Evco Evk802 Digital Controller Instruction Manual

Evco Evk802 Digital Controller Instruction Manual

EVCO logo

Evco S.p.A. · Codice 104K802E04
EVK802 Digital controller for quick coolers management

version 1.04

PREPARATION

 Important

Please read these instructions carefully prior to installation and use, and follow all the precautions for installation and electrical connections; keep these instructions with the device for future consultation.

Installation

Per panel, using the snap-on brackets supplied; the dimensions are given in mm.
EVCO EVK802 Digital Controller - Installation

DIMENS.MINIMUMTYPICALMAXIMUM
A71,071,071,8
B29,029,029,8

EVCO EVK802 Digital Controller - Recommendations

Recommendations for installation:

  • the maximum depth with screw terminal blocks is 59.0
  • the maximum depth with removable terminal blocks is 83.0
  • the panel thickness must not exceed 8,0 mm
  • ensure that the operating conditions (operating temperature, humidity, etc.) are within the limits indicated in the technical data sheets
  • do not install the device near any sources of heat (heating elements, hot air conduits, etc.), equipment containing powerful magnets (large diffusers, etc.), areas affected by direct sunlight, rain, humidity, excessive dust, mechanical vibration, or shock
  • in compliance with safety regulations, the device must be installed correctly, and in such a way as to protect against any contact with electrical parts; all safety devices must be fixed so that they cannot be removed without the use of tools.
Electrical connections

With reference to the electrical circuit diagram:

  • the service controlled by relay K2 depends on parameter u0
  • the serial port (available on request) is the port used for communicating with the monitoring system (by means of a serial interface, via TTL, using the MODBUS communication protocol) or with the programming key; the port must not be used for both purposes simultaneously.

EVCO EVK802 Digital Controller - Electrical connections

Points to note for connecting to the electricity supply

  • do not use electric or pneumatic screw-wrenches on the terminal board
  • if the device has been moved from a cold to a warm environment, condensation may have formed inside; please wait for approx. one hour prior to switching on
  • ensure that the voltage, frequency, and operational power of the device are compatible with the local power supply
  • disconnect the power prior to proceeding with any kind of maintenance operation
  • do not use the device as a safety device
  • for repairs and any information relating to the device, contact the Evco dealer network.

USER INTERFACE

Introductory information

The device has the following operational states:

  • “on” (the device is switched on and an operating cycle is running)
  • “stand-by” (the device is switched on but no operating cycle is running)
  • “off” (the device is not switched on).

If power is interrupted during a timed blast chilling operation, when power is restored, chilling will continue from the time point at which the interruption occurred (with a maximum error of 10 minutes).
If power is interrupted during a set-temperature blast chilling operation, when power is restored, chilling will start again from the beginning.
If power is interrupted during a storage operation when power is restored the storage operation will be reset.
If power is interrupted while in “stand-by” mode when power is restored the device will be in the same state.

The display

In the “on” state, during normal operation, the display shows:

  • the amount of time remaining for a timed blast chilling operation, if this is ongoing
  • the temperature measured by the pin probe if a set-temperature chilling operation is ongoing
  • the temperature of the cabinet, if storage is ongoing.

In “standby” mode, during normal operation, the display shows the temperature of the cabinet for ½ s every 3 s.

Defrosting and the evaporator fan

The service controlled by relay K2 depends on parameter u0:

  •  if u0 = 0, the service controlled by relay K2 will be defrosting (electrical defrosting; the evaporator fan is not controlled)
  • if u0 = 1, the service controlled by relay K2 will be the evaporator fan (defrost stopping the compressor):
    – during blast chilling, the operation of the evaporator fan depends on parameter F0
    – during storage, the operation of the evaporator fan depends on the parameter F2
    – the evaporator fan is started during defrosting.
    In “standby” mode it is only possible to activate manual defrosting; if the service controlled by relay K2 is the evaporator fan (parameter u0 = 1), during defrosting the evaporator fan will be switched on, and during drip-draining, this will be switched off.

To start defrosting in manual mode:

  • ensure no procedure is running
  • press EVCO EVK802 Digital Controller - icon 1for 4 s.

Defrosting is never activated during blast-chilling.
Defrosting occurs periodically during storage; it is possible to start defrosting manually.

Viewing the status of the compressor and the evaporator fan

To view the compressor status:

  • ensure no procedure is running
  • press:EVCO EVK802 Digital Controller - icon 1 the display will show the first available label:
    – if the display shows “C-1”, the compressor will be switched on
    – if the display shows “C-0”, the compressor will be switched off
    – if the display shows “C-P”, compressor protection will be ongoing (parameters C0, C1, C2, and i7).
    To view the status of the evaporator fan:
  •  ensure no procedure is running
  • press EVCO EVK802 Digital Controller - icon 1 twice: the display will show the first available label:
    – if the display shows “F-1”, the evaporator fan will be switched on
    – if the display shows “F-0”, the evaporator fan will be switched off
    – if the display shows “F-P”, then evaporator fan deferred activation will be ongoing (parameter F8).
    To exit the procedure:
  • Press EVCO EVK802 Digital Controller - icon 1until the display shows the ongoing status value (see paragraph 2.2), or leave for 15 s.
    If the service controlled by relay K2 is defrosting (parameter u0 = 0), labels “F-1”, “F-0” and “F-P” will not be displayed.
Buzzer mute
  • ensure no procedure is running
  • press any key (the first keypress does not trigger the associated effect).

OPERATIONAL CYCLES

Introductory information

The device has the following operational cycles:

  • timed positive chilling and storage
  • timed negative chilling and storage
  • set-temperature positive chilling and storage
  • set-temperature negative chilling and storage.
    Set-temperature cycles are preceded by a test step in order to check the correct insertion of the pin probe (see paragraph 3.6).
    To re-start using the same settings as the last cycle run:
  • ensure that the device is in “stand-by” mode, that no procedures are running and that another cycle has not been selected
  • press EVCO EVK802 Digital Controller - icon 22 s: the display will show the label of the last cycle run
  • press EVCO EVK802 Digital Controller - icon 2within 60 s: in the case of a timed cycle, the display will show the duration of the blast chilling step (in minutes), or in the case of a set-temperature cycle, the set target temperature
  • pressEVCO EVK802 Digital Controller - icon 1 or EVCO EVK802 Digital Controller - icon 3within 15 s to change the value (the setting re- mains active until another cycle is selected, when the value r1, r2, r3, or r4 is restored)
  • pressEVCO EVK802 Digital Controller - icon 2 within 15 s: the cycle will be activated.
  • pressEVCO EVK802 Digital Controller - icon 2 within 60 s: in the case of a timed cycle, the display will
    show the duration of the blast chilling step (in minutes) or in the case of a set-temperature cycle, the set target tempera­ture
  • press EVCO EVK802 Digital Controller - icon 1or EVCO EVK802 Digital Controller - icon 3within 15 s to change the value (the setting remains active until another cycle is selected when the value rl, r2, r3, or r4 is restored)
  • press within 15 s: the cycle will be activated.
 Timed positive blast chilling and storage cycle

To start the cycle

• ensure the device is in “stand-by” mode and no procedures are running
• press EVCO EVK802 Digital Controller - icon 3to select “PoS” and ensure the LEDEVCO EVK802 Digital Controller - icon 4 is flashing
• pressEVCO EVK802 Digital Controller - icon 2 within 15 s: the display will show the duration of the blast chilling step (in minutes)
• press EVCO EVK802 Digital Controller - icon 1or within 15 s to change the value (the setting re- mains active until another cycle is selected, when the value assigned by parameter r1 is restored)
• pressEVCO EVK802 Digital Controller - icon 2: the display will show the chilling operational setpoint (in °C/°F) and the LEDEVCO EVK802 Digital Controller - icon 5 will flash
• press EVCO EVK802 Digital Controller - icon 1orEVCO EVK802 Digital Controller - icon 3 within 15 s to change the value (the setting re- mains active until another cycle is selected, when the value assigned by parameter r7 is restored)
• pressEVCO EVK802 Digital Controller - icon 2 within 15 s: the cycle will be activated.

Also, look at parameters RB and E0.

During chilling:

  • the display shows the residual chilling time remaining
  • the LEDEVCO EVK802 Digital Controller - icon 4 is on
  • parameter r1 sets the chilling time duration
  • parameter r7 sets the operational setpoint
  • PressEVCO EVK802 Digital Controller - icon 3 several times to:
    – display the message “PoS”
    – display the cabinet temperature
    – exit the procedure, or leave for 15 s.

Once the chilling period has elapsed:

  • the device switches to storage mode
  • the display shows the message “End”
  • the buzzer sounds for the period of time set by parameter AA
  • press any key to mute the buzzer; press once more to cancel the message “End”.

During storage:

  • the display shows the cabinet temperature
  • the LEDsEVCO EVK802 Digital Controller - icon 4 and EVCO EVK802 Digital Controller - icon 5are on
  • the parameter r9 sets the operational setpoint
  • PressEVCO EVK802 Digital Controller - icon 3 several times to:
    – display the message “PoS”
    – exit the procedure, or leave for 15 s.

To interrupt the cycle:

  • press EVCO EVK802 Digital Controller - icon 2for 2 s.
Timed negative chilling and storage cycle

To start the cycle:

  • ensure the device is in “stand-by” mode and no procedures are running
  • Press EVCO EVK802 Digital Controller - icon 3to select “nEg” and ensure the LEDEVCO EVK802 Digital Controller - icon 4 is flashing
  • press EVCO EVK802 Digital Controller - icon 2within 15 s: the display will show the duration of the blast chilling step (in minutes)
  • press EVCO EVK802 Digital Controller - icon 1orEVCO EVK802 Digital Controller - icon 3 within 15 s to change the value (the setting re- mains active until another cycle is selected, when the value assigned by parameter r2 is restored)
  • pressEVCO EVK802 Digital Controller - icon 2: the display will show the chilling operational setpoint (in °C/°F) and the LEDEVCO EVK802 Digital Controller - icon 5 will flash
  • press EVCO EVK802 Digital Controller - icon 1or EVCO EVK802 Digital Controller - icon 3within 15 s to change the value (the setting re- mains active until another cycle is selected, when the value assigned by parameter r8 is restored)
  • press EVCO EVK802 Digital Controller - icon 2within 15 s: the cycle will be activated.
    Also, look at parameters RB and E0.

During chilling:

  • the display shows the residual chilling time remaining
  • the LED EVCO EVK802 Digital Controller - icon 4is on
  • parameter r2 sets the chilling time duration
  • parameter r8 sets the operational setpoint
  • pressEVCO EVK802 Digital Controller - icon 3several times to:
    – display the message “nEg”
    – display the cabinet temperature
    – exit the procedure, or leave for 15 s.

Once the chilling period has elapsed:

  • the device switches to storage mode
  • the display shows the message “End”
  • the buzzer sounds for the period of time set by parameter AA
  • press any key to mute the buzzer; press once more to cancel the message “End”.

During storage:

  • the display shows the cabinet temperature
  • the LEDs EVCO EVK802 Digital Controller - icon 4are on
  • the parameter RA sets the operational setpoint
  • Press EVCO EVK802 Digital Controller - icon 3 several times to:
    – display the message “nEg”
    – exit the procedure, or leave for 15 s.

To interrupt the cycle:

  •  press EVCO EVK802 Digital Controller - icon 2for 2 s.

Set-temperature positive blast chilling and storage cycle

To start the cycle:

  • ensure the device is in “stand-by” mode and no procedures are running

• press EVCO EVK802 Digital Controller - icon 3to select “PoS” and ensure the LEDEVCO EVK802 Digital Controller - icon 6 is flashing
• press EVCO EVK802 Digital Controller - icon 2within 15 s: the display will show the blast chilling endpoint temperature
• press EVCO EVK802 Digital Controller - icon 1orEVCO EVK802 Digital Controller - icon 3 within 15 s to change the value (the setting re- mains active until another cycle is selected, when the value assigned by parameter r3 is reset)
• pressEVCO EVK802 Digital Controller - icon 2: the display will show the chilling operational setpoint (in °C/°F) and the LEDEVCO EVK802 Digital Controller - icon 5 will flash
• press EVCO EVK802 Digital Controller - icon 1orEVCO EVK802 Digital Controller - icon 3 within 15 s to change the value (the setting re- mains active until another cycle is selected, when the value assigned by parameter r7 is restored)
• press EVCO EVK802 Digital Controller - icon 2within 15 s: the cycle will be activated.

Also, look at parameters RB and E0.

Prior to starting the cycle:

  • the test is run in order to check correct pin probe insertion (see paragraph 3.6):
    – if the outcome of the test is positive, the cycle will be started
    – if the outcome of the test is negative, the cycle will be started in timed mode.

During chilling:

  • the display shows the temperature measured by the pin probe
  • the LED EVCO EVK802 Digital Controller - icon 6is on
  • the parameter r3 sets the blast chilling endpoint temperature
  • the parameter r5 sets the maximum chilling time duration
  • the parameter r7 sets the operational setpoint
  • Press EVCO EVK802 Digital Controller - icon 3several times to:
    – display the maximum residual chilling time remaining
    – display the message “PoS”
    – display the flashing cabinet temperature
    – exit the procedure, or leave for 15 s.

If the temperature measured by the pin probe reaches the chilling endpoint temperature prior to the expiry of the maximum chilling time duration:

  • the device will switch to storage mode
  • the display will show the message “End”
  • the buzzer will sound for the period of time set by parameter AA
  • press any key to mute the buzzer; press once more to cancel the message “End”.

If the temperature measured by the pin probe does not reach the chilling endpoint temperature prior to the expiry of the maximum chilling time duration:

  • chilling will continue
  • the LED EVCO EVK802 Digital Controller - icon 6will flash and the LED EVCO EVK802 Digital Controller - icon 7will be on
  • the buzzer will sound
  • PressEVCO EVK802 Digital Controller - icon 3 several times to:
    – mute the buzzer
    – display the time elapsed since the maximum chilling time expired
    – display the cabinet temperature
    – display the message “PoS”
    – exit the procedure, or leave for 15 s
  • when the temperature measured by the pin probe reaches the chilling endpoint temperature:
    – the device switches to storage mode
    – the LEDEVCO EVK802 Digital Controller - icon 6 will continue to flash and the LEDEVCO EVK802 Digital Controller - icon 7 will stay on
    – the display will show the message “End”
    – the buzzer will sound for the period of time set by parameter AA
    – press any key to mute the buzzer; press once more to cancel the message “End”.

During storage:

  • the display shows the cabinet temperature
  • if chilling had a positive outcome, the LEDs EVCO EVK802 Digital Controller - icon 6and EVCO EVK802 Digital Controller - icon 5 will be on; if chilling had a negative outcome, the LEDs EVCO EVK802 Digital Controller - icon 5and EVCO EVK802 Digital Controller - icon 7 will be on and the LEDEVCO EVK802 Digital Controller - icon 6 will flash
  • the parameter r9 sets the operational setpoint
  • PressEVCO EVK802 Digital Controller - icon 3 several times to:
    – display the message “PoS”
    – exit the procedure, or leave for 15 s.

To interrupt the cycle:

  • pressEVCO EVK802 Digital Controller - icon 2for2 s.
Set-temperature negative chilling and storage cycle

To start the cycle:

  • ensure the device is in “stand-by” mode and no procedures are running
  • Press EVCO EVK802 Digital Controller - icon 3to select “nEg” and ensure the LEDEVCO EVK802 Digital Controller - icon 6 is flashing
  • pressEVCO EVK802 Digital Controller - icon 2 within 15 s: the display will show the blast chilling endpoint temperature
  • press EVCO EVK802 Digital Controller - icon 1orEVCO EVK802 Digital Controller - icon 3 within 15 s to change the value (the setting re- mains active until another cycle is selected, when the value assigned by parameter r4 is restored)
  • press:EVCO EVK802 Digital Controller - icon 2 the display will show the chilling operational setpoint (in °C/°F) and the LEDEVCO EVK802 Digital Controller - icon 5 will flash
  • pressEVCO EVK802 Digital Controller - icon 1 orEVCO EVK802 Digital Controller - icon 3 within 15 s to change the value (the setting remains active until another cycle is selected when the value assigned by parameter r8 is restored)
  • pressEVCO EVK802 Digital Controller - icon 2 within 15 s: the cycle will be activated.

Also, look at parameters RB and E0.

Prior to starting the cycle:

  • the test is run in order to check correct pin probe insertion (see paragraph 3.6):
    -if the outcome of the test is positive, the cycle will be started
    – if the outcome of the test is negative, the cycle will be started in timed mode

During chilling:

  • the display shows the temperature measured by the pin probe
  • the LED EVCO EVK802 Digital Controller - icon 6is on
  • the parameter r4 sets the chilling endpoint temperature
  • the parameter r6 sets the maximum chilling time duration
  • the parameter r8 sets the operational setpoint
  • pressEVCO EVK802 Digital Controller - icon 3several times to:
    – display the maximum residual chilling time remaining
    – display the message “nEg”
    – flashing display the cabinet temperature
    – exit the procedure, or leave for 15 s.

If the temperature measured by the pin probe reaches the chilling endpoint temperature prior to the expiry of the maximum chilling time duration:

  • the device will switch to storage mode
  • the display will show the message “End”
  • the buzzer will sound for the period of time set by parameter AA
  • press any key to mute the buzzer; press once more to cancel the message “End”.

If the temperature measured by the pin probe does not reach the chilling endpoint temperature prior to the expiry of the maximum chilling time duration:

  • chilling will continue
  • the LEDEVCO EVK802 Digital Controller - icon 6 will flash and the LED will be on
  • the buzzer will sound
  • Press EVCO EVK802 Digital Controller - icon 3several times to:
    – mute the buzzer
    – display the time elapsed since the maximum chilling time expired
    – display the cabinet temperature
    – display the message “nEg”
    – exit the procedure, or leave for 15 s
  • when the temperature measured by the pin probe reaches the chilling endpoint temperature:
    – the device will switch to storage mode
    – the LED EVCO EVK802 Digital Controller - icon 6will continue to flash and the LED EVCO EVK802 Digital Controller - icon 7will continue to stay on
    – the display will show the message “End”
    – the buzzer will sound for the period of time set by parameter AA
    – press any key to mute the buzzer; press once more to cancel the message “End”.

During storage:

• the display shows the cabinet temperature
• if chilling had a positive outcome, the LEDs EVCO EVK802 Digital Controller - icon 6and EVCO EVK802 Digital Controller - icon 5 will be on; if chilling had a negative outcome, the LEDsEVCO EVK802 Digital Controller - icon 5 and EVCO EVK802 Digital Controller - icon 7will be on and the LEDEVCO EVK802 Digital Controller - icon 6 will flash
• the parameter RA sets the operational setpoint
• pressEVCO EVK802 Digital Controller - icon 3 several times to:
– display the message “nEg”
– exit the procedure, or leave for 15 s.

To interrupt the cycle:

  • pressEVCO EVK802 Digital Controller - icon 2for2 s.
Test to check correct pin probe insertion

Set-temperature cycles are preceded by a test step in order to check correct pin probe insertion.
The test has two stages:

  • if the outcome of the first stage is positive, the second will not be run
  • if the outcome of the first stage is negative, the second will be run.

The outcome of the first stage is positive if “the temperature measured by the pin probe – the temperature of the cabinet” is greater than the value set by parameter RC at least 3 times out of 5 (the comparison is made every 10 s); if parameter RC is set to 0, neither the first nor second stages will be run.

The outcome of the second stage is positive if the difference “temperature measured by the pin probe – temperature of the cabinet” is greater by at least 1ºC/1ºF (with respect to the previous comparison) at least 6 times out of 8 (the comparison is made every “rd/8 s”).

If the outcome of the test is positive:

  • the cycle will be activated.

the cycle will be activated:

  • the cycle will be started in timed mode
  • the LED EVCO EVK802 Digital Controller - icon 6will flash.

If power is interrupted during the test, when power is restored, the test will start again from the beginning.

SETTINGS

The temporary setting of operational setpoint during storage

• ensure the device is in “stand-by” mode and no procedures are running
• pressEVCO EVK802 Digital Controller - icon 2: the LED EVCO EVK802 Digital Controller - icon 5will flash
• press EVCO EVK802 Digital Controller - icon 1orEVCO EVK802 Digital Controller - icon 3within15 s
• pressEVCO EVK802 Digital Controller - icon 2or leave for 15 s.

The setting remains active until another operational cycle is selected when the value assigned by parameter r9 or ra is restored.

Setting the configuration parameters

The parameters are arranged on two levels.

To access the first level:

  • ensure the device is in “stand-by” mode and no procedures are running
  •  press EVCO EVK802 Digital Controller - icon 1and EVCO EVK802 Digital Controller - icon 3for 4 s: the display will show “PA”

To access the second level:

  • access the first level
  • PressEVCO EVK802 Digital Controller - icon 1 orEVCO EVK802 Digital Controller - icon 3 select “PA”
  • press EVCO EVK802 Digital Controller - icon 2
  • press EVCO EVK802 Digital Controller - icon 1orEVCO EVK802 Digital Controller - icon 3 within 15 s to set “-19”
  • pressEVCO EVK802 Digital Controller - icon 2 or leave for 15 s
  • press EVCO EVK802 Digital Controller - icon 1andEVCO EVK802 Digital Controller - icon 3 for4 s: the display will show “CA1”.

To select a parameter:

  • pressEVCO EVK802 Digital Controller - icon 1 orEVCO EVK802 Digital Controller - icon 3

To modify a parameter:

  • pressEVCO EVK802 Digital Controller - icon 2
  • pressEVCO EVK802 Digital Controller - icon 1 or EVCO EVK802 Digital Controller - icon 3within 15 s
  • pressEVCO EVK802 Digital Controller - icon 2 or leave for 15 s.

To exit the procedure:

  • press EVCO EVK802 Digital Controller - icon 1andEVCO EVK802 Digital Controller - icon 3 for 4 s, or leave for 60 s.

I interrupt the device power supply after altering the parameters.

Resetting configuration parameter default values
  • ensure the device is in “stand-by” mode and no procedures are running
    press EVCO EVK802 Digital Controller - icon 1andEVCO EVK802 Digital Controller - icon 3 for 4 s: the display will show “PA”
  • pressEVCO EVK802 Digital Controller - icon 2
  • press EVCO EVK802 Digital Controller - icon 1or EVCO EVK802 Digital Controller - icon 3within 15 s to set “743”
  • press EVCO EVK802 Digital Controller - icon 1orEVCO EVK802 Digital Controller - icon 3 leave for 15 s
  • press EVCO EVK802 Digital Controller - icon 1and EVCO EVK802 Digital Controller - icon 3per 4 s: the display will show “dEF”
  • pressEVCO EVK802 Digital Controller - icon 2
  • press EVCO EVK802 Digital Controller - icon 1or EVCO EVK802 Digital Controller - icon 3within 15 s to set “149”
  • press or leave for 15 s: the display will flash “dEF” for 4 s, after which the device will exit the procedure
  • interrupt the power to the device.

Ensure that the parameter default values are appropriate, particularly if the probes are NTC type.

SIGNALS

Signals
LEDMESSAGE
EVCO EVK802 Digital Controller - icon 4timed chilling LED
  • if on and the LEDEVCO EVK802 Digital Controller - icon 5 is off, a timed chilling operation is ongoing
  • if on and the LEDEVCO EVK802 Digital Controller - icon 5 is also on, a post-timed-chilling storage operation is ongoing
  • if flashing, a timed chilling and storage cycle will have been selected
EVCO EVK802 Digital Controller - icon 6set-temperature chilling LED
  •  if on and the LEDEVCO EVK802 Digital Controller - icon 5 is off, a set-temperature chilling operation is ongoing
  • if on and the LEDEVCO EVK802 Digital Controller - icon 5 is also on, a post-set-temperature chilling storage operation will be ongoing
  • if flashing, a set-temperature chilling and storage cycle will have been selected
  • if it is on for ½ s every 3 s, the test to verify correct pin probe insertion will be ongoing
  • if flashing, and the LED EVCO EVK802 Digital Controller - icon 4is on, then the test to verify correct pin probe insertion will have had a negative outcome (parameters rc and rd) and the cycle will have been started in timed mode; see paragraph 3.6
  •  if flashing, and the LEDEVCO EVK802 Digital Controller - icon 7 is on, the chilling stage will have had a negative outcome, and so this will continue
  •  if flashing, and the LEDs EVCO EVK802 Digital Controller - icon 5and EVCO EVK802 Digital Controller - icon 7 are on, the chilling stage will have had a negative outcome, the device will have switched to storage mode and this will be ongoing
EVCO EVK802 Digital Controller - icon 5storage LED
  • if on, a storage operation will be ongoing
  • if flashing, then the operational setpoint will be being modified while a storage operation is ongoing (see paragraph 4.1)

EVCO EVK802 Digital Controller - icon 5ºC

alarm LED if on, an alarm is ongoing degree Celsius LED
if on, the unit of measurement for temperature in degrees Celsius (parameter P2)

ºF

degree Fahrenheit LED
if on, the unit of measurement for temperature is degrees Fahrenheit (parameter P2)

decimal point

minute LED
if flashing, the unit of measurement of magnitude displayed is the minute

CODE

MESSAGE

– d –

defrosting or drip draining is ongoing

ALARMS

Alarms
CODEMESSAGE
ALMinimum temperature alarm Remedies:
• check the cabinet temperature
• check parameters A1 and A2Consequences:
• the device will continue to function normally
AHMaximum temperature alarm Remedies:
• check the cabinet temperature
• check parameters A3 and A4Consequences:
• the device will continue to function normally
idMicro-port input alarm (only in “stand-by” mode and if parameter i0 is set to 0 or 1) Remedies:
• check the causes which activated the input
• check parameters i0 and i1Consequences:
• the outcome set by parameter i0
iACompressor protection input alarm (only if parameter i0 is set to 2) Remedies:
• check the causes which activated the input
• check parameters i0 and i1Consequences:
• the compressor will be shut down

When the cause that triggered the alarm has been resolved, the device restores normal operation.

INTERNAL DIAGNOSTICS

 Internal diagnostics
CODEMESSAGE
Pr1Cabinet probe error Remedies:
• see P0 parameter
• check probe integrity
• check the probe-device connection
• check the cabinet temperatureConsequences if the error occurs while in “stand-by” mode:
• if parameter C11 is set to 0, it will not be possible to start any of the cycles
• if parameter C11 is set to 1, the pin probe will function as the cabinet probe, and only timed cycles will be allowed to start

Consequences if the error occurs during a timed chilling operation:
• if parameter C11 is set to 0, the cycle will be interrupted
• if parameter C11 is set to 1, the pin probe will function as the cabinet probe and the chilling operation will continue

Consequences if the error occurs during a set-temperature chilling operation:

• if parameter C11 is set to 0, the cycle will be interrupted
• if parameter C11 is set to 1, the pin probe will function as both the cabinet probe and pin probe and the chilling operation will continue Consequences if the error occurs during a storage operation:
• parameter C11 is set to 0, the compressor activity will depend on parameters C4, C5 and C6
• if parameter C11 is set to 1, the pin probe will function as the cabinet probe and the storage operation will continue

Pr2Pin probe error Remedies:
• the same as for the previous case, but in relation to the pin probeConsequences if the error occurs while in “stand-by” mode:
• only timed operation cycles will be allowed to start

Consequences if the error occurs during a timed chilling operation:
• chilling will continue

Consequences if the error occurs during a set-temperature chilling operation:
• chilling will continue in timed mode

Consequences if the error occurs during storage mode:
• storage will continue

TECHNICAL DATA

Technical data

Case: grey self-extinguishing.

Front panel protection classification (use copper conduc­tors only): IP 65.

Connections: Screw terminal blocks (power supply, inputs, and out­puts), 6 pin connector (serial port; available on request); extractable terminal block (power supply, inputs, and outputs) available on re­quest.

Operating temperature: from 0 to 55 °C ( I 0 90% relative humid­ity, without condensation).

Power supply: 230 VAC, 50/60 Hz, 3 VA (nominal); 115 VAC or 12-24 VAC/DC or 12 VAC/DC by request.

Insulation class: 2.
Alarm buzzer: integrated.
Sensor Inputs: 2 (cabinet probe and pin probe) for PTC/NTC probes.
Digital Inputs: I (door switch/multifunction) for NA/NC contact (clean contact, 5 V I mA).
Sensor range: from -50.0 to 150.0 °C for PTC probes, from -40.0 to 105.0 °C for NTC probes.
Sensitivity: 0. I °C/1°C/1°F.

Digital outputs: 2 relays:

  • compressor relay: 16 A res. @250 VAC, 5 FLA, 30 LRA (NA contact) versions with 12 VAC/DC and 12-24 VAC/DC; 8 A res. @ 250 VAC, 2 FLA, 12 LRA otherwise
  • defrosting/evaporator fan relay: 8 A res.

@250 VAC, 2 FLA, 12 LRA (exchange contacts).

The maximum permitted current on loads is 10 A.

Serial port: port for communicating with the monitoring system (by means of a serial interface, via TTL, using the MODBUS communication protocol) or with the programming key; available on request.

CONFIGURATION PARAMETERS

First level configuration parameters
PARAMMIN.MAX.M.U.DEF.MAIN CONTROLLER
r00,115,0°C/°F (I)2,0parameter r7, r8, r9, and Ra differential
rl1600min90timed positive blast chilling duration
r21600min240timed negative blast chilling duration
r3-99,099,0°C/°F (I)3,0positive blast chill end-point temperature (temperature detected by the pin probe)
r4-99,099,0°C/°F (I)-18,0negative blast chill end-point temperature (temperature detected by the pin probe)
r51600min90set-temperature positive blast chilling maximum duration
r61600min240set-temperature negative blast chilling maximum duration
r7-99,099,0°C/°F II)0,0positive blast chilling operational setpoint (cabinet temperature)
r8-99,099,0°C/°F (I)-40,0negative blast chilling operational setpoint (cabinet temperature)
r9-99,099,0°C/°F (I)2,0postpositive blast chill storage operational setpoint (cabinet temperature)
rA-99,099,0°C/°F (I)-20,0post negative blast chill storage operational setpoint (cabinet temperature)
Second level configuration parameters
PARAMMIN.MAX.M.U.DEF.SENSOR INPUTS
CAI-25,025,0°C/°F (1)0,0cabinet probe offset
CA2-25,025,0°C/°F (1)0,0pin probe offset
PO0I– – –0probe type

0 = FTC
I = NTC

P10I– – –Idegree Celsius decimal point (for the quantity displayed during normal operation)
I = YES
P20I– – –0unit of temperature measurement (2)
0 = °C
I = °F
P30I– – –Ipin probe enabling
I = YES
PARAMMIN.MAX.M.U.DEF.MAIN CONTROLLER
r00,115,0°C/°F (I)2,0parameter r7, r8, r9, and Ra differential
rl1600min90timed positive blast chilling duration
r21600min240timed negative blast chilling duration
r3-99,099,0°C/°F (I)3,0positive blast chill end-point temperature (temperature detected by the pin probe)
r4-99,099,0°C/°F (I)-18,0negative blast chill end-point temperature (temperature detected by the pin probe)
r51600min90set-temperature positive blast chilling maximum duration
r61600min240set-temperature negative blast chilling maximum duration
r7-99,099,0°C/°F (I)0,0positive blast chilling operational setpoint (cabinet temperature)
r8-99,099,0°C/°F ( I )-40,0negative blast chilling operational setpoint (cabinet temperature)
r9-99,099,0°C/°F ( I )2,0postpositive blast chill storage operational setpoint (cabinet temperature)
rA-99,099,0°C/°F ( I )-20,0post negative blast chill storage operational setpoint (cabinet temperature)
rb02– – –Ikind of cycle enabled

0 = positive chilling
I = positive chilling and negative chilling
2 = negative chilling

rc0,099,0°C/°F (I)5,0“temperature detected by the pin probe – temperature of the cabinet” difference for the first stage of the test to check correct pin probe insertion (see paragraph 3.6)

0 = test will not be performed (neither the first nor second stages)

rd199s60duration of the second stage of the test to check correct pin probe insertion (see paragraph 3.6J
PARAM.MIN.MAX.M.U.DEFCOMPRESSOR PROTECTION
C00240min0operational cycle deferred compressor start-up; deferred compressor power restoration also follow­ing a power interruption during an operational cycle
C 10240min5minimum elapsed time period between two consecutive compressor start-up operations
C20240min3minimum compressor shut-down time
C30240s0minimum compressor start-up time
C40240minI 0storage cabinet probe error compressor shut-down duration; see also C5 and C6 (only if CII = 0)
C50240minI 0positive storage cabinet probe error compressor start-up duration; see also C4 (only if CIT = 0)
C60240min20negative storage cabinet probe error compressor start-up duration; see also C4 (only if CII = 0)
C I 10I0pin probe operation during cabinet probe error

0 = pin probe
IF THE ERROR OCCURS IN “STAND-Br MODE – it will not be possible to start any of the cycles

IF THE ERROR OCCURS DURING A TIMED OR SET TEMPERATURE BLAST CHILLING OPERATION – the cycle will be interrupted

IF THE ERROR OCCURS DURING A STORAGE OPERATION – compressor activity will depend on parameters C4, C5 and C6

I = both pin probe and cabinet probe
IF THE ERROR OCCURS WHILE IN “STAND-BY MODE – the pin probe will operate as a cabinet probe and it will only be possible to start timed cycles

IF THE ERROR OCCURS DURING TIMED BLAST CHILLING – the pin probe will operate as a cabinet probe and chilling will continue

IF THE ERROR OCCURS DURING SET-TEMPERATURE BLAST CHILLING – the pin probe will operate as both a pin probe and a cabinet probe and chilling will continue’ it is recommended to set the 10 parameters to 2 (COMPRESSOR PROTECTION)

IF THE ERROR OCCURS DURING A STORAGE OPERATION – the pin probe will operate as a cabinet probe and storage will continue

PARAM.MIN.MAX.M.U.DEFDEFROST
d0099h8defrost interval (3)
0 = regular periodic defrosting will never be enabled
d3099min30defrost duration
0 = defrosting will never be enabled
d7015min2drip-drain duration
pARAMMIN.MAX.M.U.DEF.TEMPERATURE ALARMS (4)
Al0,099.0°C/°F (1)10.0the temperature below which the minimum temperature alarm is activated: see also A2 (5)
A2011minimum temperature alarm type

0 = no alarm

1 = depending on parameters r9 and rA (or ‘r9 – AI’ and “rA – An

A40.099.0°C/°F (1)10,0the temperature above which the maximum temperature alarm is activated: see also AS (5)
AS011maximum temperature alarm type

0 = no alarm

I = depending on parameters r9 and rA (or 19 + A4′ and “rA + M”)

A60240min15storage operation start-up temperature alarm delay
A70240min15temperature alarm delay
A80240min15drip-drain end maximum temperature alarm delay 16)
A90240min1 5door switch input deactivation maximum temperature alarm delay (only if i0 = 0 or 1) (7)
AA0240s5blast chill completion buzzer duration
PARAMMIN.MAX.M.U.DEE.EVAPORATOR FAN (only if u0 = I)
FO022evaporator fan activity during chilling

0 = off
I = on
2 = in parallel with the compressor

F2021evaporator fan activity during storage

0 = off
I = on
2 = in parallel with the compressor

F8099min0evaporator fan start-up delay following defrost cycle start
PARAMMIN.MAX.M.U.DEEDIGITAL INPUTS
i0041digital input operation

0 = DOOR SWITCH  – in this case parameters I 1, i2, and i3 assume significance: enabling input will cause the evaporator fan to be shut down (at most for the period of time set by i3 or until input will be disabled) 181 (91

1 = DOOR SWITCH INPUT – in this case, parameters I 1, i2, and i3 assume significance: enabling input will cause the compressor and evaporator fan to be shut down (at most for the period of time set by i3 or until input will be disabled) (8) (9)

2 = COMPRESSOR PROTECTION – in this case, parameters I 1 and i7 assume significance: the compressor will be shut-down, the display will flash code 1A” and the buzzer will be activated (until the input will be deactivated)

3 = DOOR SWITCH INPUT – in this case, parameters I 1, i2, and i3 assume significance: enabling input will cause the evaporator fan to be shut down (at most for the period of time set by i3 or until input will be disabled) (8)

4 = 2aQIILISOICLUNELEC – in this case, parameters I 1, i2, and i3 assume significance: enabling input will cause the compressor and evaporator fan to be shut down (at most for the period of time set by i3 or until input will be disabled) 181 (10)

 i1022digital input contact type

0 = NA (input active with contact closed)
1 = NC (input active with contact open)
2 = no input

i2-1120min30door switch input alarm activation delay (solo se i0 = 0 o I) -1= the alarm will not sound
i3-1120min15door switch input activation effect maximum duration (only if i0 = 0 or I) -1= the effect will last until the input will be disabled
i70120min0compressor protection deactivation compressor delay (only if i0 = 2)
PARAMMIN.MAX.M.U.DEF.DIGITAL OUTPUTS
u0011service controlled by relay K2 (see paragraph 2.3)

0 = defrosting
1 = evaporator fan

PARAMMIN.MAX.M.U.DEF.SERIAL NETWORK (MODBUS)
LA1247247device address
Lb032baud rate

0 = 2.400 baud
1 = 4.800 baud
2 = 9.600 baud
3 = 19.200 baud

LP022parity

0 = none (no parity)
1 = odd
2 = even

PARAMMIN.MAX.M.U.DEE.ENABLING
E0031quantity modifiable quickly before starting the cycle

0 = no quantity
1 = if you have selected a timed chilling cycle, the chilling duration
if you have selected a set-temperature chilling cycle, the chilling end-point temperature

2 = if you have selected a timed chilling cycle, the chilling duration, and the chilling operational setpoint
if you have selected a set-temperature chilling cycle, the chilling operational setpoint

3 = if you have selected a timed chilling cycle, the chilling duration, and the chilling operational setpoint
if you have selected a set-temperature chilling cycle, the chilling end-point temperature, and the chilling operational setpoint

 E90 11reserved
  1. the unit of measurement depends on parameter P2
  2. set the parameters relating to the controllers appropriately after altering parameter P2
  3. the device stores the defrost interval count every 30 minutes; altering parameter d0 has the effect of concluding the previous defrost interval or
    manual defrost activation
  4. the temperature alarm functions are only enabled during storage operations
  5. the parameter differential is 2.0 ºC/4 ºF
  6. there are no temperature alarms during defrosting and drip draining, if they occur following defrost activation
  7. there is no maximum temperature alarm while door switch input is enabled if occurring after input activation
  8. the evaporator fan will be shut down providing defrosting is not ongoing
  9. the compressor and/or ventilator fan are shut down 10 s after input activation
  10.  the compressor is shut down 10 s after input activation.

SONY MDR-RF855RK Wireless Stereo Headphone System - warning The device must be disposed of in accordance with local regulations pertaining to the collection of electrical and electronic appliances.

EVCO logo

EVCO S.p.A.
Via Mezzaterra 6, 32036 Sedico Belluno ITALY
Phone +39-0437-852468
Fax +39-0437-83648
[email protected]
www.evco.it

This document belongs to Evco; unless you are authorized by Evco, you can not publish it.
Evco does not take any responsibility for features, technical data, and possible mistakes related to this document or coming by its use.
Evco does not take any responsibility for damages coming from the non-observance of the additional information.
Evco reserves the right to make any change without prior notice and at any time without prejudice to the basic safety and operating features.

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals