Evco Ev3143 Advanced Controller Instruction Manual

Evco Ev3143 Advanced Controller Instruction Manual

EVCO - Logo

EV3143
Controller with two independent regulators for refrigerated milk storage units and ice cream batch freezers

EVCO EV3143 Advanced Controller - Cover

  • 230 VAC or 115 VAC power supply (according to the model)
  • 2 analogue inputs (PTC/NTC)
  • door switch/multi-purpose input
  • main relay 16 A res. @ 250 VAC
  • alarm buzzer
  • TTL MODBUS slave port for BMS
  • hot or cold mode regulation.

MEASUREMENTS AND INSTALLATION

Measurements in mm (inches). To be fitted to a panel, snap-in brackets provided.

EVCO EV3143 Advanced Controller - MEASUREMENTS AND INSTALLATION

INSTALLATION PRECAUTIONS

  • the thickness of the panel must be between 0.8 and 2.0 mm (1/32 and 1/16 in)
  • ensure that the working conditions are within the limits stated in the TECHNICAL SPECIFICATIONS section
  • do not install the device close to heat sources, equipment with a strong magnetic field, in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations, or shocks
  • in compliance with safety regulations, the device must be installed properly to ensure adequate protection from contact with electrical parts. All protective parts must be fixed in such a way as to need the aid of a tool to remove them.

ELECTRICAL CONNECTION

N.B.
• use cables of an adequate section for the current running through them
• to reduce any electromagnetic interference, locate the power cables as far away as possible from the signal cables.

EVCO EV3143 Advanced Controller - ELECTRICAL CONNECTION

P10OPERATIONPROBE 1PROBE 2LOAD 1LOAD 2LOAD 3
0controller with two independent regulatorsregulator 1regulator 2regulator 1regulator 2alarm
1controller for refrigerated milk storage unitstankauxiliarycompres- sorauxiliarybeater
2controller for ice cream batch freezerstankplatecompres- sorplate heatersbeater

PRECAUTIONS FOR ELECTRICAL CONNECTION

  • if using an electrical or pneumatic screwdriver, adjust the tightening torque
  • if the device is moved from a cold to a warm place, humidity may cause condensation to form inside. Wait for about an hour before switching on  the power
  • make sure that the supply voltage, electrical frequency, and power are within the set limits. See the section TECHNICAL SPECIFICATIONS
  • disconnect the power supply before carrying out any type of maintenance
  • do not use the device as a safety device
  • for repairs and for further information, contact the EVCO sales network.

FIRST-TIME USE

  1. Carry out the installation following the instructions given in the section MEASUREMENTS AND INSTALLATION.
  2. Power up the device as set out in the section ELECTRICAL CONNECTION: an internal test will startup.
    The test normally takes a few seconds; when it is finished the display will switch off.
  3. Configure the device as shown in the section Setting configuration parameters.
    PAR.DEF.PARAMETERMIN… MAX.
    SP10.0load 1 setpointr1… r2
    SP20.0load 2 setpointr12… r13
    SP30.0beater setpointr16… r17
    PO1type of probe0 = PTC 1 = NTC
    P20temperature measurement unit0 = °C 1 = °F
    P100operating logic0 = controller with two independent regulators
    1 = controller for refrigerated milk storage units
    2 = controller for ice cream batch freezers 1…

    Then check that the remaining settings are appropriate; see the section CONFIGURATION PARAMETERS.

  4. Disconnect the device from the mains.
  5. Make the electrical connection as shown in the section ELECTRICAL CONNECTION, without powering up the device.
  6. When connecting to an RS-485 network, connect the EVIF22TSX interface; see the relevant instruction sheets.
  7. Power up the device again.

USER INTERFACE AND MAIN FUNCTIONS

EVCO EV3143 Advanced Controller - USER INTERFACE AND MAIN FUNCTIONS

Switching the device on/off
  1. If POF = 1 (default), touch the ON/STAND-BY key for 4 s.
    If the device is switched on, the display will show the P5 value (“probe 1 temperature” default); if the display shows an alarm code, see the section ALARMS.
LEDONOFFFLASHING
compressor oncompressor off– compressor protection in progress
– setpoint being set
plate heaters onplate heaters offsetpoint being set
regulator 1 onregulator 1 off– load 1 protection in progress
– setpoint being set
defrost active
beater onbeater offsetpoint being set
alarm active and silenced –alarm active and not silenced
temperature displayed
regulator 2 onregulator 2 off– load 2 protection in progress
– setpoint being set
device offdevice ondevice being switched on/off

When 30 s have elapsed without the keys being pressed, the display will show the “Loc” label and the keypad will automatically lock.

Unlocking the keypad

Touch a key for 1 s: the display will show the label “UnL”.

Quick setting:
  • of setpoints (if P9 = 1 or 3)
  • beater switch on/off times (if P9 = 2 or 3)

Check that the keypad is not locked.

1.Touch the SET key: the display will show the label “SP1”.
2.Touch the UP or DOWN key within 15 s to set the load 1 setpoint value within the limits r1 and r2 (default “-50… 50”).
3.Touch the SET key: the display will show the label “SP2”.
4.Touch the UP or DOWN key within 15 s to set the load 2 setpoint value within the limits r12 and r13 (default “-50… 50”).
5.Touch the SET key: the display will show the label “SP3”.
6.Touch the UP or DOWN key within 15 s to set the beater setpoint value within the limits r16 and r17 (default “-50… 50”).
7.Touch the SET key: the display will show the label “t0”.
8.Touch the UP or DOWN key within 15 s to set the time the beater is switched off within the limits 0… 240 min.
9.Touch the SET key: the display will show the label “t1”.
10.Touch the UP or DOWN key within 15 s to set the time the beater is switched on within the limits 0… 240 min.
11.Touch the SET key (or take no action for 15 s).

Settings are temporary: when the device is switched back on (and after a power failure), it resets the values SP1, SP2, SP3, t0 and t1.

Starting up/interrupting batch freezing (if P10 = 2)

Check that the keypad is not locked.

  1. Touch the ON/STAND-BY key.
Manually switching on the beater (if P10 = 1)

Check that the keypad is not locked.

  1. Touch the DOWN key for 4 s.

The beater is switched on for time t1.

Activating manual defrost (if r5 and/or r19 = 0, default)

Check that the keypad is not locked.

  1. Touch the UP key for 4 s.
Silencing the buzzer (if Pbu = 2 or 3)

Touch a key.
If u4 = 1, the alarm output is also deactivated.

OPERATION

Controller with two independent regulators (P10 = 0, default)

Cold mode regulation regulator 1 (r5 = 0).

EVCO EV3143 Advanced Controller - OPERATION

Hot mode regulation regulator 1 (r5 = 1).

EVCO EV3143 Advanced Controller - OPERATION 2

Cold mode regulation regulator 2 (r10 = 0).

EVCO EV3143 Advanced Controller - OPERATION 3

Hot mode regulation regulator 2 (r10 = 1).

EVCO EV3143 Advanced Controller - OPERATION 4

Controller for refrigerated milk storage units (P10 = 1)

Compressor operation.

EVCO EV3143 Advanced Controller - Compressor operation

Beater operation set to t0 and t1 (r14 = 0).

EVCO EV3143 Advanced Controller - Controller for ice cream batch freezers (P10 = 2) 2

Beater operation set to r19, t0 and t1 if beater setpoint is not reached (r14 = 1).
Cold mode regulation beater (r19 = 0)

EVCO EV3143 Advanced Controller - Controller for ice cream batch freezers (P10 = 2) 3

Beater operation set to r19, t0 and t1 if beater setpoint is not reached (r14 = 1).
Hot mode regulation (r19 = 1).

EVCO EV3143 Advanced Controller - Controller for ice cream batch freezers (P10 = 2) 5

Controller for ice cream batch freezers (P10 = 2)

The batch freezing cycle consists of 4 phases:

  • heating
  • cooking
  • cooling
  • conservation.
Heating

The compressor remains off.
Plate heaters operation.
EVCO EV3143 Advanced Controller - HeatingBeater operation.
EVCO EV3143 Advanced Controller - Heating 2End of phase.
EVCO EV3143 Advanced Controller - End of phase

At the end of the phase the buzzer emits 10 beeps 1 s long.
If there is a power failure during the phase, it starts back up again from the beginning.

Cooking

The compressor remains off.
Plate heaters operation.
EVCO EV3143 Advanced Controller - CookingBeater operation.
EVCO EV3143 Advanced Controller - Cooking 2
End of phase.
EVCO EV3143 Advanced Controller - Cooking 3At the end of the phase the buzzer emits 10 beeps 1 s long.
If there is a power failure during the phase, it starts back up again from the beginning.

Cooling

Compressor operation.
EVCO EV3143 Advanced Controller - Cooling The plate heaters remain off.
Beater operation.
EVCO EV3143 Advanced Controller - Cooling 2

End of phase.
EVCO EV3143 Advanced Controller - Cooling 3At the end of the phase the buzzer emits 10 beeps 1 s long.
If there is a power failure during the phase:

  • the phase starts back up again from the beginning if (tank temperature after the powerfailure – tank temperature before the power failure) < PFd
  • the cycle starts back up again from the beginning of the heating phase if (tank temperature after the power failure tank temperature before the power failure) > PFd.
Conservation

Compressor operation.

EVCO EV3143 Advanced Controller - Compressor operation 2

The plate heaters remain off.
Beater operation.
EVCO EV3143 Advanced Controller - Conservation 2End of phase.

EVCO EV3143 Advanced Controller - Conservation 3

If there is a power failure during the phase:

  • the phase starts back up again from the beginning if (tank temperature after the power failure – tank temperature before the power failure) < PFd
  • the cycle starts back up again from the beginning of the heating phase if (tank temperature after the power failure
  • tank temperature before the power failure) > PFd.

ADDITIONAL FUNCTIONS

Viewing the temperatures detected by the probes

Check that the keypad is not locked.

1Touch the DOWN key for 4 s.
2Touch the UP or DOWN key within 15 s to select a label.
LAB.DESCRIPTION
Pb1probe 1 temperature
Pb2probe 2 temperature
3Touch the SET key.
4Touch the ON/STAND-BY key (or take no action for 60 s) to exit the procedure.

SETTINGS

Setting configuration parameters
1Touch the SET key for 4 s: the display will show the label “PA”.
2Touch the SET key.
3Touch the UP or DOWN key within 15 s to set the PAS value (default “-19”).
4Touch the SET key (or take no action for 15 s): the display will show the label “SP1”.
5Touch the UP or DOWN key to select a parameter.
6Touch the SET key.
7Touch the UP or DOWN key within 15 s to set the value.
8Touch the SET key (or take no action for 15 s).
9Touch the SET key for 4 s (or take no action for 60 s) to exit the procedure.
Restoring factory (default) settings and saving customised settings

N.B.

  • check that the factory settings are appropriate; see the section CONFIGURATION PARAMETERS.
  • saving customised settings overwrites the factory settings.
1Touch the SET key for 4 s: the display will show the label “PA”.
2Touch the SET key.
3Touch the UP or DOWN key within 15 s to set the value.
VAL. MEANING
149value for restoring the factory information (default)
161value for saving customised settings
4Touch the SET key (or take no action for 15 s): the display will show the label “dEF” (for setting the “149” value) or the label “MAP” (for setting the “161” value).
5Touch the SET key.
6Touch the UP or DOWN key within 15 s to set the value.
VAL. 1 MEANING
1controller with two independent regulators
2controller for refrigerated milk storage units
3controller for ice cream batch freezers
7Touch the SET key (or take no action for 15 s): the display will show “- – -” flashing for 4 s, after which the device will exit the procedure.
8Disconnect the device from the power supply.
9Touch the SET key for 2 s before action 6 to exit the procedure beforehand.

CONFIGURATION PARAMETERS

NO.PAR.DEF.SETPOINTMIN… MAX.
1SP10.0load 1 setpointrl… r2
2SP20.0load 2 setpointr7… r8
3SP30.0beater setpointr16… r17
NO.PAR.DEF.ANALOGUE INPUTSMIN… MAX.
4CAl0.0probe 1 offset-25… 25 °C/°F
5CA20.0probe 2 offset-25… 25 °C/°F
6PO1type of probe0 = PTC 1 = NTC
7P10enable decimal point °C0 = no 1 = yes
8P20temperature measurement unit0 = °C 1 = °F
9P32probe 1 function
not visible if P10 = 2
0 = disabled
1 = tank probe
2 = regulator 1
3 = condenser probe
10P42probe 2 function
not visible if PIO = 2
0 = disabled
1 = plate probe
2 = regulator 2
3 = condenser probe
11P50value displayed0 = probe 1 temperature
1 = probe 2 temperature
2 = load 1 setpoint
3 = load 2 setpoint
12P85display refresh time0… 250 s: 10
13R0enable quick settings block0 = disabled
1 = setpoint
2 = beater on/off times
3 = beater on/off setpoint + times
14P100operating logic0 = controller with two inde-
pendent regulators
1 = controller for refrigerated milk storage units
2 = controller for ice cream batch freezers
NO.PAR.DEF.REGULATIONMIN… MAX.
15r02.0load 1 setpoint differential1… 15 °C/°F
16rl-50load 1 minimum setpoint-99 °C/°F… r2
17r2500load 1 maximum setpointrl… 150 °C/°F
18r50hot or cold mode regulation regu- lator 10 = cold mode 1 = hot mode
19r62.0load 2 setpoint differential1… 15 °C/°F
20r7-50load 2 minimum setpoint-99 °C/°F… r8
21r8500load 2 maximum setpointr7… 150 °C/°F
22r91enable regulator 20 = no 1 = yes
if P10 = 1
23r100hot or cold mode regulation regu- lator 20 = cold mode 1 = hot mode
24r140beater mode in normal operation0 = parameter set to tO and tl
1 = parameter set to r19, tO, ti if the beater setpoint is not reached
25r150.5beater setpoint differential1… 15 °C/°F
26r16-50beater minimum setpoint-99 °C/°F… r17
27r1750beater maximum setpointr16… 150 °C/°F
28r190hot or cold mode regulation
beater
0 = cold mode 1 = hot mode
29r200beater mode in beater probe
alarm
0 = off
1 = set to tO and tl
30r210constraint between beater and
compressor
0 = disabled
1 = on if compressor on and parameter set to r14
2 = on if compressor off and parameter set to r14
3 = on if compressor on
NO.PAR.DEF.BEATERMIN… MAX.
31tO3beater off time0… 240 min
32tl2beater on time0… 240 min
33t20beater off delay from compressor off0… 240 min
34t310minimum beater on and off time0… 240 s
NO.PAR.DEF.LOADSMIN… MAX.
35CO3load 1 on delay from power-on0… 240 min
36Cl5delay between two load 1 switch- ons0… 240 min
37C23load 1 minimum off time0… 240 min
38C30load 1 minimum on time0… 240 s
39C410load 1 off time in probe 1 alarm0… 240 min if C6 = 2
40C515load 1 on time in probe 1 alarm0… 240 min if C6 = 2
41C63load 2 on delay from power-on and load 2 minimum off time0… 240 min
42C72load 2 minimum on time0… 240 s
43C85delay between two load 2 switch- ons0… 240 min
44C1010load 2 off time in probe 2 alarm0… 240 min if C6 = 2
45C1115load 2 on time in probe 2 alarm0… 240 min if C6 = 2
46C1380.0high condensation signal thresh- old
not visible if P10 = 2
0… 199 °C/°F differential = 2 °C/4 °F
47C1490.0high condensation alarm thresh- old0… 150 °C/°F
48C1560high condensation alarm delay0… 240 s
NO.PAR.DEF.DEFROSTING (if r5 = 0)MIN… MAX.
49dO8automatic defrost interval regula- for 1 and regulator 20… 99 h
0 = manual only
50d330defrost duration regulator 10… 99 min
51d40enable defrost at power-on0 = no 1 = yes
52d50defrost delay from power-on0… 99 min
53d62value displayed when defrosting0 = value P5 (if P5 = 0 or 1)
1 = value P5 (if P5 = 0 or 1)
at defrost activation
2 = label dEF
54d1030defrost duration regulator 20… 99 min
55d120constraint between defrost regu- lator 1 and defrost regulator 20 = disabled
1 = regulator defrost is acti-
vated only if defrost of the other regulator is not in progress. If it is, it waits for this to end.
NO.PAR.DEF.ALARMSMIN… MAX.
56Al–10.0low temperature alarm threshold probe 1-99… 150 °C/°F
57A21type of low temperature alarm probe 10 = disabled
1 = relative to load 1 setpoint
2 = absolute
58A410.0high temperature alarm threshold probe 1-99… 150 °C/°F
59AS1type of high temperature alarm probe 10 = disabled
1 = relative to load 1 setpoint
2 = absolute
60A612high temperature alarm delay
probe 1 from power-on
0… 99 minx10
61A715high/low temperature alarm delay probe 10… 240 min
62AS15high temperature alarm delay
probe 1 after defrosting regulator
1
0… 240 min
63A10– – –unused
64All–10.0low temperature alarm threshold probe 2-99… 150 °C/°F
65Al21type of low temperature alarm probe 20 = disabled
1 = relative to load 2 setpoint
2 = absolute
66A1410.0high temperature alarm threshold probe 2-99… 150 °C/°F
67A151type of high temperature alarm probe 20 = disabled
1 = relative to load 2 setpoint
2 = absolute
68A1612high temperature alarm delay
probe 2 from power-on
0… 99 minx10
69A1715high/low temperature alarm delay probe 20… 240 min
70A1815high temperature alarm delay
probe 2 after defrosting regulator
2
0… 240 min
71A192.0high/low temperature alarm reset differential1… 15 °C/°F
NO.PAR.DEF.DIGITAL INPUTSMIN… MAX.
72i20door switch/multi-purpose input alarm signal delay0… 120 min
73i30maximum compressor and beater off time with door switch/multipurpose input active0… 120 min
74i70door switch/multi-purpose input alarm activation delay0… 120 min
75i50door switch/multi-purpose input function0 = disabled
1 = compressor off
2 = beater off
3 = multi-purpose input
alarm
4 = switches device on/off
5 = thermal switch alarm
6 = door open alarm
76i60activation door switch/multi-pur- pose input0 = with contact closed
1 = with contact open
NO.PAR.DEF.DIGITAL OUTPUTSMIN… MAX.
77u13K1 relay configuration0 = compressor
1 = plate heaters
2 = beater
3 = load 1
4 = load 2
5 = alarm
78u24K2 relay configurationas ul
79u35K3 relay configurationas ul
80u41enable silencing alarm output0 = no 1 = yes
NO.PAR.DEF.BATCH FREEZERMIN… MAX.
81Snd-50threshold for neutral zone regula- tion during cooking99… 150 °C/°F
82d2n1.0neutral zone value0… 99.0 °C/°F
83r230.0minimum plate setpoint during batch freezing heating and cooking0 °C/°F… r24
84r24130maximum plate setpoint during batch freezing heating and cookingr23… 150 °C/°F
85r250.0minimum tank setpoint at end of batch freezing heating and batch freezing cooking setpoint0 0C/0F… r26
86r26pO
O
maximum tank setpoint at end of batch freezing heating and bat& freezing cooking setpointr25… 150 °C/°F
87r270.0minimum tank setpoint at end of batch freezing cooling and tank setpoint during conservation-2 0C/0F… r28
88r28130maximum tank setpoint at end of batch freezing cooling and tank setpoint during conservationr27… 60 0C/°F
89SAl50.0tank setpoint for beater on or on/off during batch freezing-99… 150 0C/°F differential = 5 0C/10 of
90PFd5.0difference in tank temperature af- ter power failure during batch freezing cooling or conservation due to reactivating heating1… 25 °C/°F
NO.PAR.DEF.BATCH FREEZING HEATINGMIN… MAX.
P 1OH2.0plate differential setpoint during batch freezing heating and plate setpoint during batch freezing cooking1… 25 °C/°F
921Z1freezing n1H0hours beater on during batch
heating
0… 23 h
93nln2minutes beater on during batch freezing heating0… 59 min
94n1S0seconds beater on during batch freezing heating0… 59 s
95FIH0hours beater off during batch
freezing heating
0… 23 h
96F1n2minutes beater off during batch freezing heating0… 59 min

EVCO S.p.A. | EV3143 | Instruction sheet ver. 1.0 | Code 1043143E103 | Page 3 of 3 | PT 22/19

97F1S0seconds beater off during batch freezing heating0… 59 s
2NO.PAR.DEF.BATCH FREEZING COOKINGMIN… MAX.
98SPC30.0plate setpoint during batch freez- ing cooking and plate setpoint during batch freezing cookingr23… r24
99SU230.0tank setpoint at end of batch freezing heating and tank setpoint during batch freezing cookingr25… r26
100r2H2.0tank differential setpoint during batch freezing cooking1… 25 °C/°F
101C2H1duration in hours of batch freezing cooking0… 23 h
102C2n0duration in minutes of batch
freezing cooking
0… 59 min
103C2S0duration in seconds of batch
freezing cooking
0… 59 s
104n2H0hours beater on during batch
freezing cooking
0… 23 h
105n2n2minutes beater on during batch freezing cooking0… 59 min
106n2S0seconds beater on during batch freezing cooking0… 59 s
107F2H0hours beater off during batch
freezing cooking
0… 23 h
108F2n2minutes beater off during batch freezing cooking0… 59 min
109F2S0seconds beater off during batch freezing cooking0… 59 s
3NO.PAR.DEF.BATCH FREEZING COOLINGMIN… MAX.
110SU330.0tank setpoint at end of batch
freezing cooling and tank setpoint during batch freezing conservation
r27… r28
111SA310.0tank setpoint for beater on at end of batch freezing cooking0… 25 °C/°F
112ZIfreezing
n3H
0hours beater on during batch
cooling
0… 23 h
113n3n2minutes beater on during batch freezing cooling0… 59 min
114n3S0seconds beater on during batch freezing cooling0… 59 s
115F3H0hours beater off during batch
freezing cooling
0… 23 h
116F3n2minutes beater off during batch freezing cooling0… 59 min
117F3S0seconds beater off during batch freezing cooling0… 59 s
4NO.PAR.DEF.BATCH FREEZING CONSERVA-
TION
MIN… MAX.
118r4H2.0tank differential setpoint during batch freezing conservation1… 25 °C/°F
119n4H0hours beater on during batch
freezing conservation
0… 23 h
120n4n2minutes beater on during batch freezing conservation0… 59 min
121n4S0seconds beater on during batch freezing conservation0… 59 s
122F4H0hours beater off during batch
freezing conservation
0… 23 h
123F4n2minutes beater off during batch freezing conservation0… 59 min
124F4S0seconds beater off during batch freezing conservation0… 59 s
125F4C0beater mode during batch freezing conservation0 = independent on the compressor
1 = on if compressor on, according to n4… and F4… if compressor off
NO.PAR.DEF.SECURITYMIN… MAX.
126H4E0timeout for locking the keypad0… 240 s
127POF1enable ON/STAND-BY key0 = no 1 = yes
128PAS-19password-99… 999
129PA1– – –unused
130PA2– – –unused
NO.PAR.DEF.UNUSEDMIN… MAX.
131Hr0– – –unused
NO.PAR.DEF.UNUSEDMIN… MAX.
132rE0– – –unused
133rEl– – –unused
NO.PAR.DEF.MODBUSMIN… MAX.
134LA247MODBUS address1… 247
135Lb2MODBUS baud rate0 = 2,400 baud
1 = 4,800 baud
2 = 9,600 baud
3 = 19,200 baud
136bLE– – –unused
NO.PAR.DEF.SECURITYMIN… MAX.
137bul0duration of buzzer activation
when setpoint reached
0… 240 s
138Pbu2enable buzzer0 = disabled
1 = keys only
2 = alarms only
3 = keys and alarms

ALARMS

CODEDESCRIPTIONRESETTO CORRECT
Pr1probe 1 alarmautomatic– check PO
– check integrity of the probe
– check electrical connection
Pr2probe 2 alarmautomatic
rtcunusedunusedunused
Alllow-temperature alarm
probe 1
automaticcheck Al and A2
AH1high-temperature alarm
probe 1
automaticcheck A4 and AS
AL2low-temperature alarm
probe 2
automaticcheck All and Al2
AH2high-temperature alarm
probe 2
automaticcheck A14 and A15
iddoor open alarmautomaticcheck i5 and i6
PFpower failure alarmmanual– touch a key
– check electrical connection
COHhigh condensation signalautomaticcheck C13
CSdhigh condensation alarmmanual– switch the device off and on – check C14
iAmulti-purpose input alarmautomaticcheck i5 and i6
itthermal switch alarmautomatic– switch the device off and on – check i5 and i6

TECHNICAL SPECIFICATIONS

Purpose of the control device:function controller.
Construction of the control device:built-in electronic device.
Housing:black, self-extinguishing.
Category of heat and fire resistance:D.
Measurements:
75.0 x 33.0 x 59.0 mm (2 15/16 x 1 5/16 x
2 5/16 in) with fixed screw terminal blocks
75.0 x 33.0 x 81.5 mm (2 15/16 x 1 5/16 x 3 3/16 in) with plug-in screw terminal blocks
Mounting methods for the control device:to be fitted to a panel, snap-in brackets provided
Degree of protection provided by the casing:IP65 (front).
Connection method:
fixed screw terminal blocks for
wires up to 2.5 mm²
plug-in screw terminal blocks
for wires up to 2.5 mm² (on
request)
Micro-MaTch connector
Maximum permitted length for connection cables:
power supply: 10 m (32.8 ft)analogue inputs: 10 m (32.8 ft)
digital inputs: 10 m (32.8 ft)digital outputs: 10 m (32.8 ft).
Operating temperature:from 0 to 55 °C (from 32 to 131 °F).
Storage temperature:from -25 to 70 °C (from -13 to 158 °F).
Operating humidity:relative humidity without condensate from 10
to 90%.
Pollution status of the control device:2
Compliance:
RoHS 2011/65/ECWEEE 2012/19/EUREACH (EC) Regulation
no. 1907/2006
EMC 2014/30/EULVD 2014/35/EU.
Power supply:
230 VAC (+10% -15%), 50/60 Hz (±3 Hz), max. 2 VA insulated in EV3143N7
115 VAC (+10% -15%), 50/60 Hz (±3 Hz), max. 2 VA insulated in EV3143N5.
Earthing methods for the control device:none.
Rated impulse-withstand voltage:4 KV.
Over-voltage category:III.
Software class and structure:A.
Analogue inputs:2 for PTC or NTC probes (probe 1 and probe 2).
PTC probes:Type of sensor:KTY 81-121 (990 W @ 25 °C, 77 °F)
Measurement field:from -50 to 150 °C (from -58 to 302 °F)
Resolution:0.1 °C (1 °F).
NTC probes:Type of sensor:ß3435 (10 KW @ 25 °C, 77 °F)
Measurement field:from -40 to 105 °C (from -40 to 221 °F)
Resolution:0.1 °C (1 °F).
Digital inputs:1 dry contact (door switch/multi-purpose).
Dry contact:Type of contact:5 VDC, 1.5 mA
Power supply:none
Protection:none.
Digital outputs:3 electromechanical relays.
K1 relay:SPST, 16 A res. @ 250 VAC
K2 relay:SPDT, 8 A res. @ 250 VAC.
K3 relay:SPST, 5 A res. @ 250 VAC.
Type 1 or Type 2 actions:type 1.
Additional features of Type 1 or Type 2 actions:C.
Displays:custom display, 3 digits, with function icons.
Alarm buzzer:built-in.
Communications ports:1 TTL MODBUS slave port for BMS.

N.B.
The device must be disposed of according to local regulations governing the collection of electrical and electronic equipment.

This document and the solutions contained therein are the intellectual property of EVCO and thus protected by the Italian Intellectual Property Rights Code (CPI). EVCO imposes an absolute ban on the full or partial reproduction and disclosure of the content other than with the express approval of EVCO. The customer (manufacturer, installer, or end-user) assumes all responsibility for the configuration of the device. EVCO accepts no liability for any possible errors in this document and reserves the right to make any changes at any time without prejudice to the essential functions and safety features of the equipment.

EVCO - Logo
EVCO S.p.A.
Via Feltre 81, 32036 Sedico (BL) ITALY
Tel. +39 0437/8422 | Fax +39 0437/83648
email [email protected] | web www.evco.it

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals