Saci Pumps Ejoy New Speed Control System Instruction Manual

Saci Pumps Ejoy New Speed Control System Instruction Manual

saci - logoejoy New Speed Control System
Instruction Manualsaci pumps ejoy New Speed Control System

SAFETY RULES

Before installing and using the product:

  • Carefully read the whole of this manual.
  •  Check that the data indicated on the plate is desired information and is appropriate for the installation, and in particular that the nominal voltage of the pump is compatible with that of the installation.
  • The installation and maintenance must be carried out solely and exclusively by authorised personnel, responsible for making the electrical connections in accordance with the current safety regulations.
  • The pump must not be used by people with reduced physical, sensory or mental capabilities, or without the ue experience or knowledge, except if a person responsible for their safety has explained the instructions and supervised their operation of the pump.
  • Do not let children play with the pump.
  • The manufacturer accepts no liability for damage caused by improper use of the product and shall not be held responsible for damage caused by maintenance or repairs carried out by unqualified staff and/or using nonoriginal replacement parts.
  • The use of unauthorised replacement parts, alterations of the product or improper use shall automatically render the product guarantee null and void.

During normal operation:

  • Before removing the cover of the speed variator, connect the mains voltage and wait 5 minutes for the electronic circuit board to discharge any residual voltage inside.
  • Never disconnect the variator while the motor is rotating. This action can cause irreparable damage to the speed variator and affect the other electronic systems connected to the same electric grid.
  • Although the pump is not operational, the electrical supply must still be cut off to the whole speed variator for any maintenance work.
  • If there are any anomalies in the installation, the pump can be stopped manually using the button STOP for this purpose.

TECHNICAL DATA

Nominal values:

Power supply voltage (V)220-240 V (1~ – 50/60Hz)
Operating speed (RPM)700 r.p.m – 2800 r.p.m
Maximum current (A)11:00 AM
Protection ratingIP 55

Limits of use:

  • Minimum ambient temperature: -10ºC
  • Maximum ambient temperature: +40ºC
  • Variation in the supply voltage: +/- 10%

INSTALLATION / ASSEMBLY

Before installing the pump, carefully read the whole of this manual and consult the safety rules valid in each country.
Installation of the pump:

  • It must be installed in a well ventilated area, protected from damp and direct exposure to the sun and rain. Failure to comply with these indications can significantly reduce the life of the speed variator.
  • Before making the electrical connections, ensure the cable used to provide power to the pump is not live.
  • Carefully verify the electrical data indicated in the specifications plate of the speed variator before connecting the electric current.
  • The electric power cables to the pump must be of the correct size for the nominal consumption of the motor and the length of cable required.
  • Also ensure that the grid has electrical protection; a high-sensitivity differential switch (30 mA, class B for industrial applications) is particularly recommended.
  • In addition to the differential switch, it is advisable to install magnetothermal protection to control the power supply to the pump.

ELECTRICAL CONNECTIONSsaci pumps ejoy New Speed Control System - ELECTRICAL CONNECTIONS

SignalDescription
Outputs relay 1 and 2Outputs that acts depending on how they have been programmed. These outputs are potential free and have a maximum load of 5 amperes at 230 Vac.
FanWhen wall-mounted, as there is no cooling from the motor’s own fan, the ventilation system of the wall mounting shall be used for this cooling.
This output is at 24Vdc and is activated whenever thepump is running.
Digital inputs 1 and 2Any potential free contact that will perform the programmed functions can be connected to these inputs.
N.B. Do not apply voltage to these inputs.
Pressure transducerIf it is connected, it will be used by the speed variator to determine the pressure of the installation as well as the pressure during the “BACK WASH” cycle.

saci pumps ejoy New Speed Control System - SCREEN FORMAT

KeyFunction
V1Timed pump activation at speed 1
V2Timed pump activation at speed 2
V3Timed pump activation at speed 3
AUTTo activate the normal operation of the pump
STOPTo disable the pump at any time
BACK WASHTo initiate the filter cleaning cycle (back wash)
LIGHTSManually activate lighting time
F1Key to activate the text on the screen
F2Key to activate the text on the screen
UPDown Keys for moving around the menu
POWERIndicates voltage
RUNIndicates that the pump is operating
ALARMIndicates that there is an active alarm

MAIN SCREEN

This screen will show the current status of the pump:saci pumps ejoy New Speed Control System - MAIN SCREENYou can directly view the instantaneous rotational speed of the motor, the pressure of the installation (only if the pressure transducer is installed) and the instantaneous consumption of motor. In brackets, just to the side of the instantaneous consumption, you can see the nominal consumption of the motor entered in the start-up wizard (point 8 of this manual).
From this screen, if you click on the keys ( UP) or ( Down), you can directly access the display menu. This acts a short cut for checking data you need view without having to access the settings menu.

OPERATION MODE

The purpose of all pumps designed for swimming pool cleaning is to keep the water clean and in optimum ondition. The most notable development is that with the logic of the speed variator, this process is achieved with high energy savings.
The variator enables the operation of a pump in the installation, in addition to being able to control the automatic activation of the pool lights and also help to clean the filter, in addition to other functions.
There is a daily setting of various filtration sequences (up to 4 sequences every day), in which the pump’s operating speed can also be indicated.
The default of pump operation mode is automatic. Once time bands and the days of the week on which filtering is required have been indicated, the pump will filter at the speed indicated for each band. It is here where we must take into account that the slower the operating speed, the greater the energy savings.
The keyboard includes 3 buttons identified as V1, V2 and V3, which enable timed operation of the pump at the speed set in the corresponding parameter, in case the pump needs to be activated manually.
If there is a pressure transducer installed, the system will monitor the pressure of the installation at all times, to warn if it detects excess soiling in the filter. Once this warning has been received, or at any other time, when the button “BACK WASH” is pressed, a simple wizard will guide you through cleaning the filter. This wizard will tell you to move the filter valves to cleaning mode, then rinse and finally back to filtration.

START-UP

The first time you apply voltage to your unit, you will see parameter 1.1 that belongs to menu 1 General Setup, which at the same time is the start-up wizard.
You will also see this screen if you restore the factory settings.
In this menu, enter the basic parameters of the installation prior to programming the time intervals that you wish to have the pump filtering.saci pumps ejoy New Speed Control System - START-UPSelect the desired language with the ( Down) key and, with the F2 key (Next), move on to parameter 1.2 to continue with the set-up wizard.saci pumps ejoy New Speed Control System - START-UP 1In this parameter enter the date and time. The speed variator will be overned by this for scheduling the start and stop times. Continue with F2 key to access the screen where you will enter the nominal current of the motor, indicated on its specifications plate.saci pumps ejoy New Speed Control System - START-UP 2With the keys ( UP) and ( Down) you can increase and decrease, respectively, the nominal consumption of the pump motor. Use the F2 key to move on to menu 1.4.saci pumps ejoy New Speed Control System - START-UP 3This screen shows a sequence of starting and stopping the motor at low speed, to be able to see if the motor is rotating in the correct direction. If it is not, the keys ( UP) and ( Down) invert the rotation direction.
This is the last screen in the startup wizard.

SETUP MENU (SCHEMATIC)

saci pumps ejoy New Speed Control System - SETUP MENU

SETUP MENU

1. GENERAL CONFIG
Par.DescriptionUnitsVALUESNotes
DefaultMin.Max.
 1.1 LANGUAGE 1.1 English  To define the language used to interact with
the variator.
1.2SET TIMETo adjust the date and time of the variator.
 1.3 MOTOR CURRENT A 5 0.1 11Indicate the consumption in amperes AT 400V found on the motor specifications plate.
 1.4 ROTATION DIRECTION 0 0 1Modify the motor rotation direction, if it is rotating anticlockwise.
2. FILTRATION
Par.DescriptionUnitsVALUESNotes
DefaultMin.Max.
 2.01 NUMBER OF BANDS MONDAY 0 0 4The number of times the swimming pool water must be recirculated per day (Monday).
2.02 EDIT BAND MONDAY* (1)00:00Sets the start time of band 1.
2.0324:00Sets the end time of band 1.
2.04rpm14007002800Sets the rotational speed of band 1.
2.05 EDIT BAND MONDAY (2)00:00Sets the start time of band 2.
2.0624:00Sets the end time of band 2.
2.07rpm14007002800Sets the rotational speed of band 2.
2.08 EDIT BAND MONDAY (3)00:00Sets the start time of band 3.
2.0924:00Sets the end time of band 3.
2.10rpm14007002800Sets the rotational speed of band 3.
2.11 EDIT BAND MONDAY (4)00:00Sets the start time of band 4.
2.1224:00Sets the end time of band 4.
2.13rpm14007002800Sets the rotational speed of band 4.
 2.14 COPY DAY MONDAY TO TUESDAY**Enables you to copy the previous time settings to the next day (Tuesday).
Par.DescriptionUnits.VALUESNotes
DefaultMin.Max.
2.86 EDIT BAND SUNDAY (1)00:00Sets the start time of band 1.
2.8724:00Sets the end time of band 1.
2.88rpm14007002800Sets the rotational speed of band 1.
2.89 

EDIT BAND SUNDAY (2)

00:00Sets the start time of band 2.
2.9024:00Sets the end time of band 2.
2.91rpm14007002800Sets the rotational speed of band 2.
2.92  EDIT BAND SUNDAY (3)00:00Sets the start time of band 3.
2.9324:00Sets the end time of band 3.
2.94rpm14007002800Sets the rotational speed of band 3.
2.95 EDIT BAND SUNDAY (4)00:00Sets the start time of band 4.
2.9624:00Sets the end time of band 4.
2.97rpm14007002800Sets the rotational speed of band 4.
  • There is a complete configuration for every day of the week. This manual only explains how to configure Monday and Sunday, as a summary, but the process is the same for the other days of the week.
  • When the day’s settings are complete, it allows you to copy this configuration directly to the following day, saving time when setting every day individually.
3. LAVADO DE FILTRO
Par.DescriptionUnits.VALUESNotes
DefaultMin.Max.
3.01WASH SPEEDrpm28007002800Sets the speed of the pump for the filter cleaning process.
3.02WASH DURATIONmin5160Pump operating time during the filter wash process.
3.03RINSE DURATIONmin1060Once the filter is clean, the operating time of the pump for rinse the remaining dirty water from the filter.
3.04DIRTY FILTER WARNING PRESSUREbar1,512.5Pressure from which a warning will appear on the screen requiring the filter to be cleaned (for this function it is necessary to install a pressure transducer).
4. LIGHTS
Par.DescriptionUnits.VALUESNotes
DefaultMin.Max.
4.01PRESENCE OF LIGHTSNONOYESThe daily lighting cycle of the pool is programmed if it is indicated that there are lights.
4.02LIGHTS ON, MONDAY*OFFOFFONEnable/disable pool lighting on Mondays.
4.03LIGHTS START, MONDAY*00:00Indicate the start time of the lighting cycle.
4.04LIGHTS END, MONDAY*00:00Indicate the end time of the lighting cycle.
4.23RGB TESTEnables the colour sequence to be changed if there are RGB LEDs in the pool.
  • There is a complete configuration for every day of the week. This manual only explains how to configure Monday, but the process is the same for the other days of the week.
5. SKIMMING
Par.DescriptionUnits.VALUESNotes
DefaultMin.Max.
5.01SKIMMING DURATIONmin205To program the duration of the surface cleaning program (SKIMMING) of the pool. If 0 minutes is indicated, SKIMMING is disabled.
5.02SKIMMING INTERVALh3124Indicate how often the SKIMMING program is to be started.
5.03SKIMMING FLOWrpm28007002800Tell the pump what speed is required for the SKIMMING program.
6. FIXED SPEED
Par.DescriptionUnits.VALUESNotes
DefaultMin.Max.
6.01SPEED V1rpm9507002800Set the speed at which the pump is to run at speed V1.
6.02SPEED V2rpm14007002800Set the speed at which the pump is to run at speed V2.
6.03SPEED V3rpm28007002800Set the speed at which the pump is to run at speed V3.
7. INPUTS OUTPUTS
Par.DescriptionUnits.VALUESNotes
DefaultMin.Max.
7.01DIGITAL INPUT 1UnusedUnused External stop
External stop INV Fixed speed Fixed speed INV
An input can be used to perform a remote stop (the INV option is for a contact that opens to switch on) or for the pump to operate at a certain speed when the input 1 is activated or deactivated (INV option).
7.02SPEED IN 1rpm14007002800If digital input 1 is enabled for fixed speed, indicate the speed at which it is to operate when this input is given.
7.03DIGITAL INPUT 2Same as parameter 7.01 but for input 2.
7.04SPEED IN 2Same as parameter 7.02 but for input 2.
7.05OUTPUT 1OFFOFF
Salt chlorinator Wash
Alarm (NO) Alarm (NA) Run Clock (NO) Clock (NA)
Relay 1 can be programed to be activated (or deactivated for NC-terminated options) whenever the pump is started, when the pump is filtering (saline chlorinator), when an alarm occurs or when a certain programming cycle is running.
7.06SCHEDULE PROGRAMME 1OFFOFF M-Su M-F S-Su
M, T,X,T,F,S,Su
This parameter is visible only if one of the 2 clock options is selected in the previous parameter. It enables the days or the block of days to be programmed, such as M-Su that refers to Monday through Sunday, in which the relay is to be activated.
7.07START TIME PROGRAMME 100:00Indicate start time for programme 1.
7.08STOP TIME PROGRAMME 100:00Indicate start time for programme 2.
7.09OUTPUT 2Same as parameter 7.05 for output 2.
Par.DescriptionUnits.VALUESNotes
DefaultMin.Max.
7.10SCHEDULE PROGRAMME 2OFFOFF M-Su M-F S-Su
M, T,X,T,F,S,Su
This parameter is visible only if one of the 2 clock options is selected in the previous parameter. It enables the days or the block of days to be programmed, such as M-Su that refers to Monday through Sunday, in which the relay is to be activated.
7.11START TIME PROGRAMME 2Same as parameter 7.07 for program 2.
7.12STOP TIME PROGRAMME 2Same as parameter 7.08 for program 2.
8. PARÁMETROS AVANZADOS
Par.DescriptionUnits.VALUESNotes
DefaultMin.Max.
8.01NOMINAL FREQUENCY MOTORHz280014003400Modifies the maximum speed of pump operation.
8.02UNITS OF PRESSUREBarBarPSIYou can modify the units to represent the pressure of the installation.
8.03FULL-SCALE VALUE TRANSDUCERBar10558Enables you to adjust the range of detection of the transducer if its scale is not the standard 4-20 mA (0-10 Bar).
8.04MAXIMUM FILTER PRESSUREBar2.525In this point, indicate the maximum pressure that the filter supports, so that in normal operation the inverter takes it into account and acts accordingly so that this pressure is never exceeded.
8.05SWITCHING FREQUENCYKHz7.72,516Enables you to modify the switching frequency of the variator, reducing the noise, although uncommon, of the switching at the expense of an increase in temperature of the electronics.
N.B. We do not recommend modifying the default value except when expressly indicated by the Technical Department.
8.06LOW WATER LEVEL ALARM ACTIVEONONOFFEnables the constant monitoring of the pump running dry, if this occurs.
8.07LOW WATER ALARM LIMIT%755090Value used in the mathematical algorithm that calculates the pump running dry.
8.08PRIMING TIMEmin2110During the priming time, the detection of running dry will not be operative even though the monitoring is enabled.

9. MANUAL MODEsaci pumps ejoy New Speed Control System - MANUAL MODEThe objective of this screen is to test the pump operation, at a specific speed, for a controlled time, to correctly select the operating speeds of the cycles in section 2 of the settings menu.
Press F2 to activate the pump initially for 2 minutes at the maximum frequency of the pump. Each time you press the F2 key increases the operating time on a scale of 2 minutes, 15 minutes, 30 minutes, 1 hour, 2 hours, 4 hours or 8 hours. At any time, by pressing the F1 key, you can stop the pump operation.
Every time you press the keys ( UP) or ( UP) you increase or decrease, respectively, the operating speed of the pump by 10 rpm.

10. DISPLAY
Par.DescriptionUnits.VALUESNotes
DefaultMin.Max.
10.01MODULE TEMPERATUREºCShows the current temperature of the power module. If the temperature is very high, the speed variator itself will limit the speed of the pump to prevent the electronics of the speed variator being damaged.
10.02ANALOGUE SIGNALmA420Shows the value of the pressure transducer reading in mA.
10.03VOLTAGE HOURSHoursIndicates the hours the pump has been connected to the electricity grid regardless of whether it has been running or not.
10.04HOURS OF WORKHoursIndicates the hours of pump operation.
10.05ENERGY METERkWhIndicates the pump consumption in kWh.
10.06DIGITAL INPUT 1001Indicates whether input 1 is enabled or not; if it is enabled, the reason for this.
10.07DIGITAL INPUT 2001Indicates whether input 2 is enabled or not; if it is enabled, the reason for this.
10.08RELAY 1 OUTPUT001Indicates whether relay 1 is enabled or not; if it is enabled, the reason for this.
10.09RELAY 2 OUTPUT001Indicates whether relay 2 is enabled or not; if it is enabled, the reason for this.
11.00SOFTWARE VERSIONIndicates the version of the software of the control panel (screen) and the power panel (aluminium radiator).
11.01POWER CONSUMED BY PUMPWIndicates the instantaneous power consumed by the pump.

11. ALARM LOG
Shows a log of anomalies of the pump where the speed variator is connected, indicating the date, the time and the anomaly that occurred. This information is very important for detecting possible anomalies in the functioning of the installation.

12. RESETS
Par.DescriptionUnits.VALUESNotes
DefaultMin.Max.
12.01RESET METERSNONOYESEnter YES to delete the voltage hours and the energy meter.
12.02RESET ALARM HISTORYNONOYESEnter YES to reset all the faults stored in the alarm history.
12.03FACTORY SETTINGSNONOYESThis parameter will remove all the settings entered in the configuration of the variator, returning it to its initial status, as it was when installed for the first time.

11. ALARMS

MessageReasonsSolution(s)
 PRESSURE WARNING: FILTER CLEANINGIndicates that the pressure entered in the parameter (DIRTY FILTER WARNING PRESSURE) has been exceeded.Press the button BACK WASH and perform the steps indicated by the filter cleaning wizard, as the system detects a high pressure in the filter, probably due to excess soiling.
ALARM F01 OVERCURRENTIndicates excessive consumption in the motor.Check that the pump rotates freely with no obstructions.
The motor is communicated or has burnt out.Disconnect the motor from the variator and check that the message disappears. If this is not the case, contact your nearest technical service.
ALARM F02 SHORT CIRCUITNot all wires have been connected.Check that all the cables of the motor are correctly connected to the motor itself and also to the variator. Also supervise the correct wiring of the frequency converter’s power supply.
Internal fault in the variator.Contact your nearest technical service.
 ALARM F03
EXCESS TEMPERATURE OF THE MODULE
The power module has reached a very high temperature, compromising its reliability.Ensure the ambient temperature does not exceed the extremes set out in this manual.
Ensure the variator is properly ventilated; in this case check that the pump has a fan and that the fan cover has been installed.
ALARM F04 INPUT VOLTAGEThe variator is not receiving electric current, of is outside of the upper and lower limits.The electrical supply to the variator has been interrupted.
The electrical connection cable from the mains electricity to the variator has been disconnected.
MessageReasonsSolution(s)
  ALARM F06 MOTOR FAULTThe motor is communicated/disconnected. Loss of synchronism.Check that the cables to the motor are properly connected, as the variator is not detecting the motor, or it is burnt out.
There may also be a loss of synchronism of the motor during operation due to a significant, quick change in the pumping conditions.
ALARM F07
LOW WATER LEVEL
The variator detects that the pump is working without water in the body of the pump.Ensure the pump aspirates the fluid correctly.
ALARM F08 MAXIMUM PRESSURE LIMITThe variator detects that the filter is very soiled or at a pressure close to bursting.Check the filter does not need cleaning and that the impulsion valves allow recirculation.
 ALARM X13 INTERNAL ERRORThere is no communication between the control panel (cover), and the power plate (radiator).
Internal fault in the variator.
Check that the flat cable that communicates both electronic circuits are well connected and tightened.
There may be one-off read error of the firmware. We recommend cutting the power to the variator for a few minutes. If, when the power is reconnected to the variator, the message remains, contact your nearest technical service.

WARRANTY
The guarantee on the speed variator is 24 months from the date of purchase: The use of non-original spare parts, alterations or improper use shall render the product warranty void.

DISPOSAL AND ENVIRONMENTAL ASPECTS

To dispose of the parts that comprise the speed variator, you must abide by the current regulations and laws of the country where the product is used. In any case, do not dispose of polluting parts into the environment.
WEE-Disposal-icon.pngThis symbol on the product indicates that it should not be disposed of with other household waste.
This stipulation only refers to the disposal of equipment within the European Union (2012/19 /EU). It is the user’s responsibility to dispose of the equipment by delivering it to a designated collection point for the recycling and disposal of electrical equipment. For more information about equipment collection points, contact your local waste disposal agency.

DECLARATION OF CONFORMITY
declares, under its full responsibility, that the products to which this manual refers comply with the following European Directives and national action provisions:

DIRECTIVESNORMS
– Directive 2014/30/EU (EMC)– EN 61800-3 Category C2 (EMC)
– Directive 2014/35/EU (Low Voltage)– EN 61800-5-1 (LV)
– Directive 2012/19/EU (RAEE)– EN 50581 (RoHS)
– Directive 2011/65/CE (RoHS II)– EN 60529 (IP Code)

Granollers, 1st February 2019

saci pumps ejoy New Speed Control System - SignatureDavid Ferré Ferrer
GERENTE
Camí the Can Muntanyola, 4-22 – Pol. Ind. Palou Nord
08401 Granollers (Spain)
Tel. (+34) 933 842 351
Fax (+34) 933 842 900
www.sacipumps.com
[email protected]

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals