alarm Status Relay The unit shall include a relay for unit failure notification. In addition, a normally open contact is available for field connection.

Digit 12: Power Option (PO)
N = None

D = Cassette Power Disconnect Switch The unit shall be fitted with a power disconnect switch located on the control panel, sized for the full load amperage of the unit to enable the unit to be disconnected from the power supply prior to any maintenance.

Digit 13: Control Communication Option (CC)
N = None

B = BACnet IP Compatible Network Card The Carel microprocessor controller shall come equipped with a plug-in card allowing for complete compatibility with a BACnet IP building management system.

M = BACnet MS/TP Compatible Network Card The Carel microprocessor controller shall come equipped with a plug-in card allowing for complete compatibility with a BACnet MS/TP building management system.

AIR 8-105.11

5

ACCESSORIES – FIELD INSTALLED

Ceiling Cassette

FIELD INSTALLED ACCESSORIES
Fresh Air Duct Collars The Cassette chassis features two or three fresh air knockouts depending on model size. Any number can be removed to allow fresh air to enter the unit. A duct collar is available for fastening to the unit to allow connection of a 3″ flexible duct. A replacement filter is included with fresh air duct collars to aid in balancing the amount of return air and fresh air delivered to the unit’s coil.
Supply Air Duct Collars A limited amount of conditioned air can be ducted from the unit by removing the branch duct knockouts (up to 2 per unit) and connecting flexible ducting. For model sizes 08 and 12, there are a total of three knockouts positioned on three of the unit sides (one per side). For all other model sizes, a total of four knockouts are available and are arranged in pairs along two of the unit sides (two per side). A duct collar is available to allow connection of a 5″ or 6″ (depending on units size) flexible duct to the Cassette.
On model sizes 08 and 12, it is recommended that only one of the three branch duct knockouts are utilized, due to the small capacity of the unit.
Shroud A sheet metal shroud is available to cover the unit housing when the unit is not mounted in a drop ceiling. Painted Sky White with hammertone finish.
Figure 6.1 – Duct Shroud

Control Valves For control of chilled water or hot water flow, a three-way, threeport diverting type valve or a two-way, two-port control valve is supplied loose for on site installation. Actuation is via a 24V signal from the unit’s electrical panel.
· Two Position Spring Return Control Valves · Two Position Spring Return Control Valves with Two Shut-
Off Valves (package)
On a four pipe system where two-way valves are specified, the chilled water valve will be a normally closed type. The hot water valve will be a normally open type. Where three-way valves are specified, the same type valve will be supplied for both coils and should be installed normally closed to the coil in the case of the chilled water coil and normally open to the coil in the case of the hot water coil.
On a two pipe changeover system where a two-way valve is specified, a normally open valve is supplied. Where a threeway valve is specified, this should be installed normally open to the coil. In both cases, a pipe mounted changeover thermostat is factory supplied and shipped loose for field installation. The changeover thermostat is used to monitor water supply temperature and allow action of the valve accordingly.
Condensing Unit (for DX or Heat Pump units) Refer to Breeze submittal for details.
Low Ambient Kit (Use with Condensing Units) Fan speed control for compressor operation down to 0°F outside temperature.

6

AIR 8-105.11

PERFORMANCE DATA

Ceiling Cassette

Table 7.1 – Cooling Performance – DX Cooling Only and Heat Pump Units

Model

Entering Air DB ºF @
50% RH

High

Total Cooling Sensible Cooling

BTU/h

BTU/h

Fan Speed

Medium

Total Cooling Sensible Cooling

BTU/h

BTU/h

72

16,500

14,400

16,300

13,900

CSD/CSH 18

75

17,500

14,900

17,200

14,400

80

19,200

15,600

18,900

15,100

72

20,000

16,800

19,600

16,100

CSD/CSH 24

75

21,000

17,300

20,600

16,500

80

23,000

18,000

22,600

17,200

72

27,600

25,000

27,000

23,600

CSD/CSH 30

75

29,000

25,800

27,600

25,000

80

31,400

27,000

31,000

25,400

72

33,400

28,400

33,000

27,600

CSD/CSH 36

75

35,000

29,200

34,600

28,200

80

38,200

30,400

37,800

29,400

72

37,800

31,600

37,200

30,200

CSD/CSH 42

75

39,500

32,400

39,000

31,000

80

42,500

33,400

42,000

32,000

j Cooling capacities are based on 95/75°F DB/WB Outdoor Ambient

Low

Total Cooling Sensible Cooling

BTU/h

BTU/h

15,800

13,100

16,800

13,500

18,500

14,200

19,300

15,600

20,400

16,000

22,200

16,700

26,400

22,200

27,800

22,800

30,200

23,800

32,200

26,200

34,000

26,800

37,000

27,800

36,800

29,400

38,500

30,000

41,500

31,000

Table 7.2 – Heating Performance – Heat Pump Units

Model

Entering Air DB ºF

High

Total Heating (BTU/h)

Fan Speed Medium
Total Heating (BTU/h)

50

19,100

18,900

CSH 18

60

17,800

17,600

70

16,400

16,200

50

24,400

24,000

CSH 24

60

22,800

22,600

70

21,400

21,000

50

30,400

30,200

CSH 30

60

29,000

28,800

70

27,400

27,200

50

35,800

35,600

CSH 36

60

34,200

33,800

70

32,400

32,000

50

39,500

39,000

CSH 42

60

38,200

37,800

70

37,200

36,800

j Heating capacities are based on 47/43°F DB/WB Outdoor Ambient

Low Total Heating (BTU/h)
18,600 17,200 16,000 23,800 22,200 20,800 29,800 28,200 26,800 35,000 33,400 31,600 39,000 37,800 36,600

AIR 8-105.11

7

PERFORMANCE DATA

Ceiling Cassette

Table 8.1 – Cooling Performance – Chilled Water Units

Model

Filter

Entering Air DB °F @
50% RH

72

STD.

75

80

CCW 08

72

MERV 10

75

80

72

STD.

75

80

CCW 12

72

MERV 10

75

80

72

STD.

75

80

CCW 18

72

MERV 10

75

80

72

STD.

75

80

CCW 20

72

MERV 10

75

80

72

STD.

75

80

CCW 33

72

MERV 10

75

80

72

STD.

75

80

CCW 36

72

MERV 10

75

80

TC BTUH 5,900 7,300 9,900 4,000 5,000 6,800 8,800 10,900 14,600 5,300 6,600 8,900 14,200 17,700 23,900 12,900 16,000 21,600 14,500 18,100 24,500 12,900 16,000 21,600 24,400 30,000 40,300 23,300 28,700 38,400 26,800 33,100 44,600 23,300 28,700 38,400

Chilled Water Inlet / Outlet, °F

40/50°F

45/55°F

SC

FLOW PR DROP

TC

SC

FLOW

BTUH

GPM

PSI

BTUH

BTUH

GPM

4,900

1.2

5,500

1.5

6,500

2.0

2.9

4,100

3,900

0.8

4.3

5,100

4,500

1.0

7.4

7,800

5,500

1.6

3,300

0.8

3,700

1.0

4,400

1.3

1.6

2,800

2,600

0.6

2.3

3,500

3,100

0.7

3.8

5,400

3,700

1.1

7,100

1.7

8,000

2.2

9,400

2.9

1.7

6,100

5,700

1.2

2.5

7,600

6,600

1.5

4.2

11,200

8,000

2.2

4,300

1.1

4,800

1.3

5,700

1.8

0.7

3,700

3,400

0.7

1.1

4,600

3,900

0.9

1.8

6,800

4,800

1.4

11,700

2.8

13,200

3.5

15,600

4.8

1.5

10,000

9,500

2.0

2.2

12,500

10,800

2.5

3.7

18,200

13,200

3.6

10,500

2.6

11,900

3.2

14,000

4.3

1.3

9,000

8,500

1.8

1.8

11,300

9,800

2.3

3.1

16,500

11,900

3.3

12,000

2.9

13,500

3.6

15,900

4.9

1.6

10,200

9,700

2.0

2.3

12,800

11,100

2.5

3.9

18,600

13,500

3.7

10,500

2.6

11,900

3.2

14,000

4.3

1.3

9,000

8,500

1.8

1.8

11,300

9,800

2.3

3.1

16,500

11,900

3.3

19,400

4.9

21,800

6.0

25,800

8.0

3.1

17,200

15,800

3.4

4.4

21,400

18,000

4.3

7.4

31,100

21,900

6.2

18,500

4.6

20,800

5.7

24,600

7.7

2.8

16,400

15,100

3.3

4.1

20,500

17,100

4.1

6.8

29,700

20,800

5.9

21,500

5.3

24,100

6.6

28,600

8.9

3.6

18,900

17,500

3.8

5.2

23,500

19,900

4.7

8.8

34,300

24,200

6.9

18,500

4.6

20,800

5.7

24,600

7.7

2.8

16,400

15,100

3.3

4.1

20,500

17,100

4.1

6.8

29,700

20,800

5.9

j Test conditions based on ANSI/AHRI Standard 440 k TC = Total Cooling Capacity l SC = Sensible Cooling Capacity m All duties based on 208V/1Ph/60Hz supply voltage and high fan speed except where stated otherwise n Pressure drops are coil only, excluding valves

PR DROP PSI 1.5 2.2 4.8 0.8 1.2 2.5 0.9 1.3 2.6 0.3 0.5 1.1 0.8 1.2 2.3 0.7 1.0 1.9 0.8 1.2 2.4 0.7 1.0 1.9 1.6 2.4 4.6 1.5 2.2 4.2 1.9 2.8 5.5 1.5 2.2 4.2

8

AIR 8-105.11

PERFORMANCE DATA

Ceiling Cassette

Table 9.1 – Heating Performance – Chilled Water Units with Optional Heating Coil

Hot Water 180°F Inlet / 160°F Outlet

Model

Filter

70°F Entering Air DB

Capacity (btuh)

PD (psi) Flow (gpm)

60°F Entering Air DB

Capacity (btuh)

PD (psi) Flow (gpm)

STD.

17,100

2.8

1.7

18,900

3.3

1.9

CCW 08

MERV 10 13,400

1.8

1.3

14,700

2.1

1.5

CCW 12

N/A

N/A

N/A

STD.

27,300

1.1

2.7

30,000

1.3

3.0

CCW 18

MERV 10 24,800

0.9

2.5

27,300

1.1

2.7

STD.

27,900

1.1

2.8

30,700

1.4

3.1

CCW 20

MERV 10 24,800

0.9

2.5

27,300

1.1

2.7

STD.

41,200

1.4

4.1

45,300

1.7

4.5

CCW 33

MERV 10 42,300

1.5

4.2

45,900

1.7

4.6

STD.

45,200

1.7

4.5

49,800

2.0

5.0

CCW 36

MERV 10 42,300

1.5

4.2

45,900

1.7

4.6

j All duties based on 208V/1Ph/60Hz supply voltage and high fan speed except where stated otherwise k Pressure drops are coil only, excluding valves

50°F Entering Air DB

Capacity (btuh)

PD (psi) Flow (gpm)

20,600

3.8

2.0

16,100

2.5

1.6

N/A

32,800

1.5

3.3

29,800

1.3

3.0

33,500

1.6

3.3

29,800

1.3

3.0

49,400

2.0

4.9

49,300

2.0

4.9

54,300

2.3

5.4

49,300

2.0

4.9

Table 9.2 – Heating Performance – Chilled Water Units with 2-Pipe Changeover

Hot Water 180°F Inlet / 160°F Outlet

Model

Filter

70°F Entering Air DB

Capacity (btuh)

PD (psi) Flow (gpm)

60°F Entering Air DB

Capacity (btuh)

PD (psi) Flow (gpm)

50°F Entering Air DB

Capacity (btuh)

PD (psi) Flow (gpm)

STD.

21,000

6.3

2.1

23,100

7.5

2.3

25,100

8.8

2.5

CCW 08

MERV 10 14,200

3.1

1.4

15,600

3.7

1.6

17,000

4.3

1.7

STD.

29,000

3.1

2.9

31,900

3.7

3.2

34,800

4.4

3.5

CCW 12

MERV 10 17,400

1.2

1.7

19,100

1.5

1.9

20,800

1.7

2.1

STD.

55,100

3.6

5.5

60,400

4.2

6.0

65,600

4.9

6.5

CCW 18

MERV 10 49,200

2.9

4.9

53,900

3.4

5.4

58,600

4.0

5.8

STD.

55,100

3.6

5.5

60,400

4.2

6.0

65,600

4.9

6.5

CCW 20

MERV 10 49,200

2.9

4.9

53,900

3.4

5.4

58,600

4.0

5.8

STD.

80,500

5.5

8.0

88,200

6.4

8.8

95,900

7.5

9.5

CCW 33

MERV 10 76,500

5.0

7.6

83,900

5.9

8.4

91,200

6.8

9.1

STD.

89,300

6.6

CCW 36

MERV 10 76,500

5.0

8.9

97,900

7.8

7.6

83,900

5.9

9.7

106,400

9.1

10.6

8.4

91,200

6.8

9.1

j All duties based on 208V/1Ph/60Hz supply voltage and high fan speed except where stated otherwise k Pressure drops are coil only, excluding valves

AIR 8-105.11

9

PERFORMANCE DATA

Ceiling Cassette

Table 10.1 – Heating Performance – DX Cooling and Heat Pump Units with Optional Heating Coil

Model CSD/CSH 18 CSD/CSH 24 CSD/CSH 30 CSD/CSH 36 CSD/CSH 42

Entering Air DB ºF @ 50% RH
50 60 70 50 60 70 50 60 70 50 60 70 50 60 70

Hot Water 180ºF Inlet / 160ºF Outlet

Heating Capacity

Flowrate

Pressure Drop

BTU/h

GPM

PSI

46,389

4.8

1.3

42,598

4.4

1.1

38,746

4.0

0.9

50,279

5.3

1.5

46,153

4.8

1.2

41,993

4.4

1.0

67,912

7.1

3.3

62,277

6.5

2.8

56,609

5.9

2.3

71,636

7.5

3.6

65,640

6.9

3.1

59,600

6.2

2.6

77,386

8.1

4.2

70,803

7.4

3.5

64,268

6.7

3.0

j All duties based on high fan speed except where stated otherwise k Pressure drops are coil only, excluding valves

10

AIR 8-105.11

UNIT DIMENSIONAL DATA

Ceiling Cassette

Figure 11.1 – Dimensions – Small Chassis: CCW08 and CCW12 (in inches)

1 3/4

3 3/16

25 3/16

1 CW OUTLET 2 CW INLET 3 HW INLET (Optional) 4 HW OUTLET (Optional) 5 BRANCH DUCT OPENING (x3) 6 FRESH AIR INTAKE (x2) 7 PUMP INSPECTION PORT 8 CONDENSATE DRAIN 9 CONTROL PANEL 10 MOUNTING BRACKET 11 ELECTRIC HEAT FUSE BOX OR TRANSFORMER

3 3/16

25 3/16

2 3/16 1 1/4

10 11/16

2 3/4

5

1

11 1/4

22 1/2

A
19 9/16

5

5 3/16 11 5/16

22 1/2 15/16 4 11/16

22 15/16

7/8

7

8

1 1/16

9 11/16

A

12 9/16 19 1/2

9

2

4 9/16

5 1/16
3 1/16 11

10

1 7/16

6 1/4 5 1/16
4 5/8 3 3/4

2 1/16

3 3/8 4 11/16

3 1 4

AIR 8-105.11

1 1/8 2 3/4
6
9 13/16
VIEW A-A
11

UNIT DIMENSIONAL DATA

Ceiling Cassette

Figure 12.1 – Dimensions – Medium Chassis: CCW18 and CCW20 (in inches)

11/16

37 2 1/4

24 7/16 37

1 CW OUTLET 2 CW INLET 3 HW INLET (Optional) 4 HW OUTLET (Optional) 5 FRESH AIR INTAKE (x3) 6 BRANCH DUCT OPENING (x4) 7 PUMP INSPECTION PORT 8 CONDENSATE DRAIN 9 CONTROL PANEL 10 MOUNTING BRACKET 11 ELECTRIC HEAT FUSE BOX OR TRANSFORMER

24 3/8

2 5/8

32 3/8

9 1/2 2 3/4

A
28 11/16

5 3/8
6
7

5 3/8

32 5/16

8 11/16

31 3/8

3 3/16 11 13/16
1 3/8
3

8

7/8

12

A

12 9/16

6 1/4 28 9/16

9
1/2

11 3 2 1 5/16 4

2 3/4

10
1 13/16

8 6 1/2 5 1/16

1 13/16 2 3/16 4 13/16 5 3/16

1 6
2 3/4 4 7/8

AIR 8-105.11

2 3/4 3 1/8
5
7 13/16
VIEW A-A

UNIT DIMENSIONAL DATA

Ceiling Cassette

Figure 13.1 – Dimensions – Large Chassis: CCW33 and CCW36 (in inches)
2 1/4 3/4

42 1/4 49 3/16

1 CW OUTLET 2 CW INLET 3 HW INLET (Optional) 4 HW OUTLET (Optional) 5 FRESH AIR INTAKE (x3) 6 BRANCH DUCT OPENING (x4) 7 PUMP INSPECTION PORT 8 CONDENSATE DRAIN 9 CONTROL PANEL 10 MOUNTING BRACKET 11 ELECTRIC HEAT FUSE BOX OR TRANSFORMER

24 5/16 30 1/8
37

2 5/8

1/8

1

32 3/8

11 1/2 4 3/4

A
28 11/16

9 13/16

2 3/4 3 1/8

5

A
6 VIEW A-A

19 5/8 43 1/2

6 3/8
7

1 15/16

9 11/16

3 5/8 12 7/16
3 5/16
3
8 7/8

3 7/16
10 1/2 9 11/16

12 9/16

6 1/4 28 9/16

10
1 13/16

1

32

8 6 1/2
5 1/8

1 15/16 2 5/16
6 7/8 7 1/4 9 3/4

1

6

2 3/4

2 3/4

4

4 7/8

9

11

AIR 8-105.11

13

UNIT DIMENSIONAL DATA

Ceiling Cassette

Figure 14.1 – Dimensions – Medium Chassis: CSD/CSH 18 and CSD/CSH 24 (in inches)

11/16
24 3/8 30 1/8

2 1/4

1 DX LIQUID LINE

2 DX SUCTION LINE

3 HW INLET (Optional)

4 HW OUTLET (Optional)

5 FRESH AIR INTAKE (x3)

6 BRANCH DUCT OPENING (x4)

7 PUMP INSPECTION PORT

8 CONDENSATE DRAIN

9 CONTROL PANEL

10 MOUNTING BRACKET

11 ELECTRIC HEAT FUSE BOX OR TRANSFORMER

24.2

616

37

29 7/8 37
32 3/8

2 11/16
11 1/2 4 3/4

2 3/4 3 1/8
5

4 3/8

A 10
28 11/16

VIEW A-A

A
6 3/8

6

6 3/8

10 32 5/16

31 3/8

7

3 5/16 7 1/8

12 1/16

3 5/16

3

8

3 1/16

7/8

12 9/16

6 1/4 28 9/16

9

11

15/16

1 2 3 1/2
4

4 15/16

3

2 13/16

1 7/8

1 11/16

4 1/8 5 1/8 5 13/16

10 1/2 9 11/16
1 15/16

2 5/16

2 3/4

2 3/4

14

AIR 8-105.11

UNIT DIMENSIONAL DATA

Ceiling Cassette

Figure 15.1 – Dimensions – Large Chassis: CSD/CSH 30, CSD/CSH 36 and CSD/CSH 42 (in inches)

11/16

30 5/8 24 5/16

2 1/4

1 DX LIQUID LINE 2 DX SUCTION LINE 3 HW INLET (Optional) 4 HW OUTLET (Optional) 5 FRESH AIR INTAKE (x3) 6 BRANCH DUCT OPENING (x4) 7 PUMP INSPECTION PORT 8 CONDENSATE DRAIN 9 CONTROL PANEL 10 MOUNTING BRACKET 11 ELECTRIC HEAT FUSE BOX OR TRANSFORMER

42 1/4 36 5/16

49 3/16

37

2 11/16

11 1/2 4 3/4

32 3/8
A

10

28 11/16

A

2 3/4 3 1/8
5
VIEW A-A

6 3/8
7

4 3/8

6
43 1/2

3 3/8 3 7/8
8
10 1/2 9 11/16
1 15/16

12 9/16

6 1/4 28 9/16

9

15/16

6 1/4

1 7/8
11

9 13/16

1 7/8

2 3/4

2 3/4

4 7/8

AIR 8-105.11

3 1/2

4

2 7/8

6 3/8 4 7/8 2 15/16

2 1
4 7/16

3
4 7/8
6 7/16

15

TECHNICAL DATA

Ceiling Cassette

Figure 16.1 – Technical Data ­ DX Cooling Only and Heat Pump Units

DESCRIPTION Material: Fascia CONSTRUCTION Material: Chassis Type

UNITS

Model Digit 2,3 + Model Size

SD/SH 18

SD/SH 24

SD/SH 30

SD/SH 36

SD/SH 42

High Impact Polystyrene (Pearl Grey color), UL94 VO Fire Rating

Galvanized Steel

Finned Tube

Quantity

EVAPORATOR Face Area

Nominal Airflow – H/M/L

Discharge

Type

FAN

Quantity Diameter

Horsepower (per fan)

Number of Circuits REFRIGERATION
Refrigerant Type

WEIGHTS

Weight – Chassis Weight – Fascia

Suction (1)

CONNECTIONS Liquid (1)

Condensate (ID)

Type

Size

FILTRATION Type

Nominal Size

Quantity

CONDENSATE Maximum Head

PUMP

Nomincal Flowrate

Electric Heating Capacity

Max Supply Air Branch Duct Connections

OPTIONS

Supply Air Branch Duct Diameter Ducted Supply Air Volume (2)

Fresh Air Connections

Fresh Air Duct Diameter

Fresh Air Volume (3)

ft2 CFM
in HP
lbs
in
in in in gpm kW qty in CFM qty in CFM

1

4.0

5.2

590 / 540 / 465 670 / 590 / 540 920 / 800 / 680 1000 / 920 / 800 1130 / 1000 / 920

4-Way

Centrifugal

1

2

14.0 1/6

1

R-410A

66

97

18

21

0.75

0.375

0.375

Washable Polyester Foam (Standard)

11.6 x 23.2 x 0.2

MERV 10

12.0 x 25.0 x 1.0

2

3

30

0.1

3.0

5.0

2

5.0

6.0

115

130

180

200

220

3

3.0

60

65

85

90

95

1. Refrigerant line sizes should always match condensing unit connection sizes.
2. Maximum air volume available through one branch duct 6′ long, with Cassette fan(s) at high speed and corresponding fascia aperture closed.
3. Maximum fresh air through all knockouts connected to one 10′ long duct with fan at high speed. Fresh air volume will depend on duct configuration, fan speed, and filter type.
4. For electrical data, please refer to the submittal data in Breeze AccuSpec.

16

AIR 8-105.11

TECHNICAL DATA

Ceiling Cassette

Figure 17.1 – Technical Data ­ Chilled Water Units

DESCRIPTION Material: Fascia CONSTRUCTION Material: Chassis

UNITS

CW08

Model Digit 2,3 + Model Size

CW12

CW18

CW20

CW33

CW36

High Impact Polystyrene (Pearl Grey color), UL94 VO Fire Rating

Galvanized Steel

Type

Finned Tube

Quantity

Face Area

Nominal Airflow – Standard –

CHILLED WATER H/M/L

COIL

Nominal Airflow – MERV 10 –

H/M/L

Discharge

Unit Water Volume

Maximum Inlet Water Pressure

Type

1

ft2

1.8

2.8

5.2

CFM 330/300/260 360/330/300 600/540/460 620/600/540 940/850/740 1080/940/850

CFM
gal psi

200 / 170 / 160 0.29

520 / 490 / 450
4-Way 0.45 125 Centrifugal

880 / 760 / 690 0.79

FAN WEIGHTS CONNECTIONS
FILTRATION CONDENSATE
PUMP
OPTIONS

Quantity Diameter Horsepower (per fan) Weight – Chassis Weight – Fascia Chilled Water Inlet Chilled Water Outlet Condensate (ID) Type Size Type Size Quantity Maximum Head Nomincal Flowrate Electric Heating Capacity Max Supply Air Branch Duct Connections Supply Air Branch Duct Diameter Ducted Supply Air Volume (1) Fresh Air Connections Fresh Air Duct Diameter Fresh Air Volume (2)

in HP lbs
in
in
in
in GPM kW qty
in CFM qty
in CFM

1

2

12.0

15.0

14.0

1/8

1/6

40

64

97

5 0.625

18

21

0.875

0.625

0.875

0.375

Washable Polyester Foam (Standard)

14.5 x 13.5 x 0.2

11.6 x 23.2 x 0.2

MERV 10

13.0 x 13.0 x 1.0

12.0 x 25.0 x 1.0

1

2

3

30.0

0.1

1.5

3.0

5.0

2

5.0

6.0

80

100

125

200

220

2

3

3.0

40

60

65

90

95

1. Maximum air volume available through one branch duct 6′ long, with Cassette fan(s) at high speed and corresponding fascia aperture closed.
2. Maximum fresh air through all knockouts connected to one 10′ long duct with fan at high speed. Fresh air volume will depend on duct configuration, fan speed, and filter type.
3. For electrical data, please refer to the submittal data in Breeze AccuSpec.

AIR 8-105.11

17

Ceiling Cassette
THIS PAGE INTENTIONALLY LEFT BLANK

18

AIR 8-105.11

Ceiling Cassette
THIS PAGE INTENTIONALLY LEFT BLANK

AIR 8-105.11

19

Modine Manufacturing Company
1500 DeKoven Avenue Racine, Wisconsin 53403-2552 Phone: 1.866.823.1631 www.modinehvac.com
©2023 Modine Manufacturing Co.

AIR 8-105.11

Follow us @ModineHVAC See us at YouTube.com/ModineHVAC www.linkedin.com/company/modinehvac/

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals