Marstair Ckc20pd R407c Outdoor Unit Low Temp Pump Instruction Manual

Marstair Ckc20pd R407c Outdoor Unit Low Temp Pump Instruction Manual

Mastair

MARSTAIR CKC20PD R407C Outdoor Unit Low Temp Pump

MARSTAIR-CKC20PD-R407C-Outdoor-Unit-Low-Temp-Pump

GENERAL

  1. TEV Ltd recommend that personnel working on this equipment be skilled and fully conversant with the appropriate Air Conditioning, Refrigeration and Electrical practices and have sound knowledge of current Industrial Safe Working practices.
  2. CXE models are electromechanical / Electronic control units that use R407C refrigerant; they provide cooling within the range of 2.8 – 8.5 kW. These units are matched with CKC pump down outdoor units to complete a system.
  3. CXE Pump Down units are fitted with an expansion assembly and solenoid valve These units must be ran on a liquid line and matched with the Marstair CKC Pump Down units which are fitted with a liquid receiver.
  4. These units contain live electrical components, moving parts and refrigerant under pressure. Always site out of reach of children and protect from vandalism.
  5. The data plate only gives information for the CXE unit. For system details add input power and current of indoor and outdoor unit, including any heater load.

PART NUMBERS

MODELCXE 30 PDCXE 40 PDCXE 50 PDCXE 70 PDCXE 90 PD
PART NUMBER5591700655917007559170085591700955917010
MODELCKC 20 PD 1phCKC 30 PD 1phCKC 50 PD 1phCKC 80 PD 1ph
PART NUMBER55050800550508015505080355050805

Low Temperature Match 

MODELCXE 40 PDCXE 50 PDCXE 70 PDCXE 90 PD
PART NUMBER55917007559170085591700955917010
MODELCKC 20 PD 1phCKC 40 PD 1phCKC 60 PD 1phCKC 80 PD 1ph
PART NUMBER55050800550508025505080455050805

UNIT COMBINATIONS

Above 8°C System Matches 

INDOOR UNITOUTDOOR UNIT
CXE 30 PDCKC 20 PD
CXE 40 PDCKC 30 PD
CXE 50 PDCKC 50 PD
CXE 70 PDCKC 80 PD
CXE 90 PDCKC 90 PD

CX(E) OPTIONS

OPTIONAL KITS
PART NUMBER 

DESCRIPTION

559007153kW heater (CXE only)

Note: When matched with CKC outdoor unit

DIMENSIONS & WEIGHTS

MODELUNPACKEDPACKED
CX(E)HEIGHTWIDTHDEPTHWEIGHTHEIGHTWIDTHDEPTHWEIGHT
304838453201853095037021
404838453201853095037021
504838453202053095037023
704838453202353095037026
904838453202553095037028
MODELUNPACKEDPACKED
 

CKC

 

HEIGHT

 

WIDTH

 

DEPTH

WEIGHT 

HEIGHT

 

WIDTH

 

DEPTH

WEIGHT
1Ph3Ph1Ph3Ph
206209003104662098034048
306209003104862098034055
50720100035064730109039066
60720100035064730109039066
807201000350666473010903906866
908201000350767382010903907875

PERFORMANCE DATA (kW)

Above 8°C System Matches 

  12.7/10 & 2712.7/10 & 3212.7/10 & 35
 

CX

 

CKC

TotalSensibleCellar Size 

SHR

TotalSensibleCellar Size 

SHR

TotalSensibleCellar Size 

SHR

AboveBelowAboveBelowAboveBelow
kWkWkWkWkWkW
30202.81.8831520.672.71.8129490.672.61.7428470.67
40303.62.2744720.633.32.1239640.643.12.0236590.65
50505.23.23711140.6253.12671090.624.83.02641040.63
70807.24.351081690.606.94.21021610.616.64.05961520.61
90908.55.041332060.598.24.851271970.5984.681231920.59
  8/6 & 278/6 & 328/6 & 35
 

CX

 

CKC

TotalSensibleCellar Size 

SHR

TotalSensibleCellar Size 

SHR

TotalSensibleCellar Size 

SHR

AboveBelowAboveBelowAboveBelow
kWkWkWkWkWkW
30202.451.622360.652.31.5220340.662.21.4719330.67
403031.9530510.652.81.8327450.652.61.72825420.66
50504.42.7849800.634.22.6947760.6442.645730.65
70806.13.9751180.645.93.75711120.645.73.63671070.64
90907.34.55931440.627.14.4891380.6274.31861340.62

Above 4°C System Matches

  5/3 & 275/3 & 325/3 & 35
CXCKCTotalSensibleSHRTotalSensibleSHRTotalSensibleSHR
kWkWkWkWkWkW
40202.11.60.761.91.450.761.81.380.77
50403.32.460.753.12.320.7532.250.75
706053.530.714.73.330.714.53.20.71
90805.940.685.73.90.685.53.80.69

Qualification of Cellar sizing 

  • Based on standard Cellar Construction
  • Maximum product load 16 l/m³
  • Product cooling time 24 hours (Nominal plant running time 18 hours)
  • Product entering room 25°C

AIR FLOWS

MODELm³/s
CX(E) 300.61
CX(E) 400.61
CX(E) 500.66
CX(E) 700.58
CX(E) 900.55
MODELm³/s
CKC 200.32
CKC 300.71
CKC400.71
CKC 500.91
CKC 600.91
CKC 800.91
CKC900.91

SOUND POWER AND SOUND PRESSURE LEVELS

INDOOR UNIT 

Sound Pressure Levels in dB(A) at 10m distance in free field conditions. (Reference 2×10⁻⁵ N/m²)

OUTDOOR UNIT 

MAXIMUM SPEEDSOUND POWER LEVELSSOUND PRESSURE LEVELS
Frequency Hz
 1252505001K2K4KdB(A)
CKC 2077676965605439.2
CKC 3077686965605439.3
CKC 4077676965605439.2
CKC 5074686766615438.9
CKC 6073686866625439.3
CKC 8071696865605438.7
CKC9082726969635742.2

Sound Pressure Levels (SPL) at 10m distance in free field conditions. (Reference 2×10⁻⁵ N/m²)

ELECTRICAL DATA

Above 8°C System Matches 

 

 

MODEL INDOOR/OUTDOOR

1 PH 230V 50Hz
INPUT POWERFULL LOADS AMPSSYSTEM MAX. STARTING CURRENT
COOLINGHEATINGCOOLINGHEATING
kWkWAMPSAMPSAMPS
CX(E) 30 + CKC 201.32.97.713.830
CX(E) 40 + CKC 301.62.98.213.838
CX(E) 50 + CKC 502.22.99.713.860
CX(E) 70 + CKC 803.22.912.313.878
CX(E) 90 + CKC 904.42.917.713.8116
 

 

MODEL INDOOR/OUTDOOR

3 PH 4000V 50Hz
INPUT POWERFULL LOADS AMPSSYSTEM MAX. STARTING CURRENT
COOLINGHEATINGCOOLINGHEATING
kWkWAMPSAMPSAMPS
CX(E) 70 + CKC 803.22.95.713.842
CX(E) 90 + CKC 904.42.97.913.850

Above 4°C System Matches 

 

 

MODEL INDOOR/OUTDOOR

1 PH 230V 50Hz
INPUT POWERFULL LOADS AMPSSYSTEM MAX. STARTING CURRENT
COOLINGHEATINGCOOLINGHEATING
kWkWAMPSAMPSAMPS
CXE 40 + CKC 201.32.97.713.830
CXE 50 + CKC 402.12.910.213.852
CXE 70 + CKC 602.42.99.813.863
CXE 90 + CKC 803.22.912.313.878

UNIT ELECTRICAL LOADS [230V 50Hz 1Ph (A) or 400V 50Hz 3Ph (A/Ph)

 

MODEL

FAN MOTORHEATER
CX(E) 300.813
CX(E) 400.813
CX(E) 500.813
CX(E) 700.813
CX(E) 900.813
CKC20304050608090
Fan motor0.40.60.60.60.60.60.6
R407C compressor

(1 Ph) nominal FLA

 

6

 

10.4

 

10.2

 

8.3

 

9.8

 

10.9

 

16.3

R407C compressor

(3 Ph) nominal FLA

 

 

 

 

 

 

4.3

 

6.5

Crankcase heater0.250.250.25

CX(E) DIMENSIONS MARSTAIR-CKC20PD-R407C-Outdoor-Unit-Low-Temp-Pump-1MARSTAIR-CKC20PD-R407C-Outdoor-Unit-Low-Temp-Pump-2

INSTALLATION

CONTENTS
PARTS DESCRIPTIONQTYACTION
Envelope containing operating instructions and Declaration of Conformity1Pass to the end user.
Mounting brackets2Use to hang unit.
 
Drain Stub/Nut/Gasket 1Fitted by installer.
Drain stub adaptor 1Convert to ¾drain if required.
Screw M5 6To fix brackets to unit.
Washer nylon 6To fix brackets to unit.
Washer M5 shakeproof 6To fix brackets to unit.
Reducing flare nut 1/2” – 3/8” 1Fit to liquid connection on the CXE 70 indoor unit when matched with a CKC 60 outdoor unit

The unit may be mounted on a wall or solid ceiling using brackets supplied. It should be matched with the appropriately sized outdoor unit; this instruction should be used in conjunction with the outdoor unit installation instructions.

UNIT COMBINATIONS

  1. Fit all kits prior to installing the unit. (Heater kit is easier to fit when unit has been mounted).
  2. Ensure that the mounting surface will support the operating weight of the unit (see table below).
  3. Mark out the mounting positions and drill holes to suit 6mm rawlbolt shields or equivalent strength fasteners (ensure that the unit is positioned to give sufficient access (min 0.5m) to the removable side panel).
  4. Fix the mounting brackets to the unit in the correct position for wall or ceiling mounting.
  5. Raise the unit into position and secure the fixings, ensuring that it is square and level.
  6. Remove the drain tray then fit the drain stub, nut & gasket. Refit the drain tray.MARSTAIR-CKC20PD-R407C-Outdoor-Unit-Low-Temp-Pump-3

NITROGEN CHARGE

The unit contains a small charge of dry nitrogen, which should be discharged into the atmosphere. This is a non-toxic, non- ozone depleting gas with no global warming potential. FITTING LOSSES, in equivalent straight lengths of pipe (m).

 

FITTING

Pipe Size ODTo calculate the total equivalent length, the equivalent lengths of all fittings in a pipe run must be added to the actual length of pipe in the run: these are the fittings most likely to be used.

 

R = Radius of bend d = Diameter of tube C = Centres of bend

3/8″1/2″5/8″3/4″7/8″
45° Bend0.120.150.180.210.24
90° Bend R/d = 10.370.430.490.550.61
90° Bend R/d = 1.50.240.270.30.370.43
180° Bend R/d = 1.50.730.911.11.281.46
180° Bend C/d = 2.50.460.550.640.760.85
90° Elbow0.670.851.041.251.46

A. USING SUCTION AND LIQUID LINES:
With the expansion device connected to the indoor unit, the equivalent pipe run should be 45m (20m for CKC20) maximum, including a maximum lift of 7.5m. Fully insulate the suction line. Ensure the suction pipe is insulated well over the drain tray at the indoor unit. Liquid lines should be routed to avoid hot areas. This prevents flash gas forming, which may result in erratic control of liquid refrigerant to the evaporator.

 MAXIMUM EQUIVALENT LENGTH OF SUCTION LINE PIPE SIZES (m)LIQUID LINE (m)
SYSTEM3/8″1/2″5/8″3/4″7/8″1/4″3/8″1/2″5/8″
CX(E)30 + CKC207.52020
CX(E)40 + CKC30154545
CX(E)50 + CKC507.518452045
CX(E)70 + CKC801130452045
CX(E)90 + CKC901025452045
 MAXIMUM EQUIVALENT LENGTH OF SUCTION LINE PIPE SIZES (m)LIQUID LINE
SYSTEM3/8″1/2″5/8″3/4″7/8″1/4″3/8″1/2″
CX(E)40 + CKC207.52020
CX(E)50 + CKC401536452045
CX(E)70 + CKC607.51436452045
CX(E)90 + CKC801130452045

PIPE CONNECTIONS

Units are supplied with the following male flare connections (sizes in inches):

INDOOR UNITCX(E)30CX(E)40CX(E)50CX(E)70CX(E)90
LIQUID / EXPANSION3/8″3/8″3/8″1/2″1/2″
SUCTION1/2″1/2″1/2″5/8″5/8″
OUTDOOR UNITCKC20CKC30CKC40CKC50CKC60**CKC80CKC 90
LIQUID / EXPANSION3/8″3/8″3/8”3/8″3/8”1/2″1/2″
SUCTION1/2″1/2″1/2”1/2″5/8”5/8″5/8″

RESTRICTORS

Indoor units are supplied with restrictors fitted.

NOTE
When the CXE 40 is matched with a CKC 20.
The restrictor in the indoor unit must be changed to 0.033″ When the CXE 50 is matched with a CKC 40.
The restrictor in the indoor unit remains as a 0.050″ When the CXE 70 is matched with a CKC 60.
The restrictor in the indoor unit must be changed to 0.057″ When the CXE 90 is matched with a CKC 80.
The restrictor in the indoor unit must be changed to 0.063″MARSTAIR-CKC20PD-R407C-Outdoor-Unit-Low-Temp-Pump-4

INTERCONNECTING PIPEWORK 

  1. The indoor unit has a low pressure charge of N2, which may be safely released into the atmosphere before connection. The service valves on the outdoor unit should remain closed (IN, fully clockwise) until pipework has been fitted and system evacuated.
  2. Connecting the pipework
    • Remove the flare nuts from the suction and liquid service valves.
    • Ensure that the suction line is fully insulated: if an expansion line is used this should also be fully insulated.
    • Place the flare nuts over the incoming pipework and flare the pipe ends. The use of a little refrigeration oil on the flaring tool will help.
    • Connect the pipework between the units. Do not leave pipe ends, valves etc. open to the atmosphere.
    • R407C is very hygroscopic and will absorb damaging levels of moisture if left open.
      Always use two spanners when tightening the flare nuts to avoid twisting the pipes. Use a small amount of refrigerant oil on the mating surfaces.
    • Sight glasses and filter driers are not necessary, but if required should be fitted between the outdoor unit liquid shut off valve and the expansion device.

CKC REFRIGERANT

EVACUATING 

  1. Connect a vacuum pump to the service ports on the outdoor unit valves and evacuate the system to 1000 microns (1 Torr) or better and allow to be held for a minimum of 15 minutes.
  2. Replace the caps on the service ports, (torque to 25NM).

ADDING REFRIGERANT 

  1. All units are fitted with head pressure control. The link wire across the orange terminals allows the fan to operate at full speed. THIS SHOULD BE REMOVED AFTER CHARGING
  2. If a manual HP cut-out is fitted, ensure that the reset button is depressed.
  3. A 3 minute delay occurs between successive compressor operations.
  4. R407C should be introduced through the Schrader valve on the indoor unit, or the service port on the suction service valve on the outdoor unit. No other refrigerant must be used.
    No extra POE oil needed with liquid lines. Charges shown are for guidance: actual charge will depend on the individual application. It is recommended that you charge to a sweat line on the outlet of the evaporator and/or a full sight glass if fitted.
     

     

    Charge based on:-

    Liquid lineExpansion line
    1/4″3/8″3/8″1/2″5/8″
    25 g/m60 g/m16 g/m30 g/m48 g/m
    Additional POE oil25g per 350g of additional refrigerant to a maximum of 300g

    NOTE: The new 50 Series CKC are supplied with a Nitrogen holding charge. See pages 12 & 13 for refrigerant charge information.

  5. Run the system for a few minutes to allow it to stabilize. Where possible, charge to a sweat line on the evaporator. Typical suction pressure on short lines at UK conditions should be approx. 3.8bar (55 psig).
  6. Head pressure controller
    The head pressure controller is factory set to suit the refrigerant. It may be necessary to adjust this to suit site conditions, to raise or lower the nominal head pressure.MARSTAIR-CKC20PD-R407C-Outdoor-Unit-Low-Temp-Pump-5
    • With the system switched off, connect a high pressure gauge to the liquid line service valve.
    • Switch on the system, and run for a few minutes to stabilise.
    • The head pressure should be approximately:
      R407C: 275-280 psig (18.9-19.6barg) to achieve this remove sealing plug and insert 2mm or 5/64” allen key into setting screw. Turn allen key clockwise (+) or counter clockwise (-) to readjust the setting. Do not turn setting screw more than 3 turns clockwise (+3).
      Use following table as a quick guideline for setting:
      After adjustment, re-insert sealing plug and make sure that it is properly fitted. IP65 protection requires firmly sealed plug
      NOTES: Tolerances for condensing temperatures setpoint: ±2K Min fan speed (0 rpm) and fan cut in pressure 200 psig (13.8 barg) are factory set and not adjustable.
      NOTE: The condenser fan may stop if the operating pressure drops below 200 psig (13.8 barg)

CXE PUMP DOWN 17 SERIES MATCHED WITH CKC 50 SERIES UNITS WITH MICROCHANNEL COIL

SystemPart NumberLiquid Line
CXECKC51015202530354045
 

 

R407C

CX(E)30 + CKC20559170065505080082995410791204     
CX(E)40 + CKC305591700755050801103413341634193422342534283431343434
CX(E)50 + CKC505591700855050803136616661966226638164366491654666016
CX(E)70 + CKC805591700955050805149017902090239039404490504055906140
CX(E)90 + CKC905591701055050806240029503500405061006960782086809540

LOW TEMPERATURE CXE PUMP DOWN 17 SERIES MATCHED WITH CKC 50 SERIES UNITS WITH MICROCHANNEL COIL

SystemPart NumberLiquid Line
CXECKC51015202530354045
 

 

R407C

CXE 40 + CKC 2055917007550508007398649891114     
CXE 50 + CKC 40559170085505080295612561556185634063956450650565606
CXE 70 + CKC 605591700955050804135016501950225038004350490054506000
CXE 90 + CKC 805591701055050805159018902190249040404590514056906240

ELECTRICAL CONNECTIONS

  • Cables are routed to the terminal block via the cable cord grips at the rear of the unit and then through the back of the electrics box (see page 2).
  • Cables MUST be size compatible with the recommended system fuse.

FUSES 

 

SYSTEM

COOL ONLYWITH ELECTRIC HEATER
1PH1PH
CXE 305A16A
CXE 405A16A
CXE 505A16A
CXE 705A16A
CXE 905A16A
SYSTEM1PH3PH
CKC 2016A
CKC 3016A
CKC 4020A
CKC 5016A
CKC 6020A
CKC 8025A10A/PH
CKC 9025A16A/PH

WIRING DIAGRAM

CXE PUMP DOWNMARSTAIR-CKC20PD-R407C-Outdoor-Unit-Low-Temp-Pump-6

Note: Only ‘Mains in’ supply needs connecting when running system on pump down, no need to connect to ‘CU OUT’ Terminals

CKC PUMP DOWN MARSTAIR-CKC20PD-R407C-Outdoor-Unit-Low-Temp-Pump-7

Note: Only ‘Mains in Live, Neutral & Earth’ supply needs connecting when running system on pump down, no need to connect to ‘Remote thermostat -8’ or ‘Control wire – 42’ or ‘To Evaporator unit’ Terminals

TIMER RELAY SETTINGS MARSTAIR-CKC20PD-R407C-Outdoor-Unit-Low-Temp-Pump-8

Note: Set for minimum compressor off time, minimum 30 seconds

CXE ELECTRONIC COOLING SYSTEM CONTROLS

CAREL IR33 Controller

ON/OFF SWITCH
The switch operates the fan motor and is illuminated when power is supplied to the indoor unit. When switched OFF, the fan stops, the switch remains illuminated and the crankcase heater in the outdoor unit (if fitted) remains live.

Minimum Set Temperature 8°C
INDOOR UNITOUTDOOR UNIT
CX(E) 30CKC 20
CX(E) 40CKC 30
CX(E) 50CKC 50
CX(E) 70CKC 80
CX(E) 90CKC 90
Minimum Set Temperature 4°C
INDOOR UNITOUTDOOR UNIT
CXE 40CKC 20
CXE 50CKC 40
CXE 70CKC 60
CXE 90CKC 80

TEMPERATURE CONTROL (Do not set the controller below 4⁰C.)
The SET temperature is factory set at 12⁰C.
The digital display normally displays the return air temperature.
To change the SET temperature, press and hold down the SET button. If no alarms active, the ‘St1’ label appears and the current value is shown on the screen and will flash.
To change the Setpoint value, press ▲ and ▼ keys within 60 seconds.
The display will revert to the return air temperature after 60 seconds.
The fitted de-ice thermostat will activate a de-ice cycle when there is a build up of ice on the evaporator coil.
Cellarators will only heat a room if the electric heater option is fitted.

Displaying inputs on screen display
Press ▼ to display the current input. There are 6 inputs to select from to display onto the screen. These are as follows:

  • b1: probe 1;
  • b2: probe 2;
  • di1: digital input 1;
  • di2; digital input 2;
  • St1: set point 1;
  • St2: set point 2;

Press ▲ and ▼ to select the input to be displayed. Press set for 3 seconds to confirm your choice.
To display the live temperature in the room you need to select b1: probe 1
WARNING: The following actions could damage your system:

  1. Switching the unit OFF and ON quickly
  2. Setting the unit to HEAT and then back to COOL quickly
    NB: Allow at least 3 minutes between the above actions.MARSTAIR-CKC20PD-R407C-Outdoor-Unit-Low-Temp-Pump-10

CKC INSTALLATION

MOUNTING
Whether floor or wall mounted, it is essential that the mounting surface is capable of supporting the unit weight. Leave space around the unit for air circulation and access for installation and maintenance.MARSTAIR-CKC20PD-R407C-Outdoor-Unit-Low-Temp-Pump-11

    • Pipe sizes are based on:-
      Minimum of 3.8 m/s (750 fpm) suction gas velocity for horizontal or downflow.
      Minimum of 7.6 m/s (1500 fpm) suction gas velocity for upflow.
      Maximum of 15.2 m/s (3000 fpm) suction gas.
    • Where vertical risers exceed 3m, oil traps must be formed in the pipe. This will help ensure that oil returns to the compressor. Typically fit an oil trap every 3m with a trap at the bottom of the riser.Individual pipe runs to a maximum of 45m (20m for CKC20), including 7.5m lift, are permissible with liquid lines. Performance is based on 7.5m pipe runs. Correctly sized pipes for each installation will result in no significant loss of capacity on extended pipe runs.
      CKC PIPEWORK
  1. In calculating equivalent lengths of pipe runs, the effect of bends and fittings must be taken into account. The table below covers the fittings most likely to be encountered in this installation. The equivalent lengths of all the fittings in a pipe run should be added together and the total added to the actual pipe length in order to calculate the total equivalent length.
  2. Use the shortest possible route, avoiding sharp bends.
  3. Completely insulate the suction line, fully over the indoor unit drain tray.

CX INDOOR UNIT COMPONENT IDENTIFICATION MARSTAIR-CKC20PD-R407C-Outdoor-Unit-Low-Temp-Pump-12

1Grille9De-ice stat
2Fan / motor10Heater assembly (option)
3Case11Drain stub adaptor
4Wall / ceiling mounting brackets12Drain tray
5Heater bracket13Side access panel
6Coil assembly14Electrics box door
7Thermostat bulb & bracket15Thermostat
8Restrictor assembly16Solenoid Valve

INSIDE VIEW OF ELECTRICS BOXMARSTAIR-CKC20PD-R407C-Outdoor-Unit-Low-Temp-Pump-13

CKC OUTDOOR UNIT COMPONENT IDENTIFICATIONMARSTAIR-CKC20PD-R407C-Outdoor-Unit-Low-Temp-Pump-14MARSTAIR-CKC20PD-R407C-Outdoor-Unit-Low-Temp-Pump-15

Commissioning Check List

The following information will be required to validate your 5yr parts warranty

Check and recordValueTime Held For
Leak (tightness) test pressure(bar)(min)
Strength (pressure) test pressure(bar)(min)
Evacuation level(microns)(min)
 Value
Low pressure (gauge)(barg)
Suction line temperature(°C)
Evaporator superheat(K)
Evaporator air ON / OFF(°C)                               (°C)
  
High pressure (gauge)(barg)
Liquid line temperature(°C)
Condenser sub cooling(K)
Condenser air ON / OFF(°C)                               (°C)
  
Compressor current(A)
Head pressure control set(Y/N)
  
Refrigerant type 
Charged weight(Kg)
Additional POE oil added(g)
Pipe run length(m)
Suction pipe size(ʺ)
Liquid / Expansion pipe size(ʺ)

TEV LTD, ARMYTAGE ROAD, BRIGHOUSE, WEST YORKSHIRE, HD6 1QF.
TEL: + 44 (0) 1484 405600
FAX: +44 (0) 1484 405620
EMAIL: [email protected] 
WEB: www.marstair.com

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals